Product Model
QUINT-PS/3AC/24DC/10

Selling Points
- 1High Availability: Designed for continuous operation even in the event of permanent phase failure.
- 2Reliable Performance: High efficiency (>93%) and low ripple noise (<20 mV Pk-Pk).
- 3Flexible Connectivity: Mountable on DIN rail, with options for parallel and series connections.
- 4Enhanced Protection: Magnetic fuse tripping and surge protection against internal surge voltages.
- 5Versatile Output: Output current up to 10A, with POWER BOOST option for increased capacity.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Nominal input voltage range | 3x 400 V AC ... 500 V AC | Input voltage range | 3x 400 V AC ... 500 V AC -20 % ... +15 %
2x 400 V AC ... 500 V AC -10 % ... +15 % |
Input voltage range DC | 450 V DC ... 800 V DC | Voltage type of supply voltage | AC/DC |
Inrush current | < 15 A (at 25 °C) | Inrush current integral (I | < 1.5 A |
Inrush current limitation | 15 A | AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz | Mains buffering time | > 30 ms (400 V AC)
> 46 ms (500 V AC) |
Current consumption | 3x 1.2 A (400 V AC)
3x 1 A (500 V AC)
2x 1.5 A (400 V AC)
2x 1.3 A (500 V AC) | Nominal power consumption | 411 VA |
Protective circuit | Transient surge protection; Varistor, gas-filled surge arrester | Power factor (cos phi) | 0.62 |
Typical response time | < 0.45 s | Permissible backup fuse | B6 B10 B16 AC: |
Permissible DC backup fuse | DC: Connect a suitable fuse upstream | Recommended breaker for input protection | 6 A ... 16 A (AC: Characteristics B, C, D, K) |
Discharge current to PE | < 3.5 mA | Nominal input voltage range | 500 V DC ... 600 V DC |
Input voltage range | 500 V DC ... 600 V DC -10 % ... +33 % (mid-point earthed) | Current consumption | 0.8 A (500 V DC)
0.7 A (600 V DC) |
Recommended breaker for input protection | 1x 6 A ≥ 1000 V DC (10 x 38 mm, 30 kA L/R = 2 ms) | Efficiency | typ. 93 % (400 V AC) |
Output characteristic | U/I | Nominal output voltage | 24 V DC ±1 % |
Setting range of the output voltage (U | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) | Nominal output current (I | 10 A |
POWER BOOST (I | 15 A (-25 °C ... 40 °C permanent, U | Static Boost (I | 15 A |
Selective Fuse Breaking (I | 60 A (12 ms) | Magnetic circuit breaker tripping | B2 / B4 / B6 / C2 / C4 |
Derating | 60 °C ... 70 °C (2.5 %/K) | Feedback voltage resistance | max. 35 V DC |
Protection against overvoltage at the output (OVP) | < 35 V DC | Control deviation | < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 20 mV | Output power | 240 W
360 W |
Peak switching voltages nominal load | < 20 mV | Maximum no-load power dissipation | 7 W |
Power loss nominal load max. | 19 W | Rise time | < 0.15 s (U |
Connection in parallel | yes, for redundancy and increased capacity | Connection in series | yes |
Output description | U | Maximum switching voltage | + 24 V DC |
Switching voltage range | 18 V DC ... 24 V DC | Output voltage | + 24 V DC |
Maximum inrush current | ≤ 20 mA (short-circuit-proof) | Continuous load current | ≤ 20 mA |
Output description | Relay contact, U | Maximum switching voltage | 30 V AC/DC
24 V DC |
Maximum inrush current | 0.5 A
1 A | Continuous load current | ≤ 1 A |
Output description | I | Maximum switching voltage | + 24 V DC |
Switching voltage range | 18 V DC ... 24 V DC | Output voltage | + 24 V DC |
Maximum inrush current | ≤ 20 mA (short-circuit-proof) | Continuous load current | ≤ 20 mA |
Connection method | Pluggable screw connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 | Stripping length | 7 mm |
Screw thread | M3 | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Connection method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 16 | Conductor cross section AWG max. | 12 |
Stripping length | 7 mm | Screw thread | M3 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Connection method | Pluggable screw connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 | Screw thread | M3 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Types of signaling | LED
Active switching output
Relay contact | Operating voltage display | Green LED |
Status display | U | Note on status display | U |
Status display | U | Note on status display | U |
Status display | I | Number of phases | 3.00 |
Insulation voltage input/output | 4 kV AC (type test)
2 kV AC (routine test) | Insulation voltage output / PE | 500 V DC (routine test) |
Insulation voltage input / PE | 3.5 kV AC (type test)
2 kV AC (routine test) | Product type | Power supply |
Product family | QUINT POWER | MTBF (IEC 61709, SN 29500) | > 1100000 h (25 °C)
> 630000 h (40 °C)
> 280000 h (60 °C) |
Article revision | 08 | Protection class | I |
Degree of pollution | 2 | Width | 60 mm |
Height | 130 mm | Depth | 125 mm |
Installation distance right/left (active) | 15 mm / 15 mm | Installation distance top/bottom (active) | 50 mm / 50 mm |
Width | 122 mm | Height | 130 mm |
Depth | 63 mm | Assembly note | alignable: P |
Mounting position | horizontal DIN rail NS 35, EN 60715 | With protective coating | no |
Housing material | Metal | Hood version | Galvanized sheet steel, free from chrome (VI) |
Side element version | Aluminum | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C | Maximum altitude | 4500 m |
Climatic class | 3K3 (in acc. with EN 60721) | Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) | Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min. |
Temp code | T4A (-25 ... +60 °C) | Rail applications | EN 50121-4
EN 50121-3-2 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 | Standard - Electrical safety | IEC 61010-2-201 (SELV) |
Standard - Equipment safety | GS (tested safety) | Standard - Approval for medical use | IEC 60601-1, 2 x MOOP |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 | Standard – Safety extra-low voltage | IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV) |
Standard - Safe isolation | IEC 61010-2-201 | Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Standard - surge resistance | VDE 0160 (curve W2) | Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706 Compliance Certificate |
EN 61010-1 | II (≤ 5000 m) | EN 62477-1 | III (≤ 2000 m) |
EN 61558-2-16 | II (≤ 4000 m) | CSA | CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01 |
Shipbuilding approval | DNV GL (EMC B), ABS, LR, RINA, NK, BV | UL approvals | UL Listed UL 508
UL/C-UL Recognized UL 60950-1 (3-wire + PE, star net)
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4A (Hazardous Location) |
SIL in accordance with IEC 61508 | 0 | Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC | EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 | Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) | Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion A | Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz ... 1 GHz | Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz ... 2 GHz | Test field strength | 10 V/m (Test Level 3) |
Frequency range | 2 GHz ... 3 GHz | Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A | Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) | Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) | Comments | Criterion A |
Standards/regulations | EN 61000-4-5 | Input | 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) | Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B | Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical | Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A | Voltage | 10 V (Test Level 3) |
Standards/regulations | EN 61000-6-3 | Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential | Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Specifications may be subject to change without notice