Product Model

RIF-1-RPT-LV-230AC/1X21AU

In Stock
Last updated: 2025/4/19
Phoenix Contact RIF-1-RPT-LV-230AC/1X21AU

Selling Points

  • 1High Switching Voltage: Handles up to 250 V AC/DC with a minimum switching voltage of 12 V.
  • 2Reliable Contacts: Equipped with AgNi, hard gold-plated contacts for durability and reliability.
  • 3Compact Design: Measures 16 mm wide, 93 mm high, and 75 mm deep, ideal for space-constrained applications.
  • 4Wide Operating Range: Operates within an ambient temperature range of -40 °C to 50 °C and storage/transport range of -40 °C to 85 °C.
  • 5Comprehensive Protection: Includes a varistor for overvoltage protection and a yellow LED for operating voltage display.
Product Details
RIF-1-RPT-LV-230AC/1X21AU
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Notes on operation
FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21)
Product type
Relay Module
Product family
RIFLINE complete
Application
Universal
Operating mode
100% operating factor
Mechanical service life
approx. 10
Date of last data management
10.06.2024
Article revision
05
Insulation
Safe isolation between input and output Basic insulation between the changeover contacts
Overvoltage category
III
Pollution degree
2
Service life electrical
see diagram
Maximum power dissipation for nominal condition
1.38 W
Test voltage (Winding/contact)
4 kV
Rated insulation voltage
250 V AC
Rated surge voltage
6 kV (Input/output) 4 kV (between the changeover contacts)
Nominal input voltage U
230 V AC
Input voltage range
184 V AC ... 264.5 V AC (20 °C)
Input voltage range in reference to U
see diagram
Mains frequency
50/60 Hz
Drive and function
monostable
Typical input current at U
6 mA
Typical response time
3 ms ... 12 ms
Typical release time range
3 ms ... 20 ms
Coil voltage
230 V AC
Protective circuit
Varistor
Operating voltage display
Yellow LED
Contact switching type
1 changeover contact
Type of switch contact
Single contact
Contact material
AgNi, hard gold-plated
Maximum switching voltage
30 V AC 36 V DC
Minimum switching voltage
100 mV (10 mA)
Limiting continuous current
50 mA
Maximum inrush current
50 mA
Min. switching current
1 mA (24 V)
Interrupting rating (ohmic load) max.
1.2 W (24 V DC)
Utilization category CB Scheme (IEC 60947-5-1)
AC15, 1.5 A/240 V (N/O contact) AC15, 3 A/250 V (N/C contact) DC13, 2 A/24 V (N/C contact) DC13, 0.2 A/250 V (N/O contact)
Note
Contact material
AgNi
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
12 V (at 10 mA)
Limiting continuous current
25 A (20 ms, N/O contacts)
Min. switching current
10 mA (at 12 V)
Interrupting rating (ohmic load) max.
240 W (at 24 V DC) 58 W (at 48 V DC) 48 W (at 60 V DC) 50 W (at 110 V DC) 80 W (at 220 V DC) 2500 VA (for 250 V AC)
Switching capacity
2 A (at 24 V, DC13) 0.2 A (at 110 V, DC13) 0.2 A (at 250 V, DC13) 2 A (at 24 V, AC15) 2 A (at 120 V, AC15) 2 A (at 250 V, AC15)
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 1.5 mm²
Conductor cross section flexible
0.14 mm² ... 1.5 mm² 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG
26 ... 16 (solid) 26 ... 16 (flexible)
Diameter
3.2 mm
Width
16 mm
Height
93 mm
Depth
75 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V2 (Housing)
Degree of protection (Relay base)
IP20 (Relay base)
Degree of protection (Relay)
RT II (Relay)
Ambient temperature (operation)
-40 °C ... 50 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Standards/regulations
DIN EN 50178
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice