Phoenix Contact RIF-1-RPT-LDP-24DC/1X21

Selling Points

  • 1DIN Rail Mounting: Easy installation on DIN rail for compact and efficient use.
  • 224V DC Coil: Compatible with 24V DC power for reliable operation in various systems.
  • 311A Load Current: Handles up to 11A load current, suitable for medium to high power applications.
  • 4SPDT Configuration: Single-pole double-throw (SPDT) contact configuration for versatile switching needs.
  • 5High Reliability: Designed with silver alloy contacts and a protective circuit for long-lasting performance.
Product Details
RIF-1-RPT-LDP-24DC/1X21
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Notes on operation
FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21)
Product type
Relay Module
Product family
RIFLINE complete
Application
Universal
Operating mode
100% operating factor
Mechanical service life
approx. 3x 10
Date of last data management
15.10.2024
Article revision
08
Insulation
Safe isolation between input and output Basic insulation between the changeover contacts
Overvoltage category
III
Pollution degree
2
Service life electrical
see diagram
Maximum power dissipation for nominal condition
0.43 W
Test voltage (Winding/contact)
4 kV
Rated insulation voltage
250 V AC
Rated surge voltage
6 kV (Input/output) 4 kV (between the changeover contacts)
Nominal input voltage U
24 V DC
Input voltage range
19.2 V DC ... 33.6 V DC (20 °C)
Input voltage range in reference to U
see diagram
Drive and function
monostable
Drive (polarity)
polarized
Typical input current at U
18 mA
Typical response time
8 ms
Typical release time
10 ms
Coil voltage
24 V DC
Protective circuit
Freewheeling diode
Operating voltage display
Yellow LED
Contact switching type
1 changeover contact
Type of switch contact
Single contact
Contact material
AgNi
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
12 V (10 mA)
Limiting continuous current
11 A (see diagram)
Maximum inrush current
50 A (20 ms, N/O contacts)
Min. switching current
10 mA (12 V)
Interrupting rating (ohmic load) max.
264 W (24 V DC) 58 W (48 V DC) 48 W (60 V DC) 50 W (110 V DC) 80 W (220 V DC) 2750 VA (250 V AC)
Utilization category CB Scheme (IEC 60947-5-1)
AC15, 1.5 A/240 V (N/O contact) AC15, 3 A/250 V (N/C contact) DC13, 2 A/24 V (N/C contact) DC13, 0.2 A/250 V (N/O contact)
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 1.5 mm²
Conductor cross section flexible
0.14 mm² ... 1.5 mm² 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG
26 ... 16 (solid) 26 ... 16 (flexible)
Diameter
3.2 mm
Width
16 mm
Height
96 mm
Depth
75 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V2 (Housing)
Degree of protection (Relay base)
IP20 (Relay base)
Degree of protection (Relay)
RT III (Relay)
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Standards/regulations
IEC 60947-5-1
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice