Product Model
RIF-1-RPT-LV-24AC/2X21

Selling Points
- No selling points available for this product.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Notes on operation | FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21) | Product type | Relay Module |
Product family | RIFLINE complete | Application | Universal |
Operating mode | 100% operating factor | Mechanical service life | approx. 10 |
Date of last data management | 14.08.2024 | Article revision | 08 |
Insulation | Safe isolation between input and output
Basic insulation between the changeover contacts | Overvoltage category | III |
Pollution degree | 2 | Service life electrical | see diagram |
Maximum power dissipation for nominal condition | 0.79 W | Test voltage (Winding/contact) | 4 kV |
Test voltage (Changeover contact/changeover contact) | 2.5 kV | Rated surge voltage | 6 kV (Input/output)
4 kV (between the changeover contacts) |
Nominal input voltage U | 24 V AC | Input voltage range | 19.2 V AC ... 27.6 V AC (20 °C) |
Input voltage range in reference to U | see diagram | Mains frequency | 50/60 Hz |
Drive and function | monostable | Drive (polarity) | polarized |
Typical input current at U | 33 mA | Typical response time | 3 ms ... 12 ms |
Typical release time range | 3 ms ... 20 ms | Coil voltage | 24 V AC |
Protective circuit | Varistor | Operating voltage display | Yellow LED |
Contact switching type | 2 changeover contacts | Type of switch contact | Single contact |
Contact material | AgNi | Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 5 V (10 mA) | Limiting continuous current | 8 A (see diagram) |
Maximum inrush current | 12 A (20 ms, N/O contacts) | Min. switching current | 10 mA (5 V) |
Interrupting rating (ohmic load) max. | 192 W (at 24 V DC)
96 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
57 W (at 220 V DC)
2000 VA (for 250 V AC) | Utilization category CB Scheme (IEC 60947-5-1) | AC15, 1.5 A/240 V (N/O contact)
AC15, 2 A/250 V (N/C contact)
DC13, 2 A/24 V (N/C contact)
DC13, 0.2 A/250 V (N/O contact) |
Connection method | Push-in connection | Stripping length | 8 mm |
Conductor cross section rigid | 0.14 mm² ... 1.5 mm² | Conductor cross section flexible | 0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve)
0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block) |
Conductor cross section AWG | 26 ... 16 (solid)
26 ... 16 (flexible) | Diameter | 3.2 mm |
Width | 16 mm | Height | 96 mm |
Depth | 75 mm | Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V2 (Housing) | Degree of protection (Relay base) | IP20 (Relay base) |
Degree of protection (Relay) | RT III (Relay) | Ambient temperature (operation) | -40 °C ... 50 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60 |
Standards/regulations | IEC 60947-5-1 | Mounting type | DIN rail mounting |
Assembly note | in rows with zero spacing | Mounting position | any |
Specifications may be subject to change without notice