Product Model

RIF-4-RPT-LV-230AC/3X1

In Stock
Last updated: 2025/4/19
Phoenix Contact RIF-4-RPT-LV-230AC/3X1

Selling Points

  • 1High Performance Reliability: Designed for 100% operating factor with a mechanical service life of approximately 107 cycles.
  • 2Versatile Connectivity: Pre-assembled with push-in connection, including relay base, power contact relay, plug-in display/interference suppression module, and retaining bracket.
  • 3Wide Voltage Range: Operates with a nominal input voltage of 230 V AC and a maximum switching voltage of 440 V AC.
  • 4Advanced Insulation: Basic insulation with an overvoltage category of III and pollution degree of 2.
  • 5Durable Construction: Made with AgNi contact material and a flammability rating of V2 according to UL 94 for housing.
Product Details
RIF-4-RPT-LV-230AC/3X1
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Relay Module
Product family
RIFLINE complete
Application
Universal
Operating mode
100% operating factor
Mechanical service life
approx. 10
Date of last data management
31.10.2024
Article revision
07
Insulation
Basic insulation
Overvoltage category
III
Pollution degree
2
Maximum power dissipation for nominal condition
3.22 W
Test voltage (Winding/contact)
2.5 kV
Test voltage (Contact/contact)
2.5 kV
Rated insulation voltage
250 V AC
Rated surge voltage
4 kV
Nominal input voltage U
230 V AC
Input voltage range
195.5 V AC ... 253 V AC (20 °C)
Input voltage range in reference to U
see diagram
Mains frequency
50/60 Hz
Drive and function
monostable
Typical input current at U
14 mA
Typical response time
5 ms ... 25 ms
Typical release time range
5 ms ... 20 ms
Coil voltage
230 V AC
Protective circuit
Varistor
Operating voltage display
Yellow LED
Contact switching type
3 N/O contacts
Type of switch contact
Single contact
Contact material
AgNi
Maximum switching voltage
440 V AC 250 V DC
Minimum switching voltage
10 V (24 mA)
Limiting continuous current
8 A (see diagram)
Maximum inrush current
50 A (20 ms, N/O contacts)
Min. switching current
10 mA (24 V)
Interrupting rating (ohmic load) max.
216 W (24 V DC) 480 W (48 V DC) 600 W (60 V DC) 660 W (110 V DC) 183 W (220 V DC) 2250 VA (250 V AC) 4000 VA (440 V AC)
Motor load according to UL 508
1/3 HP, 120 V AC (single-phase AC motor) 1/2 HP, 240 V AC (single-phase AC motor) 1/2 HP, 240 V AC (three-phase induction motor)
Utilization category CB Scheme (IEC 60947-5-1)
AC15, 1.5 A/240 V (N/O contact) DC13, 2 A/240 V (N/O contact)
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 1.5 mm²
Conductor cross section flexible
0.14 mm² ... 1.5 mm² 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG
26 ... 16 (solid) 26 ... 16 (flexible)
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm² 0.14 mm² ... 2.5 mm² (Ferrule with plastic sleeve) 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG
26 ... 14 (solid) 26 ... 14 (flexible)
Diameter
3.2 mm
Width
43 mm
Height
111 mm
Depth
90 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V2 (Housing)
Degree of protection (Relay base)
IP20 (Relay base)
Degree of protection (Relay)
RT I (Relay)
Ambient temperature (operation)
-40 °C ... 40 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Standards/regulations
DIN EN 50178
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice