Product Model

RAD-ISM-2400-PIPE-SET-UD-ANT

In Stock
Last updated: 2025/4/18
Phoenix Contact RAD-ISM-2400-PIPE-SET-UD-ANT

Selling Points

  • 1Transmits digital and analog signals with high accuracy, ensuring reliable data transmission in industrial environments.
  • 2Simple setup with automatic radio connection establishment, reducing installation time and effort.
  • 3Detects digital signals from 5-30 V AC/DC and one analog current signal (4-20 mA), accommodating various sensor inputs.
  • 4Built to withstand ambient temperatures from -20°C to +65°C, making it suitable for harsh industrial conditions.
  • 5Supports multiple receivers for expanded coverage and signal division or multiplication as needed.
Product Details
RAD-ISM-2400-PIPE-SET-UD-ANT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Wireless module
Supply voltage
24 V DC -50 % / +25 % (at U 230 V AC
Supply voltage range
12 V DC ... 30 V DC 85 V AC ... 250 V AC
Typical current consumption
115 mA
Max. current consumption
145 mA (at 24 V DC)
Supply voltage
24 V DC -75 % / +25 % 230 V AC
Supply voltage range
12 V DC ... 30 V DC 85 V AC ... 250 V AC
Typical current consumption
50 mA
Max. current consumption
65 mA (at 24 V DC)
Input voltage range
5 V AC/DC ... 30 V AC/DC
Switching threshold "0" signal, voltage
max. 1.5 V DC
Switching threshold "1" signal voltage
min. 5 V DC
Description of the input
Current input (analog input)
Current input signal
4 mA ... 20 mA
Input resistance current input
< 170 Ω
Description of the input
Voltage input (digital input)
Output name
2x relay output + 1 x RF link
Contact switching type
3 floating changeover contacts
Contact material
Ag, gold-plated
Maximum switching voltage
250 V AC/DC
Limiting continuous current
0.5 A
Service life electrical
8x 10
Mechanical service life
1x 10
Output name
Current output
Current output signal
4 mA ... 20 mA
Load/output load current output
700 Ω (at U
Connection method
Spring-cage connection (M12)
Conductor cross section flexible min.
0.14 mm²
Conductor cross section flexible max.
0.5 mm²
Conductor cross section AWG min.
20
Conductor cross section AWG max.
26
Direction
Uni-directional
Direction
Uni-directional
Frequency range
2.4032 GHz ... 2.4799 GHz
Channel distance
100 kHz
Number of channel groups
9
Number of channels per group
63
Transmission power
10 mW
Frequency band
2.4 GHz
Width
92 mm
Height
98 mm
Depth
340 mm
Material (Housing)
Aluminum PBT
Degree of protection
IP65 IP65
Degree of protection
IP65
Ambient temperature (operation)
-20 °C ... 65 °C -4 °F ... 149 °F -20 °C ... 65 °C -4 °F ... 149 °F
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Certificate
CE-compliant
Identification
 II 3 G Ex nL IIC T4
Note
Please follow the special installation instructions in the documentation!
Identification
Ex nL IIC T4
Electromagnetic compatibility
Conformance with R&TTE directive 1999/5/EC

Specifications may be subject to change without notice