Product Model

QUINT-PS/3AC/24DC/20

In Stock
Last updated: 2025/4/21
Phoenix Contact QUINT-PS/3AC/24DC/20

Selling Points

  • 1>93% efficiency ensures minimal power loss.
  • 2Built to withstand harsh industrial environments with protective coating.
  • 3Output voltage adjustable from 18 to 29.5 V DC.
  • 4Up to 50% additional current without voltage drop for peak loads.
  • 5Meets ITE, railway, and shipbuilding approvals for safety and reliability.
Product Details
QUINT-PS/3AC/24DC/20
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Nominal input voltage range
3x 400 V AC ... 500 V AC
Input voltage range
3x 320 V AC ... 575 V AC 2x 360 V AC ... 575 V AC 450 V DC ... 800 V DC
Input voltage range DC
450 V DC ... 800 V DC
Voltage type of supply voltage
AC/DC
Inrush current
< 20 A (typical)
Inrush current integral (I
< 3.2 A
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Mains buffering time
> 20 ms (400 V AC) > 30 ms (500 V AC)
Current consumption
3x 1.6 A (400 V AC) 3x 1.3 A (500 V AC) 0.9 A (600 V DC)
Nominal power consumption
783 VA
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi)
0.66
Typical response time
< 0.16 s
Permissible backup fuse
B6 B10 B16 AC:
Permissible DC backup fuse
DC: Connect a suitable fuse upstream
Recommended breaker for input protection
6 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE
< 3.5 mA
Efficiency
> 93 % (at 400 V AC and nominal values)
Output characteristic
U/I
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (U
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I
20 A (-25 °C ... 60 °C, U
POWER BOOST (I
26 A (-25 °C ... 40 °C permanent, U
Selective Fuse Breaking (I
120 A (12 ms)
Magnetic circuit breaker tripping
B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
max. 35 V DC
Protection against overvoltage at the output (OVP)
< 35 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %) < 3 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %)
Residual ripple
< 40 mV
Output power
480 W
Peak switching voltages nominal load
< 40 mV
Maximum no-load power dissipation
11 W
Power loss nominal load max.
40 W
Rise time
< 0.05 s (U
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Output description
U
Switching voltage range
18 V ... 24 V
Output voltage
+ 24 V DC
Maximum inrush current
≤ 20 mA (short-circuit-proof)
Continuous load current
≤ 20 mA
Output description
Relay contact, U
Maximum switching voltage
30 V AC/DC 24 V DC
Maximum inrush current
0.5 A 1 A
Continuous load current
≤ 1 A
Output description
I
Switching voltage range
18 V ... 24 V
Output voltage
+ 24 V DC
Maximum inrush current
≤ 20 mA (short-circuit-proof)
Continuous load current
≤ 20 mA
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
10
Stripping length
7 mm
Screw thread
M4
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
12
Conductor cross section AWG max.
10
Stripping length
7 mm
Screw thread
M4
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
10
Screw thread
M4
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Types of signaling
LED Active switching output Relay contact
Operating voltage display
Green LED
Status display
U
Note on status display
U
Status display
U
Note on status display
U
Status display
I
Number of phases
3.00
Insulation voltage input/output
4 kV AC (type test) 2 kV AC (routine test)
Insulation voltage output / PE
500 V DC (routine test)
Insulation voltage input / PE
3.5 kV AC (type test) 2 kV AC (routine test)
Product type
Power supply
Product family
QUINT POWER
MTBF (IEC 61709, SN 29500)
> 900000 h (25 °C) > 534000 h (40 °C) > 250000 h (60 °C)
Article revision
10
Protection class
I
Degree of pollution
2
Width
69 mm
Height
130 mm
Depth
122 mm
Width
122 mm
Height
130 mm
Depth
72 mm
Assembly note
alignable: P
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
no
Housing material
Metal
Hood version
Galvanized sheet steel, free from chrome (VI)
Side element version
Aluminum
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
5000 m
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min.
Temp code
T4 (-25 ... +60 °C)
Rail applications
EN 50121-4 EN 50121-3-2
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Electrical safety
IEC 61010-2-201 (SELV)
Standard - Equipment safety
GS (tested safety)
Standard - Approval for medical use
IEC 60601-1, 2 x MOOP
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
EN 50178
Standard – Safety extra-low voltage
IEC 61010-1 (SELV) IEC 61010-2-201 (PELV)
Standard - Safe isolation
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use
IEC 61010-1
Standard - surge resistance
VDE 0160 (curve W2)
Approval - requirement of the semiconductor industry with regard to mains voltage dips
SEMI F47-0706 Compliance Certificate
EN 62477-1
III
CSA
CAN/CSA-C22.2 No. 60950-1-07 CSA-C22.2 No. 107.1-01
Shipbuilding approval
DNV GL (EMC B), ABS, LR, RINA, NK, BV
UL approvals
UL Listed UL 508 UL/C-UL Recognized UL 60950-1 (3-wire + PE, star net) UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Comments
Criterion A
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m (Test Level 3)
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
2 GHz ... 3 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
4 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Output
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-6-3
Radio interference voltage in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice