Product Model

QUINT4-PS/3AC/24DC/20/CO

In Stock
Last updated: 2025/4/19
Phoenix Contact QUINT4-PS/3AC/24DC/20/CO

Selling Points

  • 1Provides 6 times the nominal current for 15 ms and up to 125% static boost for sustained periods.
  • 2Features a high degree of electrical immunity with an integrated gas-filled surge arrester (6 kV) and ≥ 20 ms mains failure buffer time.
  • 3Offers analog signal, digital signal, relay contact, and LED bar graph for preventive function monitoring.
  • 4Supports dynamic boost of up to 200% for 5 seconds, ensuring reliable heavy load startup.
  • 5Facilitates seamless integration into industrial networks with direct connection to QUINT UPS or CAPAROC circuit breaker systems.
Product Details
QUINT4-PS/3AC/24DC/20/CO
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Control input (configurable) Rem
Output power ON/OFF (SLEEP MODE)
Default
Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
Network type
Star network
Nominal input voltage range
3x 400 V AC ... 500 V AC 2x 400 V AC ... 500 V AC
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +10 % 2x 400 V AC ... 500 V AC -10 % ... +10 %
Typical national grid voltage
400 V AC 480 V AC
Voltage type of supply voltage
AC
Inrush current
typ. 2 A (at 25 °C)
Inrush current integral (I
< 0.1 A
Inrush current limitation
2 A (after 1 ms)
AC frequency range
50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (f
50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time
typ. 33 ms (3x 400 V AC) typ. 33 ms (3x 480 V AC)
Current consumption
3x 0.99 A (400 V AC) 3x 0.81 A (480 V AC) 2x 1.62 A (400 V AC) 2x 1.37 A (480 V AC) 3x 0.8 A (500 V AC) 2x 1.23 A (500 V AC)
Nominal power consumption
541 VA
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi)
0.94
Switch-on time
< 1 s
Typical response time
300 ms (from SLEEP MODE)
Recommended breaker for input protection
3x 4 A ... 20 A (Characteristic B, C or comparable)
Recommended fuse for input protection
≥ 300 V AC
Discharge current to PE
< 3.5 mA 1.7 mA (550 V AC, 60 Hz)
Nominal input voltage range
± 260 V DC ... 300 V DC
Input voltage range
± 260 V DC ... 300 V DC -13 % ... +30 %
Voltage type of supply voltage
DC
Current consumption
1.23 A (± 260 V DC) 1.06 A (±300 V DC)
Recommended breaker for input protection
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection
≥ 1000 V DC
Efficiency
typ. 93.9 % (400 V AC) typ. 93.8 % (480 V AC)
Output characteristic
U/I Advanced Smart HICCUP FUSE MODE
Nominal output voltage
24 V DC
Setting range of the output voltage (U
24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (I
20 A
Static Boost (I
25 A
Dynamic Boost (I
30 A (5 s)
Selective Fuse Breaking (I
120 A (15 ms)
Magnetic circuit breaker tripping
A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Derating
> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
≤ 32 V DC
Control deviation
< 0.5 % (Static load change 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, (10 Hz)) < 0.25 % (change in input voltage ±10 %)
Residual ripple
< 60 mV
Short-circuit-proof
yes
No-load proof
yes
Output power
480 W 600 W 720 W
Apparent power
686 VA (400 V, U 698 VA (480 V, U
Maximum no-load power dissipation
< 7 W (400 V AC) < 7 W (480 V AC)
Power loss nominal load max.
< 32 W (400 V AC) < 33 W (480 V AC)
Power dissipation SLEEP MODE
< 5 W (400 V AC) < 5 W (480 V AC)
Crest factor
typ. 1.78 (400 V AC) typ. 2.1 (480 V AC)
Rise time
< 80 ms (U
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Signal ground SGnd
Reference potential for Out1, Out2, and Rem
Digital
24 V DC 20 mA
Default
24 V DC 20 mA 24 V DC for U
Digital
24 V DC 20 mA
Analog
4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Default
24 V DC 20 mA 24 V DC for P
Default
closed (U
Digital
24 V DC 1 A 30 V AC/DC 0.5 A
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
4 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
10
Stripping length
8 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
4 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
10
Stripping length
8 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
1 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
Types of signaling
LED Floating signal contact Active signal output Out1 (digital, configurable) Active signal output Out2 (analog, configurable) Remote contact Signal ground SGnd
P
> 100 % (LED lights up yellow, output power > 480 W) > 75 % (LED lights up green, output power > 360 W) > 50 % (LED lights up green, output power > 240 W)
U
> 0.9 x U < 0.9 x U
Number of phases
3.00
Insulation voltage input/output
4 kV AC (type test) 2.4 kV AC (routine test)
Insulation voltage output / PE
0.5 kV DC (type test) 0.5 kV DC (routine test)
Insulation voltage input / PE
3.5 kV AC (type test) 2.4 kV AC (routine test)
Switching frequency
90.00 kHz ... 110.00 kHz (Auxiliary converter stage) 56.00 kHz ... 500.00 kHz (Main converter stage) 25.00 kHz ... 500.00 kHz (PFC stage)
Product type
Power supply
Product family
QUINT POWER
MTBF (IEC 61709, SN 29500)
> 985000 h (25 °C) > 638000 h (40 °C) > 311000 h (60 °C)
Environmental protection directive
RoHS Directive 2011/65/EU WEEE Reach
Protection class
I
Degree of pollution
2
Current
10 A
Temperature
40 °C
Time
344000 h
Additional text
400 V AC
Current
10 A
Temperature
40 °C
Time
320000 h
Additional text
480 V AC
Current
20 A
Temperature
25 °C
Time
445000 h
Additional text
400 V AC
Current
20 A
Temperature
25 °C
Time
432000 h
Additional text
480 V AC
Current
20 A
Temperature
40 °C
Time
157000 h
Additional text
400 V AC
Current
20 A
Temperature
40 °C
Time
152000 h
Additional text
480 V AC
Width
70 mm
Height
130 mm
Depth
125 mm
Installation distance right/left
5 mm / 5 mm
Installation distance top/bottom
50 mm / 50 mm
Width
122 mm
Height
130 mm
Depth
73 mm
Mounting type
DIN rail mounting
Assembly note
alignable: P
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
yes
Flammability rating according to UL 94 (housing / terminal blocks)
V0
Housing material
Metal
Hood version
Stainless steel X6Cr17
Side element version
Aluminum
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 5000 m (> 2000 m, observe derating)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
Rail applications
EN 50121-3-2 EN 50121-4 EN 50121-5 IEC 62236-3-2 IEC 62236-4 IEC 62236-5
HART FSK Physical Layer Test Specification Compliance
Output voltage U
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Electrical safety
IEC 61010-2-201 (SELV)
Standard – Safety extra-low voltage
IEC 61010-1 (SELV) IEC 61010-2-201 (PELV)
Standard - Safe isolation
IEC 61558-2-16 IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use
IEC 61010-1
Standard - Safety of transformers
EN 61558-2-16
Approval - requirement of the semiconductor industry with regard to mains voltage dips
SEMI F47-0706, EN 61000-4-11
EN 61010-1
II (≤ 2000 m)
EN 62477-1
III (≤ 2000 m)
CSA
CAN/CSA-C22.2 No. 60950-1-07 CSA-C22.2 No. 107.1-01
Shipbuilding approval
DNV GL, PRS, BV, LR, ABS
SIQ
BG (type approved)
UL approvals
UL Listed UL 508 UL/C-UL Recognized UL 60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
EMC requirements, power plant
IEC 61850-3 EN 61000-6-5

Specifications may be subject to change without notice