Phoenix Contact QUINT4-PS/1AC/12DC/2.5/PT

Selling Points

  • 1Dynamic Boost for Heavy Loads: Starts heavy loads quickly with dynamic boost technology.
  • 2Preventive Function Monitoring: Indicates critical operating states before errors occur, ensuring proactive maintenance.
  • 3High Efficiency and Long Service Life: Operates with high efficiency and long service life, minimizing power dissipation and heating.
  • 4Space-Saving Design: Narrow, slim-line design saves space in control cabinets.
  • 5Easy Installation: Tool-free Push-in connection technology for fast and easy startup.
Product Details
QUINT4-PS/1AC/12DC/2.5/PT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
Electric strength, max.
300 V AC 60 s
Typical national grid voltage
120 V AC 230 V AC
Voltage type of supply voltage
AC/DC
Inrush current
typ. 11.3 A (at 25 °C)
Inrush current integral (I
< 0.1 A
Inrush current limitation
< 11.3 A
Frequency range (f
50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time
typ. 54 ms (120 V AC) typ. 54 ms (230 V AC)
Current consumption
0.44 A (100 V AC) 0.35 A (120 V AC) 0.19 A (230 V AC) 0.2 A (240 V AC)
Nominal power consumption
32.8 VA
Protective circuit
Transient surge protection; Varistor
Typical response time
500 ms
Input fuse
3.15 A (slow-blow, internal)
Recommended breaker for input protection
6 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE
< 0.25 mA (264 V AC, 60 Hz) < 0.16 mA
Input voltage range
110 V DC ... 250 V DC -20 % ... +40 %
Voltage type of supply voltage
AC/DC
Current consumption
0.4 A (110 V DC) 0.17 A (250 V DC)
Efficiency
typ. 89.5 % (120 V AC) typ. 90.9 % (230 V AC)
Nominal output voltage
12 V DC
Setting range of the output voltage (U
12 V DC ... 15 V DC (constant capacity)
Nominal output current (I
2.5 A
Static Boost (I
3.125 A (≤ 40 °C)
Dynamic Boost (I
4.5 A (≤ 60 °C (5 s))
Feedback voltage resistance
≤ 25 V DC
Protection against overvoltage at the output (OVP)
≤ 18 V DC
Control deviation
< 0.2 % (Static load change 10 % ... 90 %) < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) < 0.1 % (change in input voltage ±10 %)
Residual ripple
< 30 mV
Short-circuit-proof
yes
No-load proof
yes
Output power
30 W 38 W 54 W
Maximum no-load power dissipation
< 0.4 W (230 V AC) < 0.5 W (120 V AC)
Power loss nominal load max.
< 3.5 W (120 V AC) < 3 W (230 V AC)
Crest factor
typ. 1.89 (120 V AC) typ. 1.97 (230 V AC)
Rise time
50 ms (U
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Digital
0 V DC 12 V DC 24 mA
Default
12 V DC 24 mA 12 V DC for U
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Types of signaling
LED
P
> P
U
> 0.9 x U < 0.9 x U
Number of phases
1.00
Insulation voltage input/output
4 kV AC (type test) 3 kV AC (routine test)
Switching frequency
4.00 kHz ... 70.00 kHz (Auxiliary converter stage) 80.00 kHz ... 190.00 kHz (Main converter stage) 30.00 kHz ... 150.00 kHz (PFC stage)
Product type
Power supply
Product family
QUINT POWER
MTBF (IEC 61709, SN 29500)
> 1848000 h (25 °C) > 1060000 h (40 °C) > 459000 h (60 °C)
Article revision
03
Protection class
II
Degree of pollution
2
Current
2.5 A
Temperature
40 °C
Time
149000 h
Additional text
120 V AC
Current
2.5 A
Temperature
40 °C
Time
211000 h
Additional text
230 V AC
Current
2.5 A
Temperature
25 °C
Time
424000 h
Additional text
120 V AC
Current
2.5 A
Temperature
25 °C
Time
609000 h
Additional text
230 V AC
Width
22.5 mm
Height
106 mm
Depth
90 mm
Installation distance right/left (active)
15 mm / 15 mm (P
Installation distance right/left (passive)
5 mm / 5 mm (P
Installation distance right/left (active, passive)
0 mm / 0 mm (P
Installation distance top/bottom (active)
30 mm / 30 mm (P
Installation distance top/bottom (passive)
30 mm / 30 mm (P
Installation distance top/bottom (active, passive)
30 mm / 30 mm (P
Mounting type
DIN rail mounting
With protective coating
no
Flammability rating according to UL 94 (housing / terminal blocks)
V0
Housing material
Plastic
Type of housing
Polycarbonate
Hood version
Polycarbonate
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 5000 m (> 2000 m, observe derating)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6)
Temp code
T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K)
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard – Safety extra-low voltage
IEC 61010-1 (SELV) IEC 61010-2-201 (PELV)
Standard - Safe isolation
IEC 61558-2-16 IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use
IEC 61010-1 IEC 61010-2-201 (SELV)
Standard - Safety of transformers
EN 61558-2-16
EN 61010-1
II (≤ 5000 m)
EN 62477-1
III (≤ 2000 m)
SIQ
CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals
UL Listed UL 61010-1 UL Listed UL 61010-2-201 UL 1310 Class 2 Power Units UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
EMC requirements for power supply
IEC 61850-3 (G,H) EN 61000-6-5 (switching devices)
Conducted noise emission
EN 55016 EN 61000-6-3 (Class B)
Noise emission
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission
EN 55016 EN 61000-6-3 (Class B)
Standards/regulations
EN 61000-3-2 EN 61000-3-2 (Class A)
Frequency range
0 kHz ... 2 kHz
Standards/regulations
EN 61000-3-3
Frequency range
0 kHz ... 2 kHz
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Comments
Criterion A
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m (Test Level X)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
4 kV (Test Level 4 - asymmetrical)
Output
4 kV (Test Level X - asymmetrical)
Signal
4 kV (Test Level X - asymmetrical)
Comments
Criterion A
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Output
0.5 kV (Test Level 2 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Signal
0.5 kV (Test Level 1 - asymmetrical) 0.5 kV (Test Level 2 - symmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-8
Frequency
16.67 Hz 50 Hz 60 Hz
Test field strength
100 A/m
Additional text
60 s
Comments
Criterion A
Frequency
50 Hz 60 Hz
Frequency range
50 Hz ... 60 Hz
Test field strength
1 kA/m
Additional text
3 s
Frequency
0 Hz
Test field strength
300 A/m
Additional text
DC, 60 s
Standards/regulations
EN 61000-4-11
Voltage
100 V AC
Frequency
60 Hz
Voltage dip
70 %
Number of periods
0.5 / 1 / 30 periods
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
40 %
Number of periods
5 / 10 / 50 periods
Additional text
Test Level 2
Comments
Criterion B
Voltage dip
0 %
Number of periods
0.5 / 1 / 5 / 50 periods
Additional text
Test Level 2
Comments
Criterion B
Standards/regulations
EN 61000-4-9
Test field strength
1000 A/m
Comments
Criterion A
Standards/regulations
EN 61000-4-12
Input
2 kV (symmetrical) 4 kV (asymmetrical)
Comments
Criterion A
Standards/regulations
EN 61000-4-16
Test level 1
16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage
30 V (10 s)
Test level 2
16.67 Hz 50 Hz 60 Hz (Test Level 2)
Voltage
300 V (1 s)
Comments
Criterion A
Standards/regulations
EN 61000-4-18
Voltage
1 kV (symmetrical) 2.5 kV (asymmetrical) 1 kV (symmetrical)
Comments
Criterion A
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Specifications may be subject to change without notice