Product Model

RIF-T3-24UC

In Stock
Last updated: 2025/4/21
Phoenix Contact RIF-T3-24UC

Selling Points

  • 1Supports 3 time functions and 4 time ranges for diverse application needs.
  • 2Operates reliably from -25°C to 50°C, ensuring consistent performance in various environments.
  • 3Designed for mounting on RIF-1, RIF-2, RIF-3, and RIF-4 relay modules.
  • 4Measures 13 mm in width, 12 mm in height, and 35 mm in depth for space-efficient installation.
  • 5Offers a general setting accuracy of 3% and repeat accuracy of 1% for precise timing control.
Product Details
RIF-T3-24UC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Plug-in module
Product family
RIFLINE complete
Article revision
04
Insulation
Basic insulation
Overvoltage category
I
Pollution degree
2
Setting accuracy
3 % (of scale end value)
Nominal voltage U
24 V AC/DC
Repeat accuracy
1 %
Rated insulation voltage
50 V DC
Rated surge voltage
0.4 kV
Nominal input voltage U
24 V DC (AC operation only permitted for RIF-1)
Input voltage range in reference to U
0.4 ... 1.2
Mains frequency
50 Hz 60 Hz
Status display
LED (yellow)
Protective circuit
Varistor
Surge voltage protection
> 56 V
Limiting continuous current
≤ 250 mA (Relay coil current)
Voltage drop at max. limiting continuous current
< 100 mV
Width
13 mm
Height
12 mm
Depth
35 mm
Ambient temperature (operation)
-25 °C ... 50 °C (RIF-1, AC coil, 2 changeover contacts at 6 A) -25 °C ... 50 °C (RIF-1, DC coil, 2 changeover contacts at 5 A) -25 °C ... 40 °C (RIF-2, DC coil, 2 changeover contacts at 8 A) -25 °C ... 40 °C (RIF-2, DC coil, 4 changeover contacts at 5 A) -25 °C ... 40 °C (RIF-3, DC coil, 3 changeover contacts at 6.75 A) -25 °C ... 40 °C (RIF-3, DC coil, 2 changeover contacts at 8 A) -25 °C ... 35 °C (RIF-4, DC coil, 3 changeover contacts at 8 A) -25 °C ... 25 °C (RIF-4, DC coil, 3 N/O contacts at 8 A)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Certificate
UKCA-compliant
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Standards/regulations
IEC 60947-5-1
Assembly note
Can be inserted into relay base
Mounting position
any