Product Model
TRIO-PS-2G/1AC/24DC/5/B+D

Selling Points
- 1Ensures regulated output voltage even in voltage fluctuations.
- 2Operates from -25°C to +70°C, with startup at -40°C.
- 3Electrically and mechanically robust, with high electric strength and vibration resistance.
- 4Simplifies installation with a push-in connection for DIN rail mounting.
- 5Allows connection in parallel for redundancy and increased capacity.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Network type | Star network | Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % | Derating | < 100 V AC (1 %/V) |
Input voltage range AC | 85 V AC ... 264 V AC | Switch-on voltage | > |
Electric strength, max. | ≤ 300 V AC 15 s | Typical national grid voltage | 120 V AC
230 V AC |
Voltage type of supply voltage | AC/DC | Inrush current | ≤ 16 A (typical) |
Inrush current integral (I | < 0.6 A | Inrush current limitation | typ. 16 A (after 1 ms) |
AC frequency range | 50 Hz ... 60 Hz ±5 Hz | Frequency range (f | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | typ. 20 ms (120 V AC)
typ. 100 ms (230 V AC) | Current consumption | 2.2 A (100 V AC)
1.9 A (120 V AC)
1.1 A (230 V AC)
1.1 A (240 V AC) |
Nominal power consumption | 272 VA | Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | 0.5 | Typical response time | < 1 s |
Input fuse | 6.3 A (internal (device protection)) | Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 0.25 mA | Nominal input voltage range | 110 V DC ... 250 V DC |
Input voltage range | 99 V DC ... 275 V DC | Derating | < 110 V DC (1 %/V) |
Switch-on voltage | ≥ 85 V DC | Shut-down voltage | < 60 V DC |
Voltage type of supply voltage | AC/DC | Mains buffering time | > 100 ms (230 V AC) |
Current consumption | 1.4 A (110 V DC)
0.6 A (250 V DC) | Efficiency | > 89 % (for 230 V AC and nominal values) |
Output characteristic | U/I with dynamic load reserve | Nominal output voltage | 24 V DC ±1 % |
Setting range of the output voltage (U | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) | Nominal output current (I | 5 A |
Dynamic Boost (I | 7.5 A (5 s) | Derating | > 60 °C ... 70 °C (2.5 %/K) |
Feedback voltage resistance | ≤ 35 V DC | Protection against overvoltage at the output (OVP) | ≤ 30 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %) | Residual ripple | < 50 mV |
Output power | 120 W
180 W | Maximum no-load power dissipation | < 1 W |
Power loss nominal load max. | < 16 W | Rise time | ≤ 12 ms (U |
Connection in parallel | yes, for redundancy and increased capacity | Connection in series | yes |
Maximum switching voltage | 30 V AC/DC | Continuous load current | 100 mA |
Connection method | Push-in connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 4 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 | Stripping length | 10 mm |
Connection method | Push-in connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 4 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 | Stripping length | 8 mm |
Connection method | Push-in connection | Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 1.5 mm² | Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 1.5 mm² | Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 16 | Stripping length | 8 mm |
Types of signaling | LED
Floating signal contact | Signalization designation | DC OK |
Status display | “DC OK” LED | Color | green |
Number of phases | 1.00 | Insulation voltage input/output | 3 kV AC (type test)
1.5 kV AC (routine test) |
Product type | Power supply | Product family | TRIO POWER |
MTBF (IEC 61709, SN 29500) | > 3380000 h (25 °C)
> 1970000 h (40 °C)
> 900000 h (60 °C) | Article revision | 02 |
Protection class | II (in closed control cabinet) | Degree of pollution | 2 |
Width | 35 mm | Height | 130 mm |
Depth | 115 mm | Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm | Mounting type | DIN rail mounting |
Assembly note | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm | Mounting position | horizontal DIN rail NS 35, EN 60715 |
With protective coating | no | Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing material | Plastic | Type of housing | Polycarbonate |
Hood version | Polycarbonate | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -25 °C | Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
Climatic class | 3K3 (in acc. with EN 60721) | Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) | Vibration (operation) | < 25 Hz, amplitude ±1.6 mm (according to DNV GL CG-0339)
15 Hz ... 150 Hz, 4g, 90 min. |
Rail applications | EN 50121-4 | Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 | Standard - Electrical safety | IEC 62368-1 (SELV) |
Standard – Safety extra-low voltage | IEC 62368-1 (SELV) und EN 60204-1 (PELV) | Standard - Safe isolation | DIN VDE 0100-410 |
Standard - Safety of transformers | EN 61558-2-16 (air clearances and creepage distances only) | Approval - requirement of the semiconductor industry with regard to mains voltage dips | Semi F47-0706 |
Shipbuilding approval | DNV GL (EMC B)
IEC 60945 | UL approvals | UL Listed UL 508
UL/C-UL Recognized UL 60950-1 |
SIL in accordance with IEC 61508 | 0 | Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC | EMC requirements for noise emission | EN 61000-6-3
EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1
EN 61000-6-2 | Noise emission | EN 55011 (EN 55022) |
Standards/regulations | EN 61000-4-2 | Contact discharge | 6 kV (Test Level 4) |
Discharge in air | 8 kV (Test Level 4) | Comments | Criterion A |
Standards/regulations | EN 61000-4-3 | Frequency range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) | Frequency range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m (Test Level 3) | Frequency range | 2 GHz ... 3 GHz |
Test field strength | 10 V/m (Test Level 3) | Comments | Criterion A |
Standards/regulations | EN 61000-4-4 | Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) | Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion A | Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical) | Output | 0.5 kV (Test Level 1 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) | Comments | Criterion B |
Standards/regulations | EN 61000-4-6 | Input/Output | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz | Comments | Criterion A |
Voltage | 10 V (Test Level 3) | Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential | Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criterion A | Normal operating behavior within the specified limits. | Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Specifications may be subject to change without notice