Product Model

QUINT4-UPS/24DC/24DC/20/USB/C1

In Stock
Last updated: 2025/4/19
Phoenix Contact QUINT4-UPS/24DC/24DC/20/USB/C1

Selling Points

  • 1Intelligent battery management with IQ Technology for superior system availability.
  • 2Robust communication interfaces including USB, PROFINET, EtherNet/IP, and EtherCAT.
  • 3High efficiency with up to 98% efficiency during operation.
  • 4Automatic battery detection and charging with up to 5 A charging current.
  • 5Reliable shutdown and restart functions to prevent data loss during power failures.
Product Details
QUINT4-UPS/24DC/24DC/20/USB/C1
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Input voltage
24 V DC
Input voltage range
18 V DC ... 30 V DC 18 V DC ... 32 V DC
Electric strength, max.
35 V DC
Internal input fuse
no
Voltage type of supply voltage
DC
Inrush current
≤ 8 A (≤ 4 ms)
Reverse polarity protection
yes
Fixed backup threshold
22 V DC
Dynamic activation threshold
> 1 V / 100 ms
Switch-on time
max. 3 s
Switch-on time during battery operation (Bat.-Start)
8 s
Voltage drop, input/output
0.4 V DC
Current consumption I
20.1 A
Current consumption I
31.2 A
Current consumption I
50 mA
Current consumption I
6.1 A
Power consumption P
474 W
Power consumption P
738 W
Power consumption P
1.3 W
Power consumption P
145 W
Number of outputs
1
Short-circuit-proof
yes
No-load proof
yes
Output voltage
24 V DC (U
Output voltage range
18 V DC ... 30 V DC 18 V DC ... 32 V DC
Output current I
20 A
Static Boost (I
25 A
Dynamic Boost (I
30 A (5 s)
Selective Fuse Breaking (I
120 A (15 ms)
Output power P
480 W
Output power P
600 W
Output voltage
24 V DC (U
Output voltage range
19 V DC ... 32 V DC
Output current I
20 A
Static Boost (I
25 A
Selective Fuse Breaking (I
120 A (15 ms)
Output power P
480 W
Output power P
600 W
Nominal capacity (without additional charger)
3 Ah ... 100 Ah
Max. capacity
135 Ah
Buffer time
19 min (12 Ah)
Battery technology
VRLA, VRLA-WTR, LI-ION
IQ-Technology
yes
Temperature sensor
yes
Interface
USB (Modbus/RTU)
Number of interfaces
1
Connection method
MINI-USB Type B
Connection marking
X1
Locking
Screw
Transmission physics
USB 2.0
Topology
Point-to-point
Product type
DC UPS
Product family
QUINT USV
Environmental protection directive
RoHS Directive 2011/65/EU WEEE Reach
Protection class
III
Degree of pollution
2
Width
40 mm
Height
130 mm
Depth
125 mm 125 mm (Device depth (DIN rail mounting))
Width
123 mm
Height
130 mm
Depth
42 mm
Installation distance right/left (active)
5 mm / 5 mm (P
Installation distance right/left (passive)
0 mm / 0 mm (P
Installation distance right/left (active, passive)
0 mm / 0 mm (P
Installation distance top/bottom (active)
50 mm / 50 mm (P
Installation distance top/bottom (passive)
40 mm / 20 mm (P
Installation distance top/bottom (active, passive)
40 mm / 20 mm (P
Mounting type
DIN rail mounting
Assembly note
alignable: horizontally 0 mm, vertically 50 mm
Mounting position
On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715
Flammability rating according to UL 94 (housing / terminal blocks)
V0
Hood version
Stainless steel X6Cr17
Side element version
Aluminum AlMg3
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 4000 m
Climatic class
3K3 (EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
2.3g
Standard designation
Protective extra-low voltage
Standards/specifications
IEC 61010-1 (SELV) IEC 61010-2-201 (PELV)
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2

Specifications may be subject to change without notice