Phoenix Contact RAD-2400-IFS

Selling Points

  • 1License-Free 2.4 GHz Frequency Band: Operate without licensing fees, ideal for industrial use.
  • 2Extended Range Up to 5 km: Achieve reliable communication over several kilometers with clear line of sight.
  • 3Quick and Easy Setup: Assign inputs and outputs without programming using the thumbwheel.
  • 4Integrated RS-232/RS-485 Interface: Support for serial data transmission and I/O signals.
  • 5Modular Extension with Up to 32 I/O Modules: Expand your network with hot-swappable I/O extension modules.
Product Details
RAD-2400-IFS
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Note on application
Only for industrial use
Product type
Wireless module
Application
I/O RS-232 RS-485
Operating mode
I/O data (Default setting, configuration via thumbwheel) Serial data (Activation and configuration via PSI-CONF software) PLC/Modbus RTU mode (Activation and configuration via PSI-CONF software) PLC / Modbus RTU dual mode (Activation and configuration via PSI-CONF software)
MTTF
733 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) 340 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) 135 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
Article revision
20
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
60 V (In accordance with EN/IEC 60079-7)
Maximum power dissipation for nominal condition
1.56 W
Transient surge protection
yes
Designation
Wireless module
Number of supported devices
≤ 250 (Addressing via PSI-CONF software) ≤ 99 (Addressing via thumbwheel)
Number of possible extension modules
≤ 32 (per wireless module)
Designation
Wireless network
Number of supported devices
≤ 99 (I/O extension modules per wireless network, serial interfaces deactivated) 0 (no I/O extension modules can be used) ≤ 99 (I/O extension modules per wireless network, access to extension modules via Modbus RTU protocol)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30.5 V DC
Max. current consumption
≤ 65 mA (at 24 V DC, at 25 °C, stand-alone) ≤ 6 A (at 24 V DC, with DIN rail connector at full capacity)
Output name
RF link relay output
Number of outputs
1
Contact switching type
Changeover contact
Contact material
PdRu, gold-plated
Maximum switching voltage
30 V AC/DC 60 V DC
Max. switching current
500 mA (30 V AC/DC) 300 mA (60 V DC)
Electrical service life
5x 10
Output name
RSSI voltage output
Number of outputs
1
Voltage output signal
0 V ... 3 V
Connection method
Screw connection
Stripping length
7 mm
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Range
≤ 5 km (The range may be considerably above or below that stated, and depends on the environment, antenna technology, and the product used)
Data rate
300 bps / 600 bps / 1.2 kbps / 2.4 kbps / 4.8 kbps / 9.6 kbps / 19.2 kbps / 38.4 kbps / 57.6 kbps / 93.75 kbps / 115.2 kbps
Connection method
COMBICON plug-in screw terminal block
Connection technology
3-conductor
Transmission length
≤ 15 m
Data rate
300 bps / 600 bps / 1.2 kbps / 2.4 kbps / 4.8 kbps / 9.6 kbps / 19.2 kbps / 38.4 kbps / 57.6 kbps / 93.75 kbps / 115.2 kbps / 187.5 kbps
Connection method
COMBICON plug-in screw terminal block
Connection technology
2-conductor
Transmission length
≤ 1200 m
Termination resistor
390 Ω (switchable via DIP switches) 150 Ω (switchable via DIP switches) 390 Ω (switchable via DIP switches)
Connection method
S-PORT (socket)
Interface description
Trusted Wireless
Direction
Bi-directional
Frequency
2400 MHz
Frequency range
2.4002 GHz ... 2.4785 GHz
Channel distance
1.3 MHz
Number of channel groups
8
Number of channels per group
55
Transmit capacity, minimum
0 dBm
Transmit capacity, maximum
≤ 20 dBm (100 mW, outside of Europe, adjustable via software) ≤ 19 dBm (Europe, can be set via software, depends on the data rate) 18 dBm (Default setting, adjustable)
Data rate
16 kbps (adjustable) 125 kbps (Default setting, adjustable) 250 kbps (adjustable)
Minimum receiver sensitivity
-106 dBm (16 kbps) -96 dBm (125 kbps) -93 dBm (250 kbps)
Antenna connection method
RSMA (female)
Security
128-bit data encryption
Wireless licenses
Europe, USA, Canada, additional countries in the e-shop
Frequency band
2.4 GHz
Wireless standard
Trusted Wireless
Status display
LED supply voltage, PWR (green) Green LED (bus communication, DAT) LED periphery error, ERR (red) 3x green, 1x yellow LED (LED bar graph receive quality, RSSI) Green LED (receive data, RX) Green LED (transmit data, TX)
Width
17.5 mm
Height
116 mm
Depth
114.5 mm
Color (Housing)
gray (RAL 7042)
Material (Housing)
PA 6.6-FR
Flammability rating according to UL 94
V0
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C (>55°C derating, see technical documentation) -40 °F ... 158 °F (>131°F derating, see technical documentation)
Ambient temperature (storage/transport)
-40 °C ... 85 °C -40 °F ... 185 °F
Altitude
2000 m
Permissible humidity (operation)
20 % ... 85 %
Permissible humidity (storage/transport)
20 % ... 85 %
Shock
16g, 11 ms
Vibration (operation)
in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
Certificate
CE-compliant
Identification
 II 3 G   Ex ec nC IIC T4 Gc
Certificate
IBExU 15 ATEX B008 X
Note
Please follow the special installation instructions in the documentation!
Identification
Ex ec nC IIC T4 Gc
Certificate
IECEx IBE 13.0019X
Identification
2Ex nA nC IIC T4 Gc X
Certificate
RU C-DE.HB49.B.00033/20
Identification
508 Listed Class I, Div. 2, Groups A, B, C, D T4A Class I, Zone 2, IIC T4
Identification
Ex ec nC IIC T4 Gc
Certificate
2022122310115624
Note
RED 2014/53/EU
Certificate
YG3RAD2400A
Note
FCC directive, part 15.247
Certificate
C-27397
Certificate
-
Certificate
06279-19-06497
Certificate
NER-ETA/314
Certificate
4720B-RAD2400A
Note
ISC directive RSS 210
Certificate
MR 10464 ANRT 2015
Certificate
IFT RCPPHRA17-1112
Certificate
MSIP-CRI-PCK-2901541
Certificate
KTL 20-KA4BO-0146X
Certificate
CCAJ18LP1990T7
Certificate
ER0126713
Identification
ISA-S71.04-1985 G3 Harsh Group A
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Standards/regulations
EN 61000-4-2
Contact discharge
± 6 kV (Test Level 3)
Discharge in air
± 8 kV (Test Level 3)
Indirect discharge
± 6 kV
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
26 MHz ... 3 GHz (Test Level 3)
Field intensity
10 V/m
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
± 2 kV (Test Level 3)
Signal
± 2 kV
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
± 0.5 kV (symmetrical) ± 1 kV (asymmetrical)
Signal
± 1 kV (asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V
Emitted radio interference in acc. with EN 55011
EN 55016-2-3 Class A industrial applications
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Standard designation
Ex Directive (ATEX)
Standards/specifications
EN 60079-0
Standard designation
Ex Directive (ATEX)
Standards/specifications
EN 60079-15
Standards/specifications
EN 300328 EN 61000-6-4 EN 61000-6-2 EN 50371 EN 60950-1
Mounting type
DIN rail mounting
Assembly note
on standard DIN rail NS 35 in accordance with EN 60715

Specifications may be subject to change without notice