Product Model
RIF-1-RSC-LV-120AC/2X21

Selling Points
- 1Supports up to 250 V AC/DC, ensuring reliable operation in diverse electrical environments.
- 2Utilizes silver-nickel (AgNi) contacts for long-lasting performance and minimal wear.
- 3Pre-assembled with a relay base, power contact relay, and interference suppression module for enhanced reliability.
- 4Offers a typical response time of 3 ms to 12 ms and release time range of 3 ms to 20 ms.
- 5Compatible with screw connections and flexible conductor cross-sections, accommodating various wiring configurations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Notes on operation | FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21) | Product type | Relay Module |
Product family | RIFLINE complete | Application | Universal |
Operating mode | 100% operating factor | Mechanical service life | approx. 10 |
Date of last data management | 21.08.2024 | Article revision | 05 |
Insulation | Safe isolation between input and output
Basic insulation between the changeover contacts | Overvoltage category | III |
Pollution degree | 2 | Service life electrical | see diagram |
Maximum power dissipation for nominal condition | 1 W | Test voltage (Winding/contact) | 4 kV |
Test voltage (Changeover contact/changeover contact) | 2.5 kV | Rated insulation voltage | 250 V AC |
Rated surge voltage | 6 kV (Input/output)
4 kV (between the changeover contacts) | Nominal input voltage U | 120 V AC |
Input voltage range | 96 V AC ... 138 V AC (20 °C) | Input voltage range in reference to U | see diagram |
Mains frequency | 50/60 Hz | Drive and function | monostable |
Drive (polarity) | polarized | Typical input current at U | 8 mA |
Typical response time | 3 ms ... 12 ms | Typical release time range | 3 ms ... 20 ms |
Coil voltage | 120 V AC | Protective circuit | Varistor |
Operating voltage display | Yellow LED | Contact switching type | 2 changeover contacts |
Type of switch contact | Single contact | Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC | Minimum switching voltage | 5 V (10 mA) |
Limiting continuous current | 8 A (see diagram) | Maximum inrush current | 12 A (20 ms, N/O contacts) |
Min. switching current | 10 mA (5 V) | Interrupting rating (ohmic load) max. | 192 W (at 24 V DC)
124 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
57 W (at 220 V DC)
2000 VA (for 250 V AC) |
Utilization category CB Scheme (IEC 60947-5-1) | AC15, 1.5 A/240 V (N/O contact)
AC15, 2 A/250 V (N/C contact)
DC13, 2 A/24 V (N/C contact)
DC13, 0.2 A/250 V (N/O contact) | Connection method | Screw connection |
Stripping length | 8 mm | Conductor cross section rigid | 0.5 mm² ... 4 mm² |
Conductor cross-section rigid (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm² | Conductor cross section flexible | 0.5 mm² ... 4 mm²
0.5 mm² ... 4 mm² (Ferrule with plastic sleeve) |
Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm²
0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) | Conductor cross section AWG | 20 ... 10 (solid)
20 ... 12 (flexible) |
Tightening torque | 0.5 Nm ... 0.6 Nm | Width | 16 mm |
Height | 90 mm | Depth | 75 mm |
Color | gray (RAL 7042) | Flammability rating according to UL 94 | V2 (Housing) |
Degree of protection (Relay base) | IP20 (Relay base) | Degree of protection (Relay) | RT III (Relay) |
Ambient temperature (operation) | -40 °C ... 50 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60 | Standards/regulations | IEC 60947-5-1 |
Mounting type | DIN rail mounting | Assembly note | in rows with zero spacing |
Mounting position | any |
Specifications may be subject to change without notice