Product Model
QUINT-UPS/24DC/24DC/5

Selling Points
- 1Automatic Battery Detection: Tool-free battery replacement during operation.
- 2Power Boost Capability: Reliable starting of difficult loads with up to 1.5 times the nominal current.
- 3Selective Fuse Breaking (SFB): Fast tripping of standard circuit breakers for enhanced safety.
- 4Comprehensive Parameterization: Extensive diagnostics and parameterization options for universal use.
- 5Durable Design: Built with a lead AGM 1.3 Ah battery module for reliable power storage.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Input voltage | 24 V DC | Nominal input voltage range | 24 V DC |
Input voltage range | 18 V DC ... 30 V DC | Input voltage range DC | 18 V DC ... 30 V DC |
Voltage type of supply voltage | DC | Buffer period | 2 h (With battery module 12 AH) |
Current consumption | 9.4 A (maximum, mains operation)
10.3 mA (No load, mains operation)
1.8 A (Charging, mains operation) | Fixed backup threshold | ≤ 22 V DC |
Variable connect threshold | 1 V/0.1 s | Efficiency | > 98 % (Mains operation, with charged energy storage)
98 % (Battery operation) |
Nominal output voltage | 24 V DC | Output voltage range | 18 V DC ... 30 V DC |
Nominal output current (I | 5 A (-25 °C ... 50 °C) | Output current limit | In mains mode according to connected upstream current limiting device
> 7.5 A (Battery operation) |
Bridging time | 28800 s | Derating | 60 °C ... 70 °C (2.5 %/K)
60 °C ... 70 °C (2.5 %/K) |
Output power | 120 W | Power dissipation | 2.5 W (Mains operation)
2.65 W (Mains operation)
2.64 W (Battery operation)
2.93 W (Battery operation) |
Connection in parallel | yes, up to 2 modules with redundancy module
2 (Devices) | Connection in series | no
no |
Nominal output voltage | 24 V DC | Output voltage range | 18 V DC ... 30 V DC |
Nominal output current (I | 5 A (-25 °C ... 60 °C) | POWER BOOST (I | 7.5 A (-25 °C ... 40 °C) |
Selective Fuse Breaking (I | 30 A (-25 °C ... 60 °C) | Duration | 12 ms (SFB technology) |
Nominal output voltage | 24 V DC | Output voltage range | 19.2 V DC ... 27.6 V DC (U |
Nominal output current (I | 5 A (-25 °C ... 60 °C) | POWER BOOST (I | 7.5 A (-25 °C ... 40 °C) |
Selective Fuse Breaking (I | 32.5 A (-25 °C ... 60 °C) | Duration | 15 ms (SFB technology) |
Output description | Relay (floating) | Maximum switching voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 100 mA | Output description | Relay (floating) |
Maximum switching voltage | ≤ 30 V AC/DC | Output voltage | 24 V |
Continuous load current | ≤ 100 mA | Output description | Relay (floating) |
Maximum switching voltage | ≤ 30 V AC/DC | Output voltage | 24 V |
Continuous load current | ≤ 100 mA | Nominal voltage U | 24 V DC |
End-of-charge voltage | 24 V DC ... 29 V DC (temperature compensated) | Charging current | 0.2 A ... 1.36 A |
Nominal capacity range | 0.8 Ah ... 140 Ah | Battery presence check/time interval | 1 min |
Battery presence check (cyclic) | 60 s | IQ technology | Yes |
Temperature compensation | 42 mV/K (preset) | Temperature compensation (preset) | 42 mV/K |
Network management | Yes | Connection method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² | Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² | Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 20 | Conductor cross section AWG max. | 12 |
Stripping length | 7 mm | Screw thread | M4 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Connection method | Pluggable screw connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 12 | Stripping length | 7 mm |
Screw thread | M4 | Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 | Screw thread | M4 |
Tightening torque, min | 0.5 Nm | Tightening torque max | 0.6 Nm |
Interface | IFS (Interface system data port) | Types of signaling | LED
Relay contact
Interface/software |
Signalization designation | Power In OK | Status display | LED |
Note on status display | static on
static on | Signalization designation | Alarm |
Status display | LED | Note on status display | static on |
Color | red | Note on status display | static on |
Signalization designation | Battery charge | Status display | LED bar graph |
Note on status display | dynamic | Color | green/red |
Note on status display | dynamic | Signalization designation | Battery mode |
Status display | LED | Note on status display | static on |
Color | yellow | Note on status display | static on |
Insulation voltage input/output | 500 V DC | Insulation voltage input, output / housing | 750 V DC |
Product type | DC UPS | Product family | QUINT USV |
IQ technology | Yes | MTBF (IEC 61709, SN 29500) | > 500000 h (25 °C)
> 500000 h (40 °C) |
Article revision | 12 | Protection class | III |
Time | 316800 h | Width | 35 mm |
Height | 130 mm | Depth | 125 mm |
Installation distance right/left | 5 mm / 5 mm | Installation distance top/bottom | 50 mm / 50 mm |
Width | 123 mm | Height | 130 mm |
Depth | 39 mm | Mounting type | DIN rail mounting |
Assembly note | alignable: horizontal 5 mm, vertical 50 mm | Mounting position | horizontal DIN rail NS 35, EN 60715 |
Housing material | Metal | Type of housing | Aluminum (AlMg3) |
Hood version | Galvanized sheet steel, free from chrome (VI) | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Climatic class | 3K3 (in acc. with EN 60721) | Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) | Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g t |
Rail applications | EN 50121-4 | Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) | UL approvals | UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 | EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 |
Standards/regulations | EN 61000-4-2 | Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) | Comments | Criterion A |
Standards/regulations | EN 61000-4-3 | Frequency range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m | Frequency range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m | Frequency range | 2 GHz ... 3 GHz |
Test field strength | 3 V/m | Comments | Criterion A |
Standards/regulations | EN 61000-4-4 | Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) | Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A | Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) | Output | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) | Comments | Criterion B |
Standards/regulations | EN 61000-4-6 | I/O/S | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz | Comments | Criterion A |
Voltage | 10 V (Test Level 3) | Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential | Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criterion A | Normal operating behavior within the specified limits. | Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Specifications may be subject to change without notice