Product Model
QUINT-PS/60-72DC/24DC/10/CO

Selling Points
- 1Regulated Output Voltage: Provides a stable 24V DC output.
- 2Wide Input Voltage Range: Operates with input voltages from 42 to 96V DC.
- 3High Efficiency: Offers high efficiency and low no-load power consumption.
- 4Durable Construction: Designed with ruggedized packaging for harsh environments.
- 5Safety Certifications: Meets cULus recognized standards, UL 508, and UL 60950-1.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Nominal input voltage range | 60 V DC ... 72 V DC | Input voltage range | 42 V DC ... 96 V DC |
Wide-range input | yes | Input voltage range DC | 42 V DC ... 96 V DC |
Voltage type of supply voltage | DC | Inrush current | < 9 A (typical) |
Inrush current integral (I | 0.64 A | Mains buffering time | typ. 10 ms (60 V DC) |
Current consumption | 5.6 A (60 V DC)
4.7 A (72 V DC) | Reverse polarity protection | ≤ 30 V DC |
Protective circuit | Transient surge protection; Varistor | Input fuse | 10 A 150 V DC (internal (device protection)) |
Efficiency | > 91 % (U
> 91 % (U | Output characteristic | U/I |
Nominal output voltage | 24 V DC ±1 % | Setting range of the output voltage (U | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (I | 10 A (-40 °C ... 60 °C) | POWER BOOST (I | 12.5 A (-40 °C ... 40 °C permanent, U |
Selective Fuse Breaking (I | 60 A (12 ms) | Magnetic circuit breaker tripping | B2 / B4 / B6 |
Derating | 60 °C ... 70 °C (2.5 %/K) | Feedback voltage resistance | 35 V DC |
Protection against overvoltage at the output (OVP) | < 35 V DC | Max. capacitive load | unlimited |
Active current limitation | 18 A | Control deviation | < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 20 mV | Short-circuit-proof | yes |
Output power | 240 W | Peak switching voltages nominal load | < 10 mV |
Maximum no-load power dissipation | 4 W (U | Power loss nominal load max. | 24 W (U |
Rise time | < 2 ms (U | Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes | Output description | U |
Switching voltage range | 18 V DC ... 24 V DC | Maximum inrush current | < 20 mA (short-circuit-proof) |
Output description | I | Switching voltage range | 18 V DC ... 24 V DC |
Maximum inrush current | < 20 mA (short-circuit-proof) | Output description | U |
Switching voltage range | 18 V DC ... 24 V DC | Maximum inrush current | ≤ 20 mA (short-circuit-proof) |
Output description | Relay | Output voltage | ≤ 30 V AC/DC |
Maximum inrush current | ≤ 100 mA | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 | Conductor cross section AWG max. | 12 |
Stripping length | 8 mm | Screw thread | M3 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Connection method | Screw connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 | Stripping length | 7 mm |
Screw thread | M3 | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 | Screw thread | M3 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Types of signaling | LED
Active switching output
Relay contact | Status display | "DC OK" LED green |
Color | green | Status display | "BOOST" LED yellow/I |
Color | yellow | Note on status display | LED on |
Status display | LED "U | Color | yellow |
Note on status display | LED on | Note on status display | U |
Number of phases | 1.00 | Insulation voltage input/output | 1.5 kV (type test)
1 kV (routine test)
1 kV (type test) |
Product type | DC/DC converters | Product family | QUINT POWER |
MTBF (IEC 61709, SN 29500) | > 1349000 h (25 °C)
> 765000 h (40 °C) | Article revision | 02 |
Protection class | I | Degree of pollution | 2 |
Width | 48 mm | Height | 130 mm |
Depth | 125 mm | Installation distance right/left | 0 mm / 0 mm (≤ 70 °C) |
Installation distance right/left (active) | 15 mm / 15 mm (≤ 70 °C) | Installation distance top/bottom | 50 mm / 50 mm (≤ 70 °C) |
Installation distance top/bottom (active) | 50 mm / 50 mm (≤ 70 °C) | Width | 122 mm |
Height | 130 mm | Depth | 51 mm |
Mounting type | DIN rail: 35 mm | Assembly note | alignable: P |
Mounting position | horizontal DIN rail NS 35, EN 60715 | With protective coating | yes |
Housing material | Metal | Type of housing | Aluminum (AlMg3) |
Hood version | Galvanized sheet steel, free from chrome (VI) | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C | Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | 100 % (at 25 °C, non-condensing) | Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min. | Temp code | T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K) |
Rail applications | EN 50121-4
EN 50155 | Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) | Standard – Safety extra-low voltage | EN 60950-1 (SELV)
EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 | Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
Standard designation | Fire protection in rail vehicles | Standards/specifications | EN 45545-2 (HL3) |
UL approvals | UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) | Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 | EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 |
Standards/regulations | EN 61000-4-2 | Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) | Comments | Criterion A |
Standards/regulations | EN 61000-4-3 | Frequency range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m (Test Level 3) | Frequency range | 1 GHz ... 2 GHz |
Test field strength | 20 V/m (Test Level 3) | Frequency range | 2 GHz ... 3 GHz |
Test field strength | 10 V/m (Test Level 3) | Comments | Criterion A |
Standards/regulations | EN 61000-4-4 | Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) | Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A | Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) | Output | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) | Comments | Criterion B |
Standards/regulations | EN 61000-4-6 | I/O/S | asymmetrical |
Frequency range | 9 kHz ... 80 MHz | Comments | Criterion A |
Voltage | 10 V (Test Level 3) | Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential | Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criterion A | Normal operating behavior within the specified limits. | Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Specifications may be subject to change without notice