Phoenix Contact TRIO3-PS/1AC/24DC/10/CO

Selling Points

  • 1Typ. 94.5% efficiency ensures optimal energy use.
  • 2Metal housing with IP20 protection rating for secure operation.
  • 3Operates within 100 V AC to 240 V AC with ±10% tolerance.
  • 4Ambient temperature range from -25 °C to 70 °C.
  • 5DIN rail mounting for straightforward integration into control cabinets.
Product Details
TRIO3-PS/1AC/24DC/10/CO
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Supply system configuration
Star network (TN, TT, IT (PE))
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 % 115 V AC ... 240 V AC ±10 % (UL)
Derating
< 100 V AC (1 %/V) 2.5 %/K, > 60 °C
Typical national grid voltage
120 V AC 230 V AC
Voltage type of supply voltage
AC
Inrush current
< 17 A (25 °C)
Inrush current integral (I
< 0.5 A
Frequency range (f
50 Hz ... 60 Hz ±10 %
Mains buffering time
typ. 27 ms (120 V AC) typ. 28 ms (230 V AC)
Current consumption
2.6 A (100 V AC) 2.2 A (120 V AC) 1.2 A (230 V AC) 1.1 A (240 V AC)
Protective circuit
Transient protection; Varistor
Power factor (cos phi)
0.95 (230 V AC)
Device mains fuse
6.3 A internal (device protection)
Recommended breaker for input protection
6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE
< 3.5 mA
Input voltage range
100 V DC ... 240 V DC ±10 % 160 V DC ... 240 V DC ±10 % (UL)
Derating
< 140 V DC (1 %/V)
Current consumption
2.7 A (100 V DC) 1.1 A (240 V DC)
Efficiency
typ. 94.5 % (120 V AC) typ. 95.5 % (230 V AC)
Nominal output voltage
24 V DC
Setting range of the output voltage (U
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I
10 A
Dynamic Boost (I
max. 15 A (5 s)
Short-circuit-proof
yes
No-load proof
yes
Derating
60 °C ... 70 °C
Crest factor
typ. 1.75 (120 V AC) typ. 1,7 (230 V AC)
Output power (P
240 W
Output power (P
max. 360 W (5 s)
Connection in parallel
yes, for increased efficiency and redundancy
Connection in series
yes, for increased output voltage (observe SELV limit)
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
≤ 35 V DC
Residual ripple
typ. 50 mV
Control deviation
< 1 % (change in load, static 10 % ... 90 %) < 3 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %)
Rise time
≤ 1 s (U
Minimum no-load power dissipation
< 1.2 W (120 V AC)
Maximum no-load power dissipation
< 1.3 W (230 V AC)
Minimum nominal load power dissipation
< 14.5 W (120 V AC)
Power loss nominal load max.
< 12 W (230 V AC)
Integrated fuse protection
no
Position
3.x
Position marking
3.1 (13), 3.2 (14)
Switch contact (floating)
OptoMOS
Switching voltage
max. 30 V DC (SELV)
Current carrying capacity
max. 100 mA
State condition
U U
Position
1.x
Position marking
1.1 (L/+), 1.2 (N/-), 1.3 ()
Connection method
Push-in connection
rigid
0.2 mm² ... 4 mm² 1.5 mm² (recommended)
flexible
0.2 mm² ... 2.5 mm² 1.5 mm² (recommended)
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm² 1.5 mm² (recommended)
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm² 1.5 mm² (recommended)
rigid (AWG)
24 ... 12 (Cu) 16 (recommended)
Stripping length
10 mm (Rigid/flexible/ferrule)
Position
2.x
Position marking
2.1, 2.2 (+), 2.3, 2.4, 2.5 (-)
Connection method
Push-in connection
rigid
0.2 mm² ... 4 mm² 1.5 mm² (recommended)
flexible
0.2 mm² ... 2.5 mm² 1.5 mm² (recommended)
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm² (Cu) 1.5 mm² (recommended)
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm² 1.5 mm² (recommended)
rigid (AWG)
24 ... 12 (Cu) 16 (recommended)
Stripping length
10 mm (Rigid/flexible/ferrule)
Position
3.x
Position marking
3.1 (13), 3.2 (14)
Connection method
Push-in connection
rigid
0.2 mm² ... 1.5 mm² 0.5 mm² (recommended)
flexible
0.2 mm² ... 1.5 mm² 0.5 mm² (recommended)
flexible with ferrule without plastic sleeve
0.25 mm² ... 1.5 mm² (Cu) 0.5 mm² (recommended)
flexible with ferrule with plastic sleeve
0.25 mm² ... 0.75 mm² 0.5 mm² (recommended)
rigid (AWG)
24 ... 16 (Cu) 20 (recommended)
Stripping length
10 mm (Rigid/flexible/ferrule)
Types of signaling
LED DC OK – signal state operation (U
Function
Visual operating state display
Color
red, yellow, green (multicolor LED)
LED off
Supply voltage input AC not present (Off)
LED on (green), DC OK
U
LED on (yellow), IOut > 90%
U
LED on (red), ISHORT
U
LED on (flashing red) OVP
U
Number of phases
1.00
Insulation voltage input/output
3 kV AC (type test) 3.1 kV DC (routine test)
Product type
Power supply
Product family
TRIO POWER
MTBF (IEC 61709, SN 29500)
> 2300000 h (25 °C) > 1300000 h (40 °C) > 610000 h (60 °C)
Environmental protection directive
RoHS Directive 2011/65/EU WEEE Reach
Article revision
00
Protection class
I
Degree of pollution
2
Width
40 mm
Height
135 mm
Depth
132 mm 125 mm (Device depth (DIN rail mounting))
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Mounting type
DIN rail mounting
Assembly note
alignable: 0 mm horizontally, 30 mm vertically
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
yes
Flammability rating according to UL 94
V0 (Housing, terminal blocks)
Hood version
Polycarbonate
Side element version
Aluminum
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock (operation)
18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation)
10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6) 50 Hz ... 150 Hz, 2.3g, 90 min.
Temp code
T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K)
EN 61010-1
III (≤ 2000 m) II (≤ 5000 m)
EN 61010-2-201
III (≤ 2000 m) II (≤ 5000 m)
Standard designation
Safety of power supply units up to 1100 V (insulation distances)
Standards/specifications
DIN EN 61558-2-16
Standard designation
Electrical safety
Standards/specifications
IEC 61010-2-201 (SELV)
Standard designation
Equipping high voltage installations with electronic equipment
Standards/specifications
EN 50178/VDE 0160 (PELV)
Standard designation
Safety for equipment for measurement, control, and laboratory use
Standards/specifications
IEC 61010-1
Standard designation
Protective extra-low voltage
Standards/specifications
IEC 61010-1 (SELV) IEC 61010-2-201 (PELV)
Standard designation
Safe isolation
Standards/specifications
IEC 61558-2-16 IEC 61010-2-201
Standard designation
Limitation of harmonic line currents
Standards/specifications
EN 61000-3-2
Standard designation
Mains variation/undervoltage
Standards/specifications
SEMI F47 EN 61000-4-11
Identification
UL/C-UL Listed UL 61010-1
Identification
UL/C-UL Listed UL 61010-2-201
Identification
PROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS (EN)  This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only. (EN)  WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. (EN)  If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. (EN)  This equipement must be installed in a suitable, tool secured/key locked enclosure.
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Interference emission
Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise immunity
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Conducted noise emission
EN 55016 EN 61000-6-3 (Class B)
Noise emission
EN 55016 EN 61000-6-3 (Class B)
Standards/regulations
EN 61000-3-2 EN 61000-3-2 (Class A)
Frequency range
0 kHz ... 2 kHz
Standards/regulations
EN 61000-3-3 EN 61000-3-3
Frequency range
0 kHz ... 2 kHz
Standards/regulations
EN 61000-4-2
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
asymmetrical 2 kV (Test Level 3)
Output
asymmetrical 2 kV (Test Level 3)
Signal
asymmetrical 1 kV (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-5
Input
symmetrical 1 kV (Test Level 3) asymmetrical 2 kV (Test Level 3)
Output
symmetrical 0.5 kV (Test Level 2) asymmetrical 1 kV (Test Level 2)
Signal
asymmetrical 1 kV (Test Level 2)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-11
Voltage
230 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
25 periods
Additional text
Class 3
Comments
Criterion A
Voltage dip
40 %
Number of periods
10 periods
Additional text
Class 3
Comments
Criterion B
Voltage dip
0 %
Number of periods
1 period
Additional text
Class 3
Comments
Criterion A
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.