Product Model

QUINT-UPS/ 24DC/12DC/5/24DC/10

In Stock
Last updated: 2025/4/17
Phoenix Contact QUINT-UPS/ 24DC/12DC/5/24DC/10

Selling Points

  • 124 V DC/10 A and 12 V DC/5 A.
  • 2> 98% in mains operation and > 93% with charged energy storage.
  • 3Ensures optimal use of buffer time and preventive monitoring of energy storage.
  • 4Fast tripping of standard circuit breakers for enhanced protection.
  • 5Combines power supply, UPS module, and energy storage for a tailored solution.
Product Details
QUINT-UPS/ 24DC/12DC/5/24DC/10
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Input voltage
24 V DC
Nominal input voltage range
18 V DC ... 30 V DC
Input voltage range
18 V DC ... 30 V DC
Input voltage range DC
18 V DC ... 30 V DC
Voltage type of supply voltage
DC
Buffer period
3 h (With battery module 38 AH)
Current consumption
16 A (maximum, mains operation) 104 mA (No load, mains operation) 4 A (Charging, mains operation)
Fixed backup threshold
≤ 22 V DC
Variable connect threshold
1 V/0.1 s
Recommended breaker for input protection
16 A ... 20 A (Characteristic B)
Efficiency
> 98 % (Mains operation, with charged energy storage) > 93 % (Mains operation, with charged energy storage)
Nominal output voltage
24 V DC
Output voltage range
18 V DC ... 30 V DC (U
Nominal output current (I
10 A (-25 °C ... 60 °C) 5 A (-25 °C ... 60 °C)
Output current limit
In mains mode according to connected upstream current limiting device > 15 A (Battery operation)
Bridging time
10800 s
Derating
60 °C ... 70 °C (2.5 %/K) 60 °C ... 70 °C (2.5 %/K)
UPS connection in parallel
yes
UPS connection in series
no
Output power
240 W
Total power P
max. 360 W
Power dissipation
2.6 W (Mains operation) 4.6 W (Mains operation) 2.9 W (Battery operation) 5.27 W (Battery operation)
Connection in parallel
yes, up to 2 modules with redundancy module 2 (Devices)
Connection in series
no no
Nominal output voltage
12 V DC 24 V DC
Output voltage range
18 V DC ... 30 V DC (U
Nominal output current (I
5 A (-25 °C ... 60 °C) 10 A (-25 °C ... 60 °C)
POWER BOOST (I
7.5 A (-25 °C ... 40 °C) 15 A (-25 °C ... 40 °C)
Selective Fuse Breaking (I
60 A (-25 °C ... 60 °C)
Duration
12 ms (SFB technology)
Nominal output voltage
12 V DC 24 V DC
Output voltage range
19.2 V DC ... 27.6 V DC (U
Nominal output current (I
5 A (-25 °C ... 60 °C) 10 A (-25 °C ... 60 °C)
POWER BOOST (I
7.5 A (-25 °C ... 40 °C) 15 A (-25 °C ... 40 °C)
Selective Fuse Breaking (I
65 A (-25 °C ... 60 °C)
Duration
15 ms (SFB technology)
Output description
Relay (floating)
Maximum switching voltage
≤ 30 V AC/DC
Continuous load current
≤ 100 mA
Output description
Relay (floating)
Maximum switching voltage
≤ 30 V AC/DC
Output voltage
24 V
Continuous load current
≤ 100 mA
Output description
Relay (floating)
Maximum switching voltage
≤ 30 V AC/DC
Output voltage
24 V
Continuous load current
≤ 100 mA
Output voltage
24 V DC
Continuous load current
100 mA
Nominal voltage U
24 V DC
End-of-charge voltage
24 V DC ... 29 V DC (temperature compensated)
Charging current
0.2 A ... 2.88 A
Nominal capacity range
1.3 Ah ... 60 Ah
Battery presence check/time interval
1 min
Battery presence check (cyclic)
60 s
Energy storage device connection in parallel
yes, 15 (observe line protection)
Energy storage device connection in series
no
IQ technology
Yes
Temperature compensation
42 mV/K (preset)
Temperature compensation (preset)
42 mV/K
Network management
Yes
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
16
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M4
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
16
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M4
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M4
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Interface
IFS (Interface system data port)
Types of signaling
LED Relay contact Interface/software
Signalization designation
Power In OK
Status display
LED
Note on status display
static on static on
Signalization designation
Alarm
Status display
LED
Note on status display
static on
Color
red
Note on status display
static on
Signalization designation
Battery charge
Status display
LED bar graph
Note on status display
dynamic
Color
red/green
Note on status display
dynamic
Signalization designation
Battery mode
Status display
LED
Note on status display
static on
Color
yellow
Note on status display
static on
Signalization designation
POWER BOOST
Insulation voltage input/output
500 V DC
Insulation voltage input, output / housing
750 V DC
Product type
DC UPS
Product family
QUINT USV
IQ technology
Yes
MTBF (IEC 61709, SN 29500)
> 652000 h (40 °C)
Article revision
04
Protection class
III
Time
33941 h
Width
35 mm
Height
130 mm
Depth
125 mm
Installation distance right/left
5 mm / 5 mm
Installation distance top/bottom
50 mm / 50 mm
Width
123 mm
Height
130 mm
Depth
39 mm
Mounting type
DIN rail mounting
Assembly note
alignable: horizontal 5 mm, vertical 50 mm
Mounting position
horizontal DIN rail NS 35, EN 60715
Housing material
Metal
Housing material
Steel sheet, zinc-plated
Type of housing
Aluminum (AlMg3)
Hood version
Galvanized sheet steel, free from chrome (VI)
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g t
Rail applications
EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
UL approvals
UL Listed UL 508 UL/C-UL Recognized UL 60950-1
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Comments
Criterion A
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m
Frequency range
2 GHz ... 3 GHz
Test field strength
3 V/m
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Comments
Criterion A
Standards/regulations
EN 61000-4-5
Input
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Output
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-6-3
Radio interference voltage in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice