Product Model
QUINT4-PS/3AC/24DC/20/IOL

Selling Points
- 194.1% efficiency in 400 V AC and 94.9% in 480 V AC, ensuring energy-efficient operation.
- 2Integrated gas-filled surge arrester up to 6 kV and ≥ 20 ms mains failure buffer time for high noise immunity.
- 3Nominal current adjustable from 2 A to 10 A, suitable for various DC load requirements.
- 4Designed for heavy load startup and miniature circuit breaker tripping, ensuring reliable operation in industrial settings.
- 5Preventive function monitoring reports critical operating states before errors occur, enhancing system reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Network type | Star network | Nominal input voltage range | 3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC |
Input voltage range | 3x 400 V AC ... 500 V AC -20 % ... +10 %
2x 400 V AC ... 500 V AC -10 % ... +10 % | Typical national grid voltage | 400 V AC
480 V AC |
Voltage type of supply voltage | AC/DC | Inrush current | typ. 2 A (at 25 °C) |
Inrush current integral (I | < 0.1 A | Inrush current limitation | 2 A (after 1 ms) |
AC frequency range | 50 Hz ... 60 Hz -10 % ... +10 % | Frequency range (f | 50 Hz ... 60 Hz -10 % ... +10 % |
Mains buffering time | typ. 33 ms (3x 400 V AC)
typ. 33 ms (3x 480 V AC) | Current consumption | 3x 0.99 A (400 V AC)
3x 0.81 A (480 V AC)
2x 1.62 A (400 V AC)
2x 1.37 A (480 V AC)
3x 0.8 A (500 V AC)
2x 1.23 A (500 V AC) |
Reverse polarity protection | yes | Nominal power consumption | 541 VA |
Protective circuit | Transient surge protection; Varistor, gas-filled surge arrester | Power factor (cos phi) | 0.94 |
Switch-on time | < 1 s | Typical response time | 300 ms (from SLEEP MODE) |
Recommended breaker for input protection | 3x 4 A ... 20 A (Characteristic B, C or comparable) | Recommended fuse for input protection | ≥ 300 V AC |
Discharge current to PE | < 3.5 mA
1.7 mA (550 V AC, 60 Hz) | Nominal input voltage range | ± 260 V DC ... 300 V DC |
Input voltage range | ± 260 V DC ... 300 V DC -13 % ... +30 % | Current consumption | 1.23 A (± 260 V DC)
1.06 A (±300 V DC) |
Recommended breaker for input protection | 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) | Recommended fuse for input protection | ≥ 1000 V DC |
Efficiency | typ. 94.1 % (400 V AC)
typ. 94.9 % (480 V AC) | Output characteristic | U/I Advanced |
Nominal output voltage | 24 V DC | Setting range of the output voltage (U | 24 V DC ... 29.5 V DC (constant capacity) |
Nominal output current (I | 20 A | Static Boost (I | 25 A |
Dynamic Boost (I | 30 A (5 s) | Selective Fuse Breaking (I | 120 A (15 ms) |
Magnetic circuit breaker tripping | A1...A16 / B2...B13 / C1...C6 / Z1...Z16 | Derating | > 60 °C ... 70 °C (2.5 %/K) |
Feedback voltage resistance | ≤ 35 V DC | Protection against overvoltage at the output (OVP) | ≤ 32 V DC |
Control deviation | < 0.5 % (Static load change 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %) | Residual ripple | < 60 mV |
Short-circuit-proof | yes | No-load proof | yes |
Output power | 480 W
600 W
720 W | Apparent power | 686 VA (400 V, U
698 VA (480 V, U |
Maximum no-load power dissipation | < 6 W (400 V AC)
< 6 W (480 V AC) | Power loss nominal load max. | < 30 W (400 V AC)
< 30 W (480 V AC) |
Power dissipation SLEEP MODE | < 5 W (400 V AC)
< 5 W (480 V AC) | Crest factor | typ. 1.78 (400 V AC)
typ. 2.1 (480 V AC) |
Rise time | < 80 ms (U | Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes | Default | closed (U |
Digital | 24 V DC 1 A
30 V AC/DC 0.5 A | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 4 mm² |
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.25 mm² | Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 4 mm² |
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.25 mm² | Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 4 mm² |
Conductor cross section AWG min. | 24 | Conductor cross section AWG max. | 10 |
Stripping length | 8 mm | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 4 mm² |
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.25 mm² | Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 4 mm² |
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.25 mm² | Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 4 mm² |
Conductor cross section AWG min. | 24 | Conductor cross section AWG max. | 10 |
Stripping length | 8 mm | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Connection method | Push-in connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 1 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 1.5 mm² |
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.2 mm² | Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 0.75 mm² |
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.2 mm² | Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 1.5 mm² |
Conductor cross section AWG min. | 24 | Conductor cross section AWG max. | 16 |
Stripping length | 8 mm | Reverse polarity protection | yes |
Specification | V1.1 | Interface | IO-Link |
Connection method | 3-conductor port class A | Connection marking | 3.3 (L+)
3.4 ()
3.5 (L-) |
Transmission speed | 230 kbps (COM3) | Cycle time | 2 ms |
Electrical isolation | yes | Amount of process data | 6 Byte (Input data) |
Device ID | 262657 | Vendor ID | 00B0 |
Interface | System communication | Connection method | 2-conductor |
Connection marking | 3.6 ()
3.5 (L-/Sgnd) | Electrical isolation | yes |
P | > 100 % (LED lights up yellow, output power > 480 W)
> 75 % (LED lights up green, output power > 360 W)
> 50 % (LED lights up green, output power > 240 W) | U | > 0.9 x U
< 0.9 x U |
Number of phases | 3.00 | Insulation voltage input/output | 4 kV AC (type test)
2.4 kV AC (routine test) |
Insulation voltage output / PE | 0.5 kV DC (type test)
0.5 kV DC (routine test) | Insulation voltage input / PE | 3.5 kV AC (type test)
2.4 kV AC (routine test) |
Switching frequency | 90.00 kHz ... 110.00 kHz (Auxiliary converter stage)
56.00 kHz ... 500.00 kHz (Main converter stage)
25.00 kHz ... 500.00 kHz (PFC stage) | Product type | Power supply |
Product family | QUINT POWER | MTBF (IEC 61709, SN 29500) | > 985000 h (25 °C)
> 638000 h (40 °C)
> 311000 h (60 °C) |
Environmental protection directive | RoHS Directive 2011/65/EU
WEEE
Reach | Article revision | 02 |
Protection class | I | Degree of pollution | 2 |
Current | 10 A | Temperature | 40 °C |
Time | 344000 h | Additional text | 400 V AC |
Current | 10 A | Temperature | 40 °C |
Time | 320000 h | Additional text | 480 V AC |
Current | 20 A | Temperature | 25 °C |
Time | 445000 h | Additional text | 400 V AC |
Current | 20 A | Temperature | 25 °C |
Time | 432000 h | Additional text | 480 V AC |
Current | 20 A | Temperature | 40 °C |
Time | 157000 h | Additional text | 400 V AC |
Current | 20 A | Temperature | 40 °C |
Time | 152000 h | Additional text | 480 V AC |
Width | 70 mm | Height | 130 mm |
Depth | 125 mm | Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm | Mounting type | DIN rail mounting |
Mounting position | horizontal DIN rail NS 35, EN 60715 | With protective coating | no |
Flammability rating according to UL 94 (housing / terminal blocks) | V0 | Housing material | Metal |
Hood version | Stainless steel X6Cr17 | Side element version | Aluminum |
Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) | Climatic class | 3K22 (in accordance with EN 60721-3-3) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) | Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) | Temp code | T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K) |
Rail applications | EN 50121-3-2
EN 50121-5
IEC 62236-3-2
IEC 62236-5 | HART FSK Physical Layer Test Specification Compliance | Output voltage U |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 | Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV) | Standard - Safe isolation | IEC 61558-2-16
IEC 61010-2-201 |
Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 | Standard - Safety of transformers | EN 61558-2-16 |
Standard - power supply devices for low voltage with DC output | EN 61204-3 | Battery charging | DIN 41773-1 |
Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706, EN 61000-4-11 | EN 61010-1 | II (≤ 5000 m) |
EN 62477-1 | III (≤ 2000 m) | EN 61558-2-16 | II (≤ 5000 m) |
CSA | CAN/CSA-C22.2 No. 61010-1-12
CAN/CSA-C22.2 No. 61010-2-201 | SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
UL approvals | UL Listed UL 61010-1
UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) | Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC | EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 | EMC requirements for power supply | IEC 61850-3 (G,H)
EN 61000-6-5 (switching devices) |
Conducted noise emission | EN 55016
EN 61000-6-3 (Class B) | Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Noise emission | EN 55016
EN 61000-6-3 (Class B) | Standards/regulations | EN 61000-3-2
EN 61000-3-2 (Class A) |
Frequency range | 0 kHz ... 2 kHz | Standards/regulations | EN 61000-3-3
EN 61000-3-3 |
Frequency range | 0 kHz ... 2 kHz | Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) | Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion A | Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz ... 1 GHz | Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz ... 6 GHz | Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A | Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) | Output | 2 kV (Test Level 4 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) | Comments | Criterion B |
Standards/regulations | EN 61000-4-5 | Input | 2 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical) |
Output | 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical) | Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B | Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical | Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A | Voltage | 10 V (Test Level 3) |
Standards/regulations | EN 61000-4-8 | Frequency | 16.7 Hz
50 Hz
60 Hz |
Test field strength | 100 A/m | Additional text | 60 s |
Comments | Criterion A | Frequency | 50 Hz
60 Hz |
Frequency range | 50 Hz ... 60 Hz | Test field strength | 1 kA/m |
Additional text | 3 s | Frequency | 0 Hz |
Test field strength | 300 A/m | Additional text | DC, 60 s |
Standards/regulations | EN 61000-4-11 | Voltage | 400 V AC |
Frequency | 50 Hz | Voltage dip | 70 % |
Number of periods | 0.5 / 1 / 25 periods | Additional text | Test Level 2 |
Comments | Criterion A: 0.5 / 1 period | Voltage dip | 40 % |
Number of periods | 5 / 10 / 50 periods | Additional text | Test Level 2 |
Comments | Criterion B | Voltage dip | 0 % |
Number of periods | 0,5 / 1 / 5 / 50 / 250 periods | Additional text | Test Level 2 |
Comments | Criterion A: 0.5 / 1 period | Standards/regulations | EN 61000-4-9 |
Test field strength | 1000 A/m | Comments | Criterion A |
Standards/regulations | EN 61000-4-12 | Input | 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A | Standards/regulations | EN 61000-4-16 |
Test level 1 | 15 Hz 150 Hz (Test Level 3) | Voltage | 10 V 1 V |
Test level 2 | 150 Hz 1.5 kHz (Test Level 3) | Voltage | 1 V |
Test level 3 | 1.5 kHz 15 kHz (Test Level 3) | Voltage | 1 V 10 V |
Test level 4 | 15 kHz 150 kHz (Test Level 3) | Voltage | 10 V |
Test level 5 | 50 Hz 60 Hz (Test Level 3) | Voltage | 10 V (Permanent) |
Test level 6 | 50 Hz 60 Hz (Test Level 3) | Voltage | 100 V (1 s) |
Comments | Criterion A | Standards/regulations | EN 61000-4-10 |
Test field strength | 100 A/m | Test level 1 | 100 kHz |
Test field strength | 100 A/m | Test level 2 | 1 MHz |
Comments | Criterion A | Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. | Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Specifications may be subject to change without notice