Product Model

QUINT-PS/12DC/24DC/ 5

In Stock
Last updated: 2025/4/18
Phoenix Contact QUINT-PS/12DC/24DC/ 5

Selling Points

  • 1High Efficiency: Achieves over 90% efficiency for optimal power output.
  • 2Robust Design: Withstands harsh industrial environments and operates from -25°C to +70°C.
  • 3Isolated Output: Provides 1.5 kV isolation voltage for safe and independent supply systems.
  • 4Regulated Output: Offers a regulated output voltage range of 18 to 29.5 V DC.
  • 5Durable Construction: Built with SFB Technology and designed for long-lasting performance in industrial settings.
Product Details
QUINT-PS/12DC/24DC/ 5
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Nominal input voltage range
12 V DC
Input voltage range
9 V DC ... 18 V DC
Wide-range input
no
Input voltage range DC
9 V DC ... 18 V DC
Voltage type of supply voltage
DC
Inrush current
< 15 A (typical)
Inrush current integral (I
< 0.3 A
Mains buffering time
typ. 3 ms (12 V DC)
Current consumption
15 A (12 V, I
Reverse polarity protection
≤ 30 V DC
Protective circuit
Transient surge protection; Varistor
Input fuse
25 A (internal (device protection))
Efficiency
> 90 %
Output characteristic
U/I
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (U
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I
5 A (-25 °C ... 60 °C)
POWER BOOST (I
6.25 A (-25 °C ... 40 °C permanent, U
Selective Fuse Breaking (I
30 A (12 ms)
Magnetic circuit breaker tripping
B2 / B4 / C2
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
35 V DC
Protection against overvoltage at the output (OVP)
< 35 V DC
Max. capacitive load
unlimited
Active current limitation
Approximately 6.9 A
Control deviation
< 1 % (change in load, static 10 % ... 90 %) < 2 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %)
Residual ripple
< 75 mV
Output power
120 W
Peak switching voltages nominal load
< 10 mV
Maximum no-load power dissipation
2 W
Power loss nominal load max.
13.5 W
Rise time
< 2 ms (U
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes 2 (Devices)
Output description
U
Switching voltage range
18 V DC ... 24 V DC
Maximum inrush current
< 20 mA (short-circuit-proof)
Output description
I
Switching voltage range
18 V DC ... 24 V DC
Maximum inrush current
< 20 mA (short-circuit-proof)
Output description
U
Switching voltage range
18 V DC ... 24 V DC
Maximum inrush current
< 20 mA (short-circuit-proof)
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
12
Stripping length
8 mm
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Types of signaling
LED Active switching output Relay contact
Status display
"DC OK" LED green
Color
green
Status display
"BOOST" LED yellow/I
Color
yellow
Note on status display
LED on
Status display
LED "U
Color
yellow
Note on status display
LED on
Number of phases
1.00
Insulation voltage input/output
1.5 kV (type test) 1 kV (routine test) 1 kV (type test)
Product type
DC/DC converters
Product family
QUINT POWER
MTBF (IEC 61709, SN 29500)
> 1005000 h (40 °C)
Article revision
04
Protection class
III
Degree of pollution
2
Width
32 mm
Height
130 mm
Depth
125 mm
Installation distance right/left
0 mm / 0 mm (≤ 70 °C)
Installation distance right/left (active)
15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom
50 mm / 50 mm (≤ 70 °C)
Installation distance top/bottom (active)
50 mm / 50 mm (≤ 70 °C)
Width
122 mm
Height
130 mm
Depth
35 mm
Mounting type
DIN rail mounting
Assembly note
alignable: P
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
no
Housing material
Metal
Type of housing
Aluminum (AlMg3)
Hood version
Galvanized sheet steel, free from chrome (VI)
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min.
Temp code
T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K)
Rail applications
EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV) EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
UL approvals
UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m (Test Level 3)
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
2 GHz ... 3 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 4 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Output
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-6-3
Radio interference voltage in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice