Product Model

QUINT4-PS/3AC/24DC/20/KONF1

In Stock
Last updated: 2025/4/19
Phoenix Contact QUINT4-PS/3AC/24DC/20/KONF1

Selling Points

  • 1Metal housing and wide temperature range from -40°C to +70°C.
  • 2Integrated gas-filled surge arrester and ≥20 ms mains failure buffering time.
  • 3Preventive function monitoring with analog, digital signals, and relay contacts.
  • 4NFC programming adapter with USB interface for wireless configuration.
  • 5Wide range input and international approval package for global use.
Product Details
QUINT4-PS/3AC/24DC/20/KONF1
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Control input (configurable) Rem
Output power ON/OFF (SLEEP MODE)
Default
Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
Network type
Star network
Nominal input voltage range
3x 400 V AC ... 500 V AC 2x 400 V AC ... 500 V AC
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +10 % 2x 400 V AC ... 500 V AC -10 % ... +10 %
Typical national grid voltage
400 V AC 480 V AC
Voltage type of supply voltage
AC/DC
Inrush current
typ. 2 A (at 25 °C)
Inrush current integral (I
< 0.1 A
Inrush current limitation
3 A (after 1 ms)
AC frequency range
50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (f
50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time
≥ 25 ms (3x 400 V AC) ≥ 25 ms (3x 480 V AC)
Current consumption
3x 0.99 A (400 V AC) 3x 0.81 A (480 V AC) 2x 1.62 A (400 V AC) 2x 1.37 A (480 V AC) 3x 0.8 A (500 V AC) 2x 1.23 A (500 V AC)
Nominal power consumption
541 VA
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time
< 1 s
Typical response time
300 ms (from SLEEP MODE)
Recommended breaker for input protection
3x 4 A ... 20 A (Characteristic B, C or comparable)
Recommended fuse for input protection
≥ 300 V AC
Discharge current to PE
< 3.5 mA 1.7 mA (550 V AC, 60 Hz)
Nominal input voltage range
± 260 V DC ... 300 V DC
Input voltage range
± 260 V DC ... 300 V DC -13 % ... +30 %
Voltage type of supply voltage
AC/DC
Current consumption
1.23 A (± 260 V DC) 1.06 A (±300 V DC)
Recommended breaker for input protection
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection
≥ 1000 V DC
Efficiency
typ. 93.9 % (400 V AC) typ. 93.8 % (480 V AC)
Nominal output voltage
26 V DC
Setting range of the output voltage (U
24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (I
20 A
Static Boost (I
25 A
Dynamic Boost (I
30 A (5 s)
Selective Fuse Breaking (I
120 A (15 ms)
Magnetic circuit breaker tripping
A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Derating
> 60 °C (2.5 %/K)
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
≤ 32 V DC
Control deviation
< 0.5 % (Static load change 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, (10 Hz)) < 0.25 % (change in input voltage ±10 %)
Residual ripple
< 60 mV
Short-circuit-proof
yes
No-load proof
yes
Output power
480 W 600 W 720 W
Apparent power
686 VA (400 V, U 698 VA (480 V, U
Maximum no-load power dissipation
< 7 W (400 V AC) < 7 W (480 V AC)
Power loss nominal load max.
< 32 W (400 V AC) < 33 W (480 V AC)
Power dissipation SLEEP MODE
< 5 W (400 V AC) < 5 W (480 V AC)
Crest factor
typ. 1.78 (400 V AC) typ. 2.1 (480 V AC)
Rise time
< 80 ms (U
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Signal ground SGnd
Reference potential for Out1, Out2, and Rem
Digital
24 V DC 20 mA
Default
24 V DC 20 mA 24 V DC for U
Default
24 V DC 20 mA 24 V DC for P
Default
closed (U
Digital
24 V DC 1 A 30 V AC/DC 0.5 A
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
30
Conductor cross section AWG max.
10
Stripping length
8 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
30
Conductor cross section AWG max.
10
Stripping length
8 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
P
> 100 % (LED lights up yellow, output power > 480 W) > 75 % (LED lights up green, output power > 360 W) > 50 % (LED lights up green, output power > 240 W)
U
> 0.9 x U < 0.9 x U
Number of phases
3.00
Insulation voltage input/output
4 kV AC (type test) 2.4 kV AC (routine test)
Insulation voltage output / PE
0.5 kV DC (type test) 0.5 kV DC (routine test)
Insulation voltage input / PE
3.5 kV AC (type test) 2.4 kV AC (routine test)
Switching frequency
90.00 kHz ... 110.00 kHz (Auxiliary converter stage) 56.00 kHz ... 500.00 kHz (Main converter stage) 25.00 kHz ... 500.00 kHz (PFC stage)
Product type
Power supply
Product family
QUINT POWER
MTBF (IEC 61709, SN 29500)
> 985000 h (25 °C) > 638000 h (40 °C) > 311000 h (60 °C)
Environmental protection directive
RoHS Directive 2011/65/EU WEEE Reach
Protection class
I
Degree of pollution
2
Current
10 A
Temperature
40 °C
Time
344000 h
Additional text
400 V AC
Current
10 A
Temperature
40 °C
Time
320000 h
Additional text
480 V AC
Current
20 A
Temperature
25 °C
Time
445000 h
Additional text
400 V AC
Current
20 A
Temperature
25 °C
Time
432000 h
Additional text
480 V AC
Current
20 A
Temperature
40 °C
Time
157000 h
Additional text
400 V AC
Current
20 A
Temperature
40 °C
Time
152000 h
Additional text
480 V AC
Width
70 mm
Height
130 mm
Depth
125 mm
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
30 mm / 30 mm
Width
122 mm
Height
130 mm
Depth
73 mm
Mounting type
DIN rail mounting
Assembly note
alignable: P
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
no
Flammability rating according to UL 94 (housing / terminal blocks)
V0
Housing material
Metal
Hood version
Stainless steel X6Cr17
Side element version
Aluminum
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 5000 m (> 2000 m, observe derating)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
Rail applications
EN 50121-3-2 EN 50121-4 EN 50121-5 IEC 62236-3-2 IEC 62236-4 IEC 62236-5
HART FSK Physical Layer Test Specification Compliance
Output voltage U
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - safety for equipment for measurement, control, and laboratory use
IEC 61010-1
Standard - Safety of power supply units up to 1100 V (insulation distances)
DIN EN 61558-2-16
Standard - Safety of transformers
EN 61558-2-16 (air clearances and creepage distances only)
Standard - power supply devices for low voltage with DC output
EN 61204-3
Approval - requirement of the semiconductor industry with regard to mains voltage dips
SEMI F47-0706, EN 61000-4-11
EN 60950-1
II
EN 61010-1
II
EN 62477-1
III
CSA
CAN/CSA-C22.2 No. 60950-1-07 CSA-C22.2 No. 107.1-01
Shipbuilding approval
DNV GL, PRS, BV, LR, ABS
UL approvals
UL Listed UL 508 UL/C-UL Recognized UL 60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
Conducted noise emission
EN 55016 EN 61000-6-3 (Class B)
Noise emission
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission
EN 55016 EN 61000-6-3 (Class B)
DNV GL conducted interference
Class A
Additional text
Area power distribution
DNV GL noise radiation
Class B
Additional text
Bridge and deck area
Frequency range
0 kHz ... 2 kHz
Frequency range
0 kHz ... 2 kHz
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Comments
Criterion A
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
4 kV (Test Level 4 - asymmetrical)
Output
4 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Comments
Criterion A
Standards/regulations
EN 61000-4-5
Input
3 kV (Test Level 4 - symmetrical) 6 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-8
Frequency
16.67 Hz 50 Hz 60 Hz
Test field strength
100 A/m
Additional text
60 s
Comments
Criterion A
Frequency
50 Hz 60 Hz
Frequency range
50 Hz ... 60 Hz
Test field strength
1 kA/m
Additional text
3 s
Frequency
0 Hz
Test field strength
300 A/m
Additional text
DC, 60 s
Standards/regulations
EN 61000-4-11
Voltage
400 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
0.5 / 1 / 25 periods
Additional text
Test Level 2
Comments
Criterion A: 0.5 / 1 period
Voltage dip
40 %
Number of periods
5 / 10 / 50 periods
Additional text
Test Level 2
Comments
Criterion B
Voltage dip
0 %
Number of periods
0.5 / 1 / 5 / 50 periods
Additional text
Test Level 2
Comments
Criterion A: 0,5 / 1 period
Standards/regulations
EN 61000-4-9
Test field strength
1000 A/m
Comments
Criterion A
Standards/regulations
EN 61000-4-12
Input
2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical)
Comments
Criterion A
Standards/regulations
EN 61000-4-16
Test level 1
50 Hz 60 Hz (Test Level 3)
Voltage
10 V (Permanent)
Test level 2
0 Hz 16.67 Hz 50 Hz 60 Hz (Test Level 2)
Voltage
100 V (1 s)
Comments
Criterion A
Standards/regulations
EN 61000-4-18
Input/Output/Signal
0.5 kV (Test Level 2 - symmetrical) 1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Specifications may be subject to change without notice