Phoenix Contact RIF-1-RSC-LDP-24DC/1ICT

Selling Points

  • 1DIN Rail Mount: Compact and easy to install on DIN rail.
  • 224V DC Coil: Reliable operation with a 24V DC coil voltage.
  • 3SPST Configuration: Single-pole single-throw (SPST) contact configuration.
  • 4IP20 Relay Base: Enhanced protection with an IP20-rated relay base.
  • 5LED Operation Indicator: Visual confirmation with an LED operation indicator.
Product Details
RIF-1-RSC-LDP-24DC/1ICT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Notes on operation
FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21)
Notes on operation
At least a basic level of insulation is maintained against adjacent modules in the DIN rail direction. If the application has higher requirements on the insulation (reinforced insulation), then these must be realized through suitable measures (e.g. partition plates).
Notes on operation
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Product type
Relay Module
Product family
RIFLINE complete
Application
high inrush currents
Operating mode
100% operating factor
Mechanical service life
3x 10
Date of last data management
21.08.2024
Article revision
02
Insulation
Safe isolation, reinforced insulation
Overvoltage category
III
Pollution degree
2
Maximum power dissipation for nominal condition
0.43 W
Test voltage (Winding/contact)
4 kV AC (50 Hz, 1 min., winding/contact)
Rated surge voltage
6 kV
Nominal input voltage U
24 V DC
Input voltage range
19.2 V DC ... 33.6 V DC (20 °C)
Input voltage range in reference to U
see diagram
Drive and function
monostable
Drive (polarity)
polarized
Typical input current at U
18 mA
Typical response time
8 ms
Typical release time
10 ms
Coil voltage
24 V DC
Protective circuit
Reverse polarity protection; Polarity protection diode Surge protection; Freewheeling diode
Operating voltage display
Yellow LED
Contact switching type
1 N/O contact
Type of switch contact
Single contact
Note regarding the switch contact
With tungsten leading contact
Contact material
AgSnO
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
12 V (100 mA)
Limiting continuous current
6 A 10 A (Value is permissible if connections 11 and 21, as well as connections 14 and 24 are bridged.)
Maximum inrush current
165 A (20 ms) 800 A (200 µs)
Min. switching current
100 mA (12 V DC)
Interrupting rating (ohmic load) max.
264 W (at 24 V DC, observe contact derating) 58 W (at 48 V DC) 48 W (at 60 V DC) 50 W (at 110 V DC) 80 W (at 220 V DC) 2750 VA (at 250 V AC, observe contact derating)
Switching capacity min.
1200 mW
Utilization category CB Scheme (IEC 60947-5-1)
AC15, 6 A/250 V (N/O contact) DC13, 2 A/24 V (N/O contact)
Connection method
Screw connection
Stripping length
8 mm
Conductor cross section rigid
0.5 mm² ... 4 mm²
Conductor cross-section rigid (2 conductors with same cross section)
0.5 mm² ... 2.5 mm²
Conductor cross section flexible
0.5 mm² ... 4 mm² 0.5 mm² ... 4 mm² (Ferrule with plastic sleeve)
Conductor cross section flexible (2 conductors with same cross section)
0.5 mm² ... 2.5 mm² 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve)
Conductor cross section AWG
20 ... 10 (solid) 20 ... 12 (flexible)
Tightening torque
0.5 Nm ... 0.6 Nm
Width
16 mm
Height
90 mm
Depth
75 mm
Color
gray (RAL 7042)
Degree of protection (Relay)
RT II (Relay)
Degree of protection (Relay base)
IP20 (Relay base)
Degree of protection (Installation location)
≥ IP54 (Installation location)
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Standards/regulations
IEC 60947-5-1
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice