Product Model
QUINT-UPS/ 24DC/12DC/5/24DC/10

Selling Points
- 124 V DC/10 A and 12 V DC/5 A.
- 2> 98% in mains operation and > 93% with charged energy storage.
- 3Ensures optimal use of buffer time and preventive monitoring of energy storage.
- 4Fast tripping of standard circuit breakers for enhanced protection.
- 5Combines power supply, UPS module, and energy storage for a tailored solution.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Input voltage | 24 V DC | Nominal input voltage range | 18 V DC ... 30 V DC |
Input voltage range | 18 V DC ... 30 V DC | Input voltage range DC | 18 V DC ... 30 V DC |
Voltage type of supply voltage | DC | Buffer period | 3 h (With battery module 38 AH) |
Current consumption | 16 A (maximum, mains operation)
104 mA (No load, mains operation)
4 A (Charging, mains operation) | Fixed backup threshold | ≤ 22 V DC |
Variable connect threshold | 1 V/0.1 s | Recommended breaker for input protection | 16 A ... 20 A (Characteristic B) |
Efficiency | > 98 % (Mains operation, with charged energy storage)
> 93 % (Mains operation, with charged energy storage) | Nominal output voltage | 24 V DC |
Output voltage range | 18 V DC ... 30 V DC (U | Nominal output current (I | 10 A (-25 °C ... 60 °C)
5 A (-25 °C ... 60 °C) |
Output current limit | In mains mode according to connected upstream current limiting device
> 15 A (Battery operation) | Bridging time | 10800 s |
Derating | 60 °C ... 70 °C (2.5 %/K)
60 °C ... 70 °C (2.5 %/K) | UPS connection in parallel | yes |
UPS connection in series | no | Output power | 240 W |
Total power P | max. 360 W | Power dissipation | 2.6 W (Mains operation)
4.6 W (Mains operation)
2.9 W (Battery operation)
5.27 W (Battery operation) |
Connection in parallel | yes, up to 2 modules with redundancy module
2 (Devices) | Connection in series | no
no |
Nominal output voltage | 12 V DC
24 V DC | Output voltage range | 18 V DC ... 30 V DC (U |
Nominal output current (I | 5 A (-25 °C ... 60 °C)
10 A (-25 °C ... 60 °C) | POWER BOOST (I | 7.5 A (-25 °C ... 40 °C)
15 A (-25 °C ... 40 °C) |
Selective Fuse Breaking (I | 60 A (-25 °C ... 60 °C) | Duration | 12 ms (SFB technology) |
Nominal output voltage | 12 V DC
24 V DC | Output voltage range | 19.2 V DC ... 27.6 V DC (U |
Nominal output current (I | 5 A (-25 °C ... 60 °C)
10 A (-25 °C ... 60 °C) | POWER BOOST (I | 7.5 A (-25 °C ... 40 °C)
15 A (-25 °C ... 40 °C) |
Selective Fuse Breaking (I | 65 A (-25 °C ... 60 °C) | Duration | 15 ms (SFB technology) |
Output description | Relay (floating) | Maximum switching voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 100 mA | Output description | Relay (floating) |
Maximum switching voltage | ≤ 30 V AC/DC | Output voltage | 24 V |
Continuous load current | ≤ 100 mA | Output description | Relay (floating) |
Maximum switching voltage | ≤ 30 V AC/DC | Output voltage | 24 V |
Continuous load current | ≤ 100 mA | Output voltage | 24 V DC |
Continuous load current | 100 mA | Nominal voltage U | 24 V DC |
End-of-charge voltage | 24 V DC ... 29 V DC (temperature compensated) | Charging current | 0.2 A ... 2.88 A |
Nominal capacity range | 1.3 Ah ... 60 Ah | Battery presence check/time interval | 1 min |
Battery presence check (cyclic) | 60 s | Energy storage device connection in parallel | yes, 15 (observe line protection) |
Energy storage device connection in series | no | IQ technology | Yes |
Temperature compensation | 42 mV/K (preset) | Temperature compensation (preset) | 42 mV/K |
Network management | Yes | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 16 | Conductor cross section AWG max. | 12 |
Stripping length | 7 mm | Screw thread | M4 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Connection method | Screw connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 | Stripping length | 7 mm |
Screw thread | M4 | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 | Conductor cross section AWG max. | 12 |
Stripping length | 7 mm | Screw thread | M4 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Interface | IFS (Interface system data port) | Types of signaling | LED
Relay contact
Interface/software |
Signalization designation | Power In OK | Status display | LED |
Note on status display | static on
static on | Signalization designation | Alarm |
Status display | LED | Note on status display | static on |
Color | red | Note on status display | static on |
Signalization designation | Battery charge | Status display | LED bar graph |
Note on status display | dynamic | Color | red/green |
Note on status display | dynamic | Signalization designation | Battery mode |
Status display | LED | Note on status display | static on |
Color | yellow | Note on status display | static on |
Signalization designation | POWER BOOST | Insulation voltage input/output | 500 V DC |
Insulation voltage input, output / housing | 750 V DC | Product type | DC UPS |
Product family | QUINT USV | IQ technology | Yes |
MTBF (IEC 61709, SN 29500) | > 652000 h (40 °C) | Article revision | 04 |
Protection class | III | Time | 33941 h |
Width | 35 mm | Height | 130 mm |
Depth | 125 mm | Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm | Width | 123 mm |
Height | 130 mm | Depth | 39 mm |
Mounting type | DIN rail mounting | Assembly note | alignable: horizontal 5 mm, vertical 50 mm |
Mounting position | horizontal DIN rail NS 35, EN 60715 | Housing material | Metal |
Housing material | Steel sheet, zinc-plated | Type of housing | Aluminum (AlMg3) |
Hood version | Galvanized sheet steel, free from chrome (VI) | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Climatic class | 3K3 (in acc. with EN 60721) | Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) | Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g t |
Rail applications | EN 50121-4 | Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) | UL approvals | UL Listed UL 508
UL/C-UL Recognized UL 60950-1 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 | EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 |
Standards/regulations | EN 61000-4-2 | Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) | Comments | Criterion A |
Standards/regulations | EN 61000-4-3 | Frequency range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m | Frequency range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m | Frequency range | 2 GHz ... 3 GHz |
Test field strength | 3 V/m | Comments | Criterion A |
Standards/regulations | EN 61000-4-4 | Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) | Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A | Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) | Output | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) | Comments | Criterion B |
Standards/regulations | EN 61000-4-6 | I/O/S | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz | Comments | Criterion A |
Voltage | 10 V (Test Level 3) | Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential | Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criterion A | Normal operating behavior within the specified limits. | Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Specifications may be subject to change without notice