Product Model

PLC-SP-EIK 1-SVN 24P/P

In Stock
Last updated: 2025/4/26
Phoenix Contact PLC-SP-EIK 1-SVN 24P/P

Selling Points

  • 1Reliable NAMUR Application: Designed for NAMUR proximity sensors applications.
  • 2High Output Current: Handles 50mA output current.
  • 3Efficient Power Consumption: Max current consumption approx. 70mA at 50mA output.
  • 4Enhanced Safety Features: Includes reverse polarity protection and surge protection.
  • 5Easy Installation: Compatible with PLC-V8 adapter and DIN rail mounting.
Product Details
PLC-SP-EIK 1-SVN 24P/P
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Solid-state relay module
Product family
PLC-INTERFACE
Application
NAMUR proximity sensors
Operating mode
100% operating factor
Date of last data management
13.10.2023
Article revision
04
Insulation
Basic insulation
Overvoltage category
I
Pollution degree
2
Maximum power dissipation for nominal condition
0.34 W
Rated insulation voltage
50 V DC
Rated surge voltage
0.4 kV
Nominal input voltage U
8.2 V DC ±10 %
Protective circuit
Surge protection; Suppressor diode
Non-load voltage
8.2 V DC ±10 %
Switching point
≥ 2.1 mA (In conductive state) ≤ 1.2 mA (In blocking state) 6.3 mA ... 10 mA (in the event of a short-circuit) 0 mA ... 0.35 mA (In the event of a wire break)
Switching hysteresis
approx. 0.2 mA
Internal resistance
approx. 1 kΩ
Cable length
< 30 m
Designation
Signal output
Contact switching type
1 N/O contact
Design of digital output
electronic
Output nominal voltage
≤ 100 mV (In conductive state) U
Limiting continuous current
50 mA
Transmission frequency
approx. 350 Hz
Voltage drop at max. limiting continuous current
≤ 1.5 V (U
Status display
LED (green)
Error indication
Red LED
Protective circuit
Surge protection; Suppressor diode
Designation
Alarm output
Output nominal voltage
U
Limiting continuous current
50 mA
Voltage drop at max. limiting continuous current
≤ 2 V (U
Error indication
Red LED
Protective circuit
Surge protection; Suppressor diode
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Width
6.2 mm
Height
80 mm
Depth
86 mm
Color
green (RAL 6021)
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 50 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Standards/regulations
IEC 60664 EN 50178
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice