Product Model
QUINT-PS-100-240AC/48DC/10

Selling Points
- 1Ensures full output power even in the event of a long-term phase failure.
- 2Designed for complex loads, ensuring reliable starting and operation.
- 3Compatible with 100-240AC input, providing flexibility in various environments.
- 4Space-saving design ideal for industrial applications.
- 5Optimized for energy efficiency, reducing operational costs and environmental impact.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Nominal input voltage range | 100 V AC ... 240 V AC | Input voltage range | 85 V AC ... 264 V AC
90 V DC ... 350 V DC |
Input voltage range AC | 85 V AC ... 264 V AC | Input voltage range DC | 90 V DC ... 350 V DC |
Voltage type of supply voltage | AC/DC | Inrush current | < 15 A (3.2 A |
Inrush current integral (I | 3.2 A | AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz | Mains buffering time | > 30 ms (120 V AC)
> 35 ms (230 V AC) |
Current consumption | approx. 4.76 A (120 V AC)
2.3 A (230 V AC) | Nominal power consumption | 524 W |
Protective circuit | Transient surge protection; Varistor | Typical response time | < 1 s |
Input fuse | 12 A (slow-blow, internal) | Permissible backup fuse | B10 B16 |
Recommended breaker for input protection | 10 A ... 16 A (Characteristics B, C, D, K) | Discharge current to PE | < 3.5 mA |
Efficiency | > 90 % | Nominal output voltage | 48 V DC ±1 % |
Setting range of the output voltage (U | 30 V DC ... 56 V DC | Nominal output current (I | 10 A (up to 60 °C) |
Output current limit | 13 A (approx. I | POWER BOOST (I | 13 A |
Derating | 60 °C (2.5 %/K) | Feedback voltage resistance | 60 V DC |
Protection against overvoltage at the output (OVP) | ≤ 60 V DC | Max. capacitive load | unlimited |
Control deviation | < 1 % (change in load, static 10 % ... 90 %)
< 5 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %) | Residual ripple | < 20 mV |
Output power | 480 W | Peak switching voltages nominal load | < 50 mV |
Maximum no-load power dissipation | < 5 W | Power loss nominal load max. | < 56 W |
Rise time | < 2 ms (U | Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes | Output description | U |
Maximum switching voltage | ≤ 24 V | Output voltage | + 24 V DC |
Maximum inrush current | ≤ 40 mA | Continuous load current | ≤ 40 mA |
Output description | Relay contact, U | Maximum switching voltage | ≤ 30 V AC/DC |
Maximum inrush current | ≤ 1 A | Continuous load current | ≤ 1 A |
Connection method | Screw connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 6 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 10 | Stripping length | 7 mm |
Screw thread | M3 | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.5 mm² | Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² | Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 | Conductor cross section AWG max. | 6 |
Stripping length | 7 mm | Screw thread | M4 |
Tightening torque, min | 1.2 Nm | Tightening torque max | 1.5 Nm |
Conductor cross section, rigid min. | 0.5 mm² | Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² | Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 | Conductor cross section AWG max. | 6 |
Screw thread | M4 | Tightening torque, min | 1.2 Nm |
Tightening torque max | 1.5 Nm | Types of signaling | LED
Active switching output
Relay contact |
Status display | "DC OK" LED green | Note on status display | U |
Status display | "DC OK" LED green | Note on status display | U |
Number of phases | 1.00 | Insulation voltage input/output | 4 kV AC (type test)
2 kV AC (routine test) |
Insulation voltage output / PE | 500 V DC (routine test) | Insulation voltage input / PE | 3.5 kV AC (type test)
2 kV AC (routine test) |
Product type | Power supply | Product family | QUINT POWER |
MTBF (IEC 61709, SN 29500) | > 500000 h | Protection class | I (with PE connection) |
Degree of pollution | 2 | Width | 157 mm |
Height | 130 mm | Depth | 125 mm |
Width | 122 mm | Height | 130 mm |
Depth | 160 mm | Mounting type | DIN rail mounting |
Assembly note | alignable: horizontally 0 mm, vertically 50 mm | Mounting position | horizontal DIN rail NS 35, EN 60715 |
Housing material | Metal | Type of housing | AluNox (AlMg1) |
Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) | Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min. | Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 | Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV)
EN 61558-2-17 |
Standard - Equipment safety | GS (tested safety) | Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Safety extra-low voltage | EN 60950-1 (SELV)
EN 60204 (PELV) | Standard - Safe isolation | DIN VDE 0100-410 |
Standard - Safety of transformers | EN 61558-2-17 | EN 62477-1 | III |
Shipbuilding approval | DNV GL (EMC A), ABS | UL approvals | UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 | EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 |
Standards/regulations | EN 61000-4-2 | Housing | Level 4 |
Contact discharge | 8 kV | Discharge in air | 15 kV |
Comments | Criterion B | Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz ... 1 GHz | Test field strength | 10 V/m |
Comments | Criterion A | Standards/regulations | EN 61000-4-4 |
Input | 4 kV (level 4 - asymmetrical: conductor to ground) | Output | 2 kV (level 3 - asymmetrical: conductor to ground) |
Signal | 1 kV (level 1 - asymmetrical: conductor to ground) | Comments | Criterion B |
Standards/regulations | EN 61000-4-5 | Input | 4 kV (inst. class 4 - asymmetrical: conductor to ground)
2 kV (inst. class 4 -symmetrical: conductor to conductor) |
Output | 0.5 kV (level 1 - asymmetrical: conductor to ground)
0.5 kV (level 1 - symmetrical: conductor to conductor) | Signal | 1 kV (level 2 - asymmetrical: conductor to ground) |
Comments | Criterion B | Standards/regulations | EN 61000-4-6 |
I/O/S | Level 3 - asymmetrical | Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A | Voltage | 10 V |
Standards/regulations | EN 61000-4-11 | Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential | Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Specifications may be subject to change without notice