Product Model

RIF-3-RPT-LV-120AC/2X21

In Stock
Last updated: 2025/4/18
Phoenix Contact RIF-3-RPT-LV-120AC/2X21

Selling Points

  • 1Universal Application: Suitable for a wide range of industrial applications.
  • 2Basic Insulation: Meets overvoltage category III and pollution degree 2 standards.
  • 3High Reliability: Approximate mechanical service life of 2 x 107 cycles.
  • 4Efficient Design: Push-in connection with a typical input current of 23 mA at 120 V AC.
  • 5Advanced Safety Features: Includes a varistor protective circuit and yellow LED operating voltage display.
Product Details
RIF-3-RPT-LV-120AC/2X21
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Relay Module
Product family
RIFLINE complete
Application
Universal
Operating mode
100% operating factor
Mechanical service life
approx. 2x 10
Date of last data management
10.06.2024
Article revision
05
Insulation
Basic insulation
Overvoltage category
III
Pollution degree
2
Maximum power dissipation for nominal condition
2.76 W
Test voltage (Winding/contact)
2.5 kV
Test voltage (Contact/contact)
2 kV
Rated insulation voltage
250 V AC
Rated surge voltage
4 kV
Nominal input voltage U
120 V AC
Input voltage range
102 V AC ... 132 V AC (20 °C)
Input voltage range in reference to U
see diagram
Mains frequency
50/60 Hz
Drive and function
monostable
Typical input current at U
23 mA
Typical response time
5 ms ... 15 ms
Typical release time range
5 ms ... 20 ms
Coil voltage
120 V AC
Protective circuit
Varistor
Operating voltage display
Yellow LED
Contact switching type
2 changeover contacts
Type of switch contact
Single contact
Contact material
AgNi
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
10 V (24 mA)
Limiting continuous current
7 A (see diagram)
Maximum inrush current
30 A (20 ms, N/O contacts)
Min. switching current
10 mA (24 V)
Interrupting rating (ohmic load) max.
168 W (24 V DC) 124 W (48 V DC) 108 W (60 V DC) 52 W (110 V DC) 48 W (220 V DC) 1750 VA (250 V AC)
Utilization category CB Scheme (IEC 60947-5-1)
AC15, 1.5 A/240 V (N/O contact) DC13, 2 A/240 V (N/O contact)
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 1.5 mm²
Conductor cross section flexible
0.14 mm² ... 1.5 mm² 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG
26 ... 16 (solid) 26 ... 16 (flexible)
Diameter
3.2 mm
Width
40 mm
Height
103 mm
Depth
90 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V2 (Housing)
Degree of protection (Relay base)
IP20 (Relay base)
Degree of protection (Relay)
RT I (Relay)
Ambient temperature (operation)
-40 °C ... 50 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Standards/regulations
DIN EN 50178
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice