Product Model
QUINT4-S-ORING/12-24DC/1X40/VP

Selling Points
- 1Active redundancy module for superior system availability and maximum operational reliability.
- 2Compatible with DIN rail mounting, ensuring easy installation in industrial settings.
- 3Robust surge protection up to 30 V DC at the output, safeguarding against voltage spikes.
- 4High efficiency with typical efficiency rates of 99% (12 V DC) and 99.2% (24 V DC).
- 5Long lifespan with MTBF exceeding 13,486,000 hours at 25°C, ensuring prolonged system uptime.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Nominal input voltage range | 12 V DC ... 24 V DC | Input voltage range | 8 V DC ... 27.5 V DC (SELV) |
Typical national grid voltage | 12 V DC
24 V DC | Voltage type of supply voltage | DC |
Current consumption | 40 A | Static Boost (I | 45 A |
Dynamic Boost (I | 60 A (5 s) | Selective Fuse Breaking (I | 215 A (15 ms) |
Reverse polarity protection | < yes60 V | Nominal input current (I | 40 A (-40 °C ... 60 °C) |
Input current I | 45 A (40 °C) | Input current I | 60 A (5 s) |
Input current I | 215 A (15 ms) | Transient surge protection | Varistor |
Voltage drop, input/output | 0.1 V DC | Efficiency | typ. 99 % (12 V DC)
typ. 99.2 % (24 V DC) |
Nominal output voltage | U | Nominal output current (I | 40 A |
Static Boost (I | 45 A | Dynamic Boost (I | 60 A (5 s) |
Selective Fuse Breaking (I | 215 A (15 ms) | Derating | 60 °C ... 70 °C (2.5 %/K) |
Protection against overvoltage at the output (OVP) | < 30 V DC | Power loss nominal load max. | 6.5 W (I
6 W (I |
Connection in series | no | Output description | Group contact |
Maximum switching voltage | max. 30 V AC/DC | Maximum inrush current | ≤ 100 mA (short-circuit-proof) |
Default | open | Default | closed |
Default | open | Default | open |
Connection method | Screw connection | Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 16 mm² | Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 16 mm² | Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.5 mm² |
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 16 mm² | Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.5 mm² |
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 16 mm² | Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 | Stripping length | 10 mm |
Screw thread | M4 | Tightening torque, min | 1.2 Nm |
Tightening torque max | 1.5 Nm | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.5 mm² | Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² | Conductor cross section flexible max. | 16 mm² |
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.5 mm² | Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 16 mm² |
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.5 mm² | Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 16 mm² |
Conductor cross section AWG min. | 20 | Conductor cross section AWG max. | 6 |
Stripping length | 10 mm | Screw thread | M4 |
Tightening torque, min | 1.2 Nm | Tightening torque max | 1.5 Nm |
Connection method | Push-in connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 1.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 1.5 mm² | Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.2 mm² |
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 0.75 mm² | Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.2 mm² |
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 1.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 16 | Stripping length | 8 mm |
Types of signaling | Relay contact, floating, current limited | U | LED off, input voltage not present or short circuit at redundancy module output |
U | LED lights up green, input voltage present | U | LED flashing red, OVP active - input voltage exceeds the permissible voltage value |
Redundancy modul faulty | LED lights up red, redundancy module needs to be factory tested | Insulation voltage input, output / housing | 500 V DC |
Product type | Redundancy module | Product family | QUINT S-ORING |
MTBF (IEC 61709, SN 29500) | > 13486000 h (25 °C)
> 7314000 h (40 °C)
> 3379000 h (60 °C) | LED | yes |
Article revision | 04 | Protection class | III |
Degree of pollution | 2 | Current | 40 A |
Temperature | 40 °C | Time | 160000 h |
Additional text | 12 V DC | Current | 40 A |
Temperature | 40 °C | Time | 149000 h |
Additional text | 24 V DC | Width | 32 mm |
Height | 130 mm | Depth | 125 mm |
Installation distance right/left | 0 mm / 0 mm | Installation distance top/bottom | 50 mm / 50 mm |
Width | 122 mm | Height | 130 mm |
Depth | 35 mm | Mounting type | DIN rail mounting |
Assembly note | alignable: P | Mounting position | horizontal DIN rail NS 35, EN 60715 |
Flammability rating according to UL 94 (housing / terminal blocks) | V0 | Housing material | Metal |
Housing material | Aluminum / stainless steel | Type of housing | Aluminum (AlMg3) |
Hood version | Galvanized sheet steel, free from chrome (VI) | Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) | Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) | Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min. | Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) | Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) | Standard - Safe isolation | DIN VDE 0100-410 |
UL approvals | UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | ATEX | II 3 G Ex ec nC IIC T4 Gc
SIQ 21 ATEX 183 X |
IECEx | Ex ec nC IIC T4 Gc
IECEx SIQ 21.0001X | Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC | EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 | Conducted noise emission | EN 55016
EN 61000-6-3 (Class B) |
Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station) | Noise emission | EN 55016
EN 61000-6-3 (Class B) |
DNV GL conducted interference | Class A | Additional text | Area power distribution |
DNV GL noise radiation | Class B | Additional text | Bridge and deck area |
Standards/regulations | EN 61000-4-2 | Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) | Comments | Criterion B |
Standards/regulations | EN 61000-4-3 | Frequency range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m (Test Level 3) | Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) | Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) | Comments | Criterion A |
Standards/regulations | EN 61000-4-4 | Input | 2 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 4 - asymmetrical) | Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A | Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) | Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical | Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A | Voltage | 10 V (Test Level 3) |
Standards/regulations | EN 61000-4-8 | Frequency | 16.67 Hz
50 Hz
60 Hz |
Test field strength | 30 A/m | Additional text | 60 s |
Comments | Criterion A | Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Specifications may be subject to change without notice