Product Model
QUINT-PS-100-240AC/12DC/10

Selling Points
- 1Wide input voltage range: 85 V AC to 264 V AC and 90 V DC to 350 V DC.
- 2High output current: 10 A at 12 V DC.
- 3Compact design: Dimensions are 85 mm wide, 130 mm high, and 130 mm deep.
- 4Robust construction: IP20 degree of protection and operating temperature range of -25 °C to 70 °C.
- 5Versatile connectivity: Screw connection for solid and flexible conductors, with a maximum cross-section of 2.5 mm².
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Nominal input voltage range | 100 V AC ... 240 V AC | Input voltage range | 85 V AC ... 264 V AC
90 V DC ... 350 V DC |
Input voltage range AC | 85 V AC ... 264 V AC | Input voltage range DC | 90 V DC ... 350 V DC |
Voltage type of supply voltage | AC/DC | Inrush current | < 15 A (typical) |
Inrush current integral (I | 1 A | AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz | Mains buffering time | > 50 ms (120 V AC)
> 50 ms (230 V AC) |
Current consumption | approx. 1.5 A (120 V AC)
0.6 A (230 V AC) | Nominal power consumption | 139 W |
Typical response time | < 1 s | Input fuse | 6.3 A (slow-blow, internal) |
Permissible DC backup fuse | DC: Connect a suitable fuse upstream | Recommended breaker for input protection | 10 A ... 16 A (Characteristics B, C, D, K) |
Efficiency | > 84 % | Nominal output voltage | 12 V DC ±1 % |
Setting range of the output voltage (U | 11.5 V DC ... 18 V DC | Nominal output current (I | 10 A (up to 60 °C) |
POWER BOOST (I | 16 A | Derating | 60 °C ... 70 °C (2.5 %/K) |
Feedback voltage resistance | 35 V DC | Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Max. capacitive load | unlimited | Residual ripple | < 30 mV |
Output power | 120 W | Peak switching voltages nominal load | < 50 mV |
Maximum no-load power dissipation | < 4 W | Power loss nominal load max. | < 22 W |
Connection in parallel | yes, for redundancy and increased capacity | Connection in series | yes |
Output description | U | Maximum switching voltage | ≤ 12 V |
Output voltage | + 12 V DC | Maximum inrush current | ≤ 40 mA |
Continuous load current | ≤ 40 mA | Output description | Relay contact, U |
Maximum switching voltage | ≤ 30 V AC/DC | Maximum inrush current | ≤ 1 A |
Continuous load current | ≤ 1 A | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 | Conductor cross section AWG max. | 12 |
Stripping length | 7 mm | Screw thread | M3 |
Connection method | Screw connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 | Stripping length | 7 mm |
Screw thread | M3 | Tightening torque, min | 0.5 Nm |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 | Conductor cross section AWG max. | 12 |
Screw thread | M3 | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Types of signaling | LED
Active switching output
Relay contact |
Operating voltage display | Green LED | Status display | "DC OK" LED green |
Note on status display | U | Status display | "DC OK" LED green |
Number of phases | 1.00 | Insulation voltage input/output | 2 kV (routine test)
4 kV (type test) |
Product type | Power supply | Product family | QUINT POWER |
MTBF (IEC 61709, SN 29500) | > 500000 h | Article revision | 22 |
Protection class | I (with PE connection) | Degree of pollution | 2 |
Width | 85 mm | Height | 130 mm |
Depth | 130 mm | Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm | Width | 122 mm |
Height | 88 mm | Depth | 88 mm |
Assembly note | alignable: horizontally 0 mm, vertically 50 mm | Mounting position | horizontal DIN rail NS 35, EN 60715 |
Housing material | Metal | Type of housing | AluNox (AlMg1) |
Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 | Standard - Electrical safety | EN 62368-1 |
Standard - Equipment safety | GS (tested safety) | Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 62368-1 |
Standard – Safety extra-low voltage | EN 62368-1 (SELV)
EN 60204 (PELV) | Standard - Safe isolation | DIN VDE 0100-410 |
Shipbuilding approval | DNV GL (EMC A) | UL approvals | UL/C-UL Recognized UL 60950-1
UL/C-UL listed UL 508
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 | EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 |
Specifications may be subject to change without notice