Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Input voltage
24 V DC (SELV)
Input voltage range
22.5 V DC ... 30 V DC
Fixed backup threshold
< 22 V DC
Current consumption I
4.3 A
Current consumption I
0.08 A
Current consumption I
0.43 A
Buffer time
9 s (3.8 A) 30 s (1 A)
Charging time
4 min (0.43 A)
Recharging time
3 min (0.43 A)
Efficiency
> 97 % (with charged energy storage device)
Connection in parallel
yes max. 2 (with decoupling module)
Connection in series
no
Output voltage
24 V DC (depending on the input voltage)
Output current I
3.8 A
Output power P
91.2 W
Maximum no-load power dissipation
< 2 W
Output voltage
24 V DC
Output current I
3.8 A
Capacity
1 kJ
Storage medium
Double-layer capacitor
Buffer time
9 s (3.8 A) 30 s (1 A)
Connection method
Push-in connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm²
rigid (AWG)
24 ... 14
Stripping length
10 mm
Connection method
Push-in connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm²
rigid (AWG)
24 ... 14
Stripping length
10 mm
Connection method
Push-in connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm²
rigid (AWG)
24 ... 14
Stripping length
10 mm
Connection labeling
3.3
State (configurable)
Remote
State condition
Remote
Connection labeling
3.1
Switching output
Transistor output, active
State (configurable)
U
Output voltage
24 V (U
Output can be loaded
20 mA
LED status indicator
green (U
Signal threshold
Input voltage in the valid range
Connection labeling
3.2
Switching output
Transistor output, active
State (configurable)
Ready
State condition (configurable)
State of charge = 100% or buffer mode
Output voltage
24 V (U
Output can be loaded
20 mA
Connection labeling
3.4
Function
Signal ground
Reference potential
U
Insulation voltage input, output / housing
500 V
Product type
DC UPS with integrated capacitor
Product family
QUINT capacity module
MTBF (IEC 61709, SN 29500)
996550 h (40 °C) 1631804 h (25 °C) 449865 h (60 °C)
Article revision
02
Protection class
III
Overvoltage category
II
Degree of pollution
2
Width
85 mm
Height
102.5 mm
Depth
90 mm
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Mounting type
DIN rail mounting
Assembly note
alignable: horizontally 0 mm, vertically 50 mm
Mounting position
Any, on NS 35 DIN rail
Housing material
Plastic
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 60 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 4000 m
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 %
Identification
UL Listed UL 61010-1
Identification
UL Listed UL 61010-2-201
Identification
UL 121201
Identification
CSA C22.2 No. 223 class 2 (buffer mode)
Identification
CAN/CSA-C22.2 No. 61010-1-12
Identification
CAN/CSA C22.2 No. 61010-2-201:14
Identification
CSA C22.2 No. 213-17
Identification
UL 1310 class 2 (buffer mode)
Identification
IEC 61010-1 IEC 61010-2-201 EN 61010-1 EN 61010-2-201
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Noise emission
EN 61000-6-3
Standards/regulations
EN 61000-4-2
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 6 GHz
Test field strength
10 V/m
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Output
1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 1 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice