Product Model

QUINT4-UPS/24DC/24DC/5/USB

In Stock
Last updated: 2025/4/18
Phoenix Contact QUINT4-UPS/24DC/24DC/5/USB

Selling Points

  • 1IQ Technology ensures reliable determination of remaining service life and buffer time.
  • 2Supports USB with Modbus/RTU, 2x RJ45 with PROFINET, EtherNet/IP, or EtherCAT protocol.
  • 3Enables daisy chain connectivity for easy network integration.
  • 4Up to 5 A charging current for efficient battery charging.
  • 598% efficiency and >1,184,000 hours MTBF for continuous system availability.
Product Details
QUINT4-UPS/24DC/24DC/5/USB
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Input voltage
24 V DC
Input voltage range
18 V DC ... 30 V DC 18 V DC ... 32 V DC
Electric strength, max.
35 V DC (Protected against polarity reversal)
Internal input fuse
no
Voltage type of supply voltage
DC
Inrush current
≤ 7 A (≤ 4 ms)
Reverse polarity protection
yes
Fixed backup threshold
22 V DC
Dynamic activation threshold
> 1 V / 100 ms
Switch-on time
max. 3 s
Switch-on time during battery operation (Bat.-Start)
8 s
Voltage drop, input/output
0.3 V DC
Current consumption I
5.1 A
Current consumption I
8.3 A
Current consumption I
45 mA
Current consumption I
1.8 A
Power consumption P
121 W
Power consumption P
211 W
Power consumption P
1.1 W
Power consumption P
43 W
Efficiency
typ. 98 %
Number of outputs
1
Short-circuit-proof
yes
No-load proof
yes
Switch-over time
0 ms
UPS connection in parallel
no
UPS connection in series
no
Energy storage device connection in parallel
Yes, 5 (observe line protection)
Energy storage device connection in series
no
Output voltage
24 V DC (U
Output voltage range
18 V DC ... 30 V DC (U 18 V DC ... 32 V DC
Output current I
5 A
Static Boost (I
6.25 A
Dynamic Boost (I
10 A (5 s)
Selective Fuse Breaking (I
30 A (15 ms)
Output power P
120 W
Output power P
155 W
Output power P
240 W (5 s)
Power dissipation No load (U
1 W
Power dissipation Nominal load (U
3 W
Output voltage
24 V DC (U
Output voltage range
19 V DC ... 32 V DC (U
Output current I
5 A
Static Boost (I
6.25 A
Selective Fuse Breaking (I
30 A (15 ms)
Output power P
120 W
Output power P
150 W
Output power P
240 W (5 s)
Power dissipation No load (U
2 W
Power dissipation Nominal load (U
3 W
End-of-charge voltage
32 V DC
End-of-charge voltage (temperature-compensated)
25 V DC ... 32 V DC
Charging current (configurable)
max. 1.5 A
Nominal capacity (without additional charger)
0.8 Ah ... 30 Ah
Max. capacity
40 Ah
Charging time
2.5 h (3.4 Ah)
Buffer time
25 min (3.4 Ah)
Deep discharge protection (configurable)
19.2 V DC
Battery technology
VRLA, VRLA-WTR, LI-ION
Charge characteristic curve
IU
IQ-Technology
yes
Temperature sensor
yes
Temperature compensation (configurable)
42 mV/K
Position
1.x
Connection method
Screw connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2 mm²
flexible with ferrule without plastic sleeve
0.2 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.2 mm² ... 2.5 mm²
rigid (AWG)
30 ... 12 (Cu)
Stripping length
6.5 mm (rigid/flexible)
Tightening torque
0.5 Nm ... 0.6 Nm
Drive form screw head
Slotted L
Position
2.x
Connection method
Screw connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.2 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.2 mm² ... 2.5 mm²
rigid (AWG)
30 ... 12 (Cu)
Stripping length
6.5 mm (rigid/flexible)
Tightening torque
0.5 Nm ... 0.6 Nm
Drive form screw head
Slotted L
Position
3.x
Connection method
Push-in connection
rigid
0.2 mm² ... 1 mm²
flexible
0.2 mm² ... 1 mm²
flexible with ferrule without plastic sleeve
0.2 mm² ... 0.75 mm² (Cu) 0.5 mm² (recommended)
flexible with ferrule with plastic sleeve
0.2 mm² ... 0.75 mm²
rigid (AWG)
24 ... 16 (Cu)
Stripping length
8 mm (rigid/flexible)
Position
4.x
Position marking
4.1 (+), 4.2 (-), 4.3 ()
Connection method
Screw connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.2 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.2 mm² ... 2.5 mm²
rigid (AWG)
30 ... 12 (Cu)
Stripping length
6.5 mm (rigid/flexible)
Tightening torque
0.5 Nm ... 0.6 Nm
Drive form screw head
Slotted L
Slave address
192
Start bit
1
Data bits
8
Parity
even
Stop bit
1
Interface
USB
Number of interfaces
1
Connection method
MINI-USB Type B
Supported protocols
Modbus/RTU
Connection marking
X1
Locking
Screw
Transmission physics
USB 2.0
Topology
Point-to-point
Transmission speed
9600 baud ... 115200 baud (Default: 115200 baud)
Transmission length
max. 5 m
Access time
≤ 2 s
Chipset
Silicon Labs CP210x
Electrical isolation
Yes, UL approved
Types of signaling
DC OK (green) Alarm (red) Bat.-Mode (yellow) SOC (red, green) Data (red, green)
Product type
DC UPS
Product family
QUINT USV
MTBF (IEC 61709, SN 29500)
> 1430000 h (25 °C) > 916900 h (40 °C) > 480100 h (60 °C)
Environmental protection directive
RoHS Directive 2011/65/EU WEEE Reach
Article revision
05
Protection class
III (without PE)
Degree of pollution
2
Time
224011 h
Width
35 mm
Height
130 mm
Depth
125 mm 125 mm (Device depth (DIN rail mounting))
Width
123 mm
Height
130 mm
Depth
37 mm
Installation distance right/left (active)
5 mm / 5 mm (P
Installation distance right/left (passive)
0 mm / 0 mm (P
Installation distance right/left (active, passive)
0 mm / 0 mm (P
Installation distance top/bottom (active)
50 mm / 50 mm (P
Installation distance top/bottom (passive)
40 mm / 20 mm (P
Installation distance top/bottom (active, passive)
40 mm / 20 mm (P
Mounting type
DIN rail mounting
Mounting position
On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715
Flammability rating according to UL 94 (housing / terminal blocks)
V0
Housing material
Metal
Hood version
Stainless steel X6Cr17
Side element version
Aluminum AlMg3
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 4000 m
Climatic class
3K3 (EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
2.3g
EN 61010-1
II (≤ 4000 m)
EN 61010-2-201
II (≤ 4000 m)
Standard designation
Protective extra-low voltage
Standards/specifications
IEC 61010-1 (SELV) IEC 61010-2-201 (PELV)
Identification
UL/C-UL Listed UL 61010-1
Identification
UL/C-UL Listed UL 61010-2-201
Identification
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
Identification
CAN/CSA-C22.2 No. 61010-1-12
Identification
CAN/CSA-IEC 61010-2-201
Identification
CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
Identification
IEC 61010-1
Identification
IEC 61010-2-201
Identification
Class Guideline DNVGL-CG-0339
Note
Location classes: Temperature D (see Application/Limitation), Humidity B, Vibration A/C, EMC B
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
Noise immunity
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply)
Noise emission
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
4 kV (Test Level 4 - asymmetrical)
Output
4 kV (Test Level 4 - asymmetrical)
Signal
4 kV (Test Level 4 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Output
1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-8
Frequency
16.67 Hz 50 Hz 60 Hz
Test field strength
100 A/m
Additional text
60 s
Comments
Criterion A
Frequency
50 Hz 60 Hz
Frequency range
50 Hz ... 60 Hz
Test field strength
1 kA/m
Additional text
3 s
Frequency
0 Hz
Test field strength
300 A/m
Additional text
DC, 60 s
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice