Product Model
PTVFIX 6X2,5 GY

Selling Points
- 1Mounting options include DIN rail, direct mounting, and adhesive mounting.
- 2Eleven different color variants for easy identification.
- 3Rated surge voltage of 6 kV and maximum power dissipation of 0.77 W.
- 4Supports rigid and flexible conductors from 0.14 mm² to 4 mm².
- 5Nominal current of 24 A and maximum load current of 32 A.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Note | The maximum load current of a single clamping unit must not be exceeded. | Product type | Distributor terminal block |
Number of positions | 1 | Number of connections | 6 |
Number of rows | 1 | Article revision | 02 |
Overvoltage category | III | Degree of pollution | 3 |
Rated surge voltage | 8 kV | Maximum power dissipation for nominal condition | 0.77 W |
Number of connections per level | 6 | Nominal cross section | 2.5 mm² |
Stripping length | 8 mm ... 10 mm | Internal cylindrical gage | A3
B3 |
Connection in acc. with standard | IEC 60998-2-2 | Conductor cross section rigid | 0.14 mm² ... 4 mm² |
Cross section AWG | 26 ... 12 (converted acc. to IEC) | Conductor cross section flexible | 0.14 mm² ... 4 mm² |
Conductor cross section, flexible [AWG] | 26 ... 12 (converted acc. to IEC) | Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² | Nominal current | 24 A |
Maximum load current | 32 A (with 4 mm² conductor cross-section) | Maximum total current | The maximum load current of the individual terminal point must not be exceeded. |
Nominal voltage | 450 V | Nominal cross section | 2.5 mm² |
Conductor cross section rigid | 0.5 mm² ... 4 mm² | Conductor cross section, rigid [AWG] | 20 ... 12 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.75 mm² ... 2.5 mm² | Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Width | 15.7 mm | Height | 28.6 mm |
Depth | 21.7 mm | Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 | Insulating material group | I |
Insulating material | PA | Static insulating material application in cold | -60 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C | Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 | Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 | Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Surface flammability NFPA 130 (ASTM E 162) | passed | Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed | Open side panel | No |
DIN rail/fixing support | NS 35/NS 15 | Result | Test passed |
Note | When aligning several blocks, it is recommended to either place a DIN rail adapter underneath the connection point or a flange element between the blocks.
For versions with 6 or 7 connections, it is enough to place one DIN rail adapter centrally per block and place flange elements after every other block.
Depending on the application case and mechanical load, other arrangements of the mounting accessory can also be chosen.
When using the DIN rail adapter PTFIX-NS35, an aligned block must not protrude by more than a half. | Time of exposure | 30 s |
Result | Test passed | Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
Spectrum | Service life test category 2, bogie-mounted | Frequency | f |
ASD level | 6.12 (m/s²)²/Hz | Acceleration | 3.12g |
Test duration per axis | 5 h | Test directions | X-, Y- and Z-axis |
Result | Test passed | Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
Pulse shape | Half-sine | Acceleration | 30g |
Shock duration | 18 ms | Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) | Result | Test passed |
Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) | Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C) |
Ambient temperature (assembly) | -5 °C ... 70 °C | Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (operation) | 20 % ... 90 % | Permissible humidity (storage/transport) | 30 % ... 70 % |
Connection in acc. with standard | IEC 60998-2-2 | Mounting type | for snapping onto a DIN rail adapter
Direct mounting with flange
Free-hanging |
Specifications may be subject to change without notice