Product Model
PTVC 2,5-MT

Selling Points
- 1Multi-level design: The PTVC 2,5-MT features a multi-level disconnect terminal block for efficient potential distribution.
- 2Customizable: Intuitive configuration and intelligent functions allow for easy planning and marking of terminal strips.
- 3Robust Construction: Built with high-quality materials, ensuring durability and reliability in demanding electrical environments.
- 4Versatile Mounting Options: Compatible with NS 35/7,5, NS 35/15, and NS 32 mounting types for flexible installation.
- 5Easy Connection: Push-in connection method simplifies wiring without the need for tools, reducing installation time and effort.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Note | The maximum load current of a single clamping unit must not be exceeded. | Product type | Disconnect terminal block |
Number of connections | 2 | Number of rows | 1 |
Potentials | 1 | Article revision | 03 |
Overvoltage category | III | Degree of pollution | 3 |
Rated surge voltage | 6 kV | Maximum power dissipation for nominal condition | 0.77 W |
Number of connections per level | 2 | Nominal cross section | 2.5 mm² |
Stripping length | 8 mm ... 10 mm | Internal cylindrical gage | A3 |
Connection in acc. with standard | IEC 60947-7-1 | Conductor cross section rigid | 0.14 mm² ... 4 mm² |
Cross section AWG | 26 ... 12 (converted acc. to IEC) | Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section, flexible [AWG] | 26 ... 14 (converted acc. to IEC) | Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² | Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve) | 0.5 mm² ... 1 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 1 mm² | Nominal current | 20 A (at 2.5 mm²) |
Maximum load current | 20 A (with 4 mm² conductor cross section, rigid) | Nominal voltage | 400 V |
Nominal cross section | 2.5 mm² | Conductor cross section rigid | 1 mm² ... 4 mm² |
Conductor cross-section flexible (ferrule without plastic sleeve) | 2.5 mm² ... | Flexible conductor cross section (ferrule with plastic sleeve) | 2.5 mm² ... |
Width | 5.2 mm | End cover width | 2.2 mm |
Height | 50.8 mm | Depth | 35.3 mm |
Depth on NS 35/7,5 | 36.8 mm | Depth on NS 35/15 | 44.3 mm |
Color | gray (RAL 7042) | Flammability rating according to UL 94 | V0 |
Insulating material group | I | Insulating material | PA |
Static insulating material application in cold | -60 °C | Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C | Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 | Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 | Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Surface flammability NFPA 130 (ASTM E 162) | passed | Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed | Result | Test passed |
Requirement temperature-rise test | Increase in temperature ≤ 45 K | Result | Test passed |
Short-time withstand current 2.5 mm² | 0.3 kA | Result | Test passed |
Test voltage setpoint | 1.89 kV | Result | Test passed |
Open side panel | Yes | Result | Test passed |
DIN rail/fixing support | NS 35 | Result | Test passed |
Rotation speed | 10 rpm | Revolutions | 135 |
Conductor cross section/weight | 0.14 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg | Result | Test passed |
Temperature cycles | 192 | Result | Test passed |
Time of exposure | 30 s | Result | Test passed |
Specification | DIN EN 50155 (VDE 0115-200):2018-05 | Spectrum | Service life test category 2, bogie-mounted |
Frequency | f | ASD level | 6.12 (m/s²)²/Hz |
Acceleration | 3.12g | Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis | Result | Test passed |
Pulse shape | Half-sine | Acceleration | 30g |
Shock duration | 18 ms | Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) | Result | Test passed |
Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) | Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C ... 70 °C | Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (operation) | 20 % ... 90 % | Permissible humidity (storage/transport) | 30 % ... 70 % |
Connection in acc. with standard | IEC 60947-7-1 | Mounting type | NS 35/7,5
NS 35/15 |
Specifications may be subject to change without notice