Product Model

QUINT-ORING/24DC/2X40/1X80

In Stock
Last updated: 2025/4/17
Phoenix Contact QUINT-ORING/24DC/2X40/1X80

Selling Points

  • 1The Auto Current Balancing ACB technology ensures uniform load distribution, doubling the service life of redundantly operated power supplies.
  • 2MOSFETs help save up to 70% energy, making it an efficient solution for power supply needs.
  • 3The module includes monitoring functions for continuous redundancy checks and maintenance alerts.
  • 4Automatically distributes load current symmetrically, ensuring consistent redundancy up to the load.
  • 5Designed for easy installation on DIN rail, making it a versatile solution for various industrial applications.
Product Details
QUINT-ORING/24DC/2X40/1X80
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Nominal input voltage range
24 V DC
Input voltage range
18 V DC ... 28 V DC (SELV)
Input voltage range DC
18 V DC ... 28 V DC (SELV)
Voltage type of supply voltage
DC
Reverse polarity protection
< yes60 V
Nominal input current (I
2x 40 A (-25 °C ... 60 °C) 1x 80 A (-25 °C ... 60 °C)
Maximum current I
2x 45 A (-25 °C ... 40 °C) 1x 90 A (-25 °C ... 40 °C) 215 A (12 ms, SFB Technology)
Transient surge protection
Varistor
Voltage drop, input/output
0.2 V (I
Efficiency
> 98 %
Nominal output voltage
U
Nominal output current (I
80 A (Increasing power) 40 A (Redundancy)
Derating
60 °C ... 70 °C (2.5 %/K)
Protection against overvoltage at the output (OVP)
≤ 32 V DC
Power loss nominal load max.
16 W (I
Connection in series
no
Output description
Group contact
Maximum switching voltage
max. 30 V AC/DC
Maximum inrush current
≤ 100 mA (short-circuit-proof)
Output description
Contact closed: Δ U
Maximum switching voltage
max. 30 V AC/DC
Maximum inrush current
≤ 100 mA (short-circuit-proof)
Maximum inrush current
≤ 100 mA (short-circuit-proof)
Connection method
Screw connection
Conductor cross section, rigid min.
0.5 mm²
Conductor cross section, rigid max.
16 mm²
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
16 mm²
Conductor cross section AWG min.
6
Stripping length
10 mm
Screw thread
M4
Tightening torque, min
1.2 Nm
Tightening torque max
1.5 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.5 mm²
Conductor cross section, rigid max.
35 mm²
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
35 mm²
Conductor cross section AWG min.
2
Stripping length
18 mm
Screw thread
M5
Tightening torque, min
2.5 Nm
Tightening torque max
4.5 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
16
Conductor cross section AWG max.
10
Stripping length
10 mm
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
10
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Types of signaling
Relay contact, floating, current limited
Status display
LED redundancy OK
Note on status display
green
Status display
ACB OK LED
Note on status display
LED bar graph green
Insulation voltage input, output / housing
500 V
Product type
Redundancy module
Product family
QUINT ORING
MTBF (IEC 61709, SN 29500)
> 720000 h (40 °C)
LED
yes
Article revision
03
Protection class
III
Degree of pollution
2
Width
66 mm
Height
130 mm
Depth
125 mm
Horizontal pitch
3.7 Div.
Installation distance right/left
5 mm / 5 mm
Installation distance top/bottom
50 mm / 50 mm
Width
122 mm
Height
130 mm
Depth
69 mm
Mounting type
DIN rail: 35 mm
Assembly note
alignable: P
Mounting position
horizontal DIN rail NS 35, EN 60715
Housing material
Metal
Type of housing
Aluminum (AlMg3)
Hood version
Galvanized sheet steel, free from chrome (VI)
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
2000 m 2000 m
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min.
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
UL approvals
UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
SIL in accordance with IEC 61508
0
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m (Test Level 3)
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
2 GHz ... 3 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Output
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-6-3
Radio interference voltage in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice