Product Model

PLC-RSP- 48DC/21AU

In Stock
Last updated: 2025/4/25
Phoenix Contact PLC-RSP- 48DC/21AU

Selling Points

  • 1Slim Design: Compact and space-efficient, perfect for control cabinets.
  • 2Safe Isolation: Ensures safe operation with DIN EN 50178 compliance between coil and contact.
  • 3Efficient Connection: Uses V8 adapter for easy and efficient connection to system cabling.
  • 4High Reliability: Integrated input circuit and interference suppression circuit for reliable operation.
  • 5Durable Construction: Built with gold-plated AgSnO terminals for long-lasting performance.
Product Details
PLC-RSP- 48DC/21AU
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Relay Module
Product family
PLC-INTERFACE
Application
Universal
Operating mode
100% operating factor
Mechanical service life
2x 10
Date of last data management
10.10.2023
Overvoltage category
III
Pollution degree
3
Maximum power dissipation for nominal condition
0.44 W
Test voltage (Winding/contact)
4 kV AC (50 Hz, 1 min., winding/contact)
Nominal input voltage U
48 V DC
Input voltage range
37.4 V DC ... 60 V DC
Typical input current at U
9.2 mA
Typical response time
5 ms
Typical release time
8 ms
Protective circuit
Reverse polarity protection; Polarity protection diode Freewheeling diode; Freewheeling diode
Operating voltage display
Yellow LED
Contact switching type
1 changeover contact
Type of switch contact
Single contact
Contact material
AgSnO, hard gold-plated
Maximum switching voltage
30 V AC 36 V DC
Minimum switching voltage
100 mV (at 10 mA)
Limiting continuous current
50 mA
Maximum inrush current
50 mA
Min. switching current
1 mA (at 24 V)
Interrupting rating (ohmic load) max.
1.2 W (at 24 V DC)
Note
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
5 V (at 100 mA)
Limiting continuous current
6 A
Min. switching current
10 mA (at 12 V)
Interrupting rating (ohmic load) max.
140 W (at 24 V DC) 20 W (at 48 V DC) 18 W (at 60 V DC) 23 W (at 110 V DC) 40 W (at 220 V DC) 1500 VA (for 250 V AC)
Switching capacity
2 A (at 24 V, DC13) 0.2 A (at 110 V, DC13) 0.1 A (at 220 V, DC13) 3 A (at 24 V, AC15) 3 A (at 120 V, AC15) 3 A (at 230 V, AC15)
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Width
6.2 mm
Height
80 mm
Depth
94 mm
Color
green (RAL 6021)
Flammability rating according to UL 94
V0 (Housing)
Degree of protection (Relay base)
IP20 (Relay base)
Ambient temperature (operation)
-40 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Standards/regulations
IEC 60664 IEC 60947-5-1
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice