Product Model
PTVFIX 6/18X2,5-G GY

Selling Points
- 1Time-saving Push-in connections for quick conductor connection.
- 2Flexible mounting options including DIN rail, direct, and adhesive mounting.
- 3Space savings of up to 50% on the DIN rail with transverse mounting.
- 4High reliability with flammability rating according to UL 94 V0.
- 5Compliance with IEC 60947-7-1 standards for secure connections.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Distributor terminal block | Number of positions | 1 |
Number of connections | 19 | Number of rows | 1 |
Potentials | 1 | Article revision | 02 |
Overvoltage category | III | Degree of pollution | 3 |
Rated surge voltage | 8 kV | Maximum power dissipation for nominal condition | 0.77 W |
Service Entrance | yes | Number of connections per level | 19 |
Nominal cross section | 2.5 mm² | Stripping length | 8 mm ... 10 mm |
Internal cylindrical gage | A3
B3 | Connection in acc. with standard | IEC 60998-2-2 |
Conductor cross section rigid | 0.14 mm² ... 4 mm² | Cross section AWG | 26 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.14 mm² ... 4 mm² | Conductor cross section, flexible [AWG] | 26 ... 12 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² | Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Nominal current | 24 A | Maximum load current | 32 A (with 4 mm² conductor cross section) |
Maximum total current | 57 A (with 10 mm² conductor cross section) | Nominal voltage | 450 V |
Nominal cross section | 2.5 mm² | Stripping length | 10 mm ... 12 mm |
Internal cylindrical gage | A5
B4 | Conductor cross section rigid | 0.5 mm² ... 10 mm² |
Cross section AWG | 20 ... 8 (converted acc. to IEC) | Conductor cross section flexible | 0.5 mm² ... 10 mm² |
Conductor cross section, flexible [AWG] | 20 ... 8 (converted acc. to IEC) | Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 6 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 6 mm² | Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve) | 0.5 mm² ... 1.5 mm² |
Nominal current | 41 A (with 6 mm² conductor cross section) | Maximum load current | 57 A (with 10 mm² conductor cross section) |
Nominal cross section | 6 mm² | Conductor cross section rigid | 0.34 mm² ... 4 mm² |
Conductor cross section, rigid [AWG] | 26 ... 12 (converted acc. to IEC) | Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.34 mm² ... 2.5 mm² | Conductor cross section rigid | 0.5 mm² ... 10 mm² |
Conductor cross section, rigid [AWG] | 18 ... 8 (converted acc. to IEC) | Conductor cross-section flexible (ferrule without plastic sleeve) | 1 mm² ... 6 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 1 mm² ... 6 mm² | Width | 56.9 mm |
Height | 28.6 mm | Depth | 21.7 mm |
Color | gray (RAL 7042) | Flammability rating according to UL 94 | V0 |
Insulating material group | I | Insulating material | PA |
Open side panel | No | Ambient temperature (operation) | -35 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C) | Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C | Permissible humidity (operation) | 20 % ... 90 % |
Permissible humidity (storage/transport) | 30 % ... 70 % | Connection in acc. with standard | IEC 60998-2-2 |
Mounting type | adhesive |
Specifications may be subject to change without notice