Product Model

QUINT4-CHARGER/1AC/24DC/10

In Stock
Last updated: 2025/4/17
Phoenix Contact QUINT4-CHARGER/1AC/24DC/10

Selling Points

  • 1High efficiency up to 91% for optimal power utilization.
  • 2Adjustable output voltage range from 19.2V to 28.6V DC.
  • 3Nominal output current of 10A for reliable charging.
  • 4Compact design with DIN rail mounting for easy installation.
  • 5Short-circuit and no-load proof for enhanced safety.
Product Details
QUINT4-CHARGER/1AC/24DC/10
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Charger
Product family
QUINT CHARGER
MTBF (IEC 61709, SN 29500)
> 500000 h (230 V AC, at 40 °C)
Article revision
02
Protection class
I
Degree of pollution
2
Number of phases
1.00
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
Derating
< 90 V AC (2.5 %/V)
Frequency range (f
50 Hz ... 60 Hz ±10 %
Current consumption
2.7 A (100 V AC) 1.2 A (240 V AC)
Input fuse
6.3 A (internal (device protection), slow-blow)
Recommended breaker for input protection
10 A ... 16 A (AC: Characteristic B, C, D, K, or comparable)
Input voltage range
110 V DC ... 250 V DC
Current consumption
2.4 A (110 V DC) 1.1 A (250 V DC)
Designation
Remote / Service
Efficiency
89 % 91 %
Nominal output voltage
24 V DC
Setting range of the output voltage (U
19.2 V DC ... 28.6 V DC
Nominal output current (I
10 A
Residual ripple
< 20 mV
Short-circuit-proof
yes
No-load proof
yes
Output power
240 W
Maximum no-load power dissipation
< 4 W (at 230 V AC)
Power loss nominal load max.
< 35 W (at 230 V AC)
Connection in parallel
no
Connection in series
no
Output voltage
24 V DC
Continuous load current
20 mA
Signal ground SGnd
Reference ground signal contacts
Output voltage
24 V DC
Continuous load current
20 mA
Signal ground SGnd
Reference ground signal contacts
Output voltage
24 V DC
Continuous load current
20 mA
Signal ground SGnd
Reference ground signal contacts
Nominal voltage U
24 V DC
Charging voltage
max. 32 V DC
Charging current
typ. 10 A
Nominal capacity range
7 Ah ... 300 Ah
Battery technology
VRLA, VRLA-WTR, LI-ION (LiFePO
Charge characteristic curve
IU
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
6.5 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
6.5 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
1.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
Interface
MINI-USB type B
Signalization designation
U
Status display
LED (green)
Signalization designation
Bat.-Voltage OK
Status display
LED (green)
Signalization designation
Alarm
Status display
LED (red)
Signalization designation
Reference potential for the signal inputs and outputs
Width
60 mm
Height
130 mm
Depth
126 mm
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Width
123 mm
Height
130 mm
Depth
63 mm
Housing material
Metal
Hood version
High-grade steel plate
Side element version
Aluminum
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 4000 m (> 2000 m, observe derating)
Climatic class
3K3 (EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at +25 °C, non-condensing)
Shock
30g, 18 ms in accordance with IEC 60068-2-27
Vibration (operation)
2 Hz ... 15 Hz, ±2.5 mm amplitude; 15 Hz ... 150 Hz, 2.3g
UL approvals
UL Listed UL 61010-1 UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C
Identification
UL Listed UL 61010
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Interference emission
Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise immunity
Immunity in accordance with EN 61000-6-2 (industrial)
Conducted noise emission
EN 61000-6-3 (Class B)
Noise emission
EN 61000-6-3 (Class B)
Frequency range
0 kHz ... 2 kHz
Standards/regulations
EN 61000-4-2
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
1 kV (Test Level 2 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Output
0.5 kV (Test Level 1 - symmetrical) 1 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Standard – Safety extra-low voltage
IEC 61010 (SELV) / (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - safety for equipment for measurement, control, and laboratory use
IEC 61010-1
EN 61010-1
II
Mounting type
DIN rail mounting

Specifications may be subject to change without notice