Phoenix Contact TRIO-PS-2G/3AC/24DC/10

Selling Points

  • 1Robust design for reliable operation in challenging ambient conditions.
  • 2Dynamic boost (1.5 x IN for 5 seconds) for secure starting and overload situations.
  • 3Tool-free push-in connection technology for fast and easy wiring.
  • 4Wide-range input voltage (3x 400 V AC to 500 V AC) for worldwide use.
  • 5High MTBF (over 2 million hours) for long-lasting performance.
Product Details
TRIO-PS-2G/3AC/24DC/10
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Network type
Star network
Nominal input voltage range
3x 400 V AC ... 500 V AC 2x 400 V AC ... 500 V AC
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +15 % 2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range AC
3x 320 V AC ... 575 V AC
Typical national grid voltage
3x 400 V AC 3x 480 V AC
Voltage type of supply voltage
AC
Inrush current
≤ 26 A (typical)
Inrush current integral (I
≤ 0.3 A
AC frequency range
50 Hz ... 60 Hz
Mains buffering time
typ. 10 ms (400 V AC) typ. 20 ms (500 V AC)
Current consumption
3x 0.6 A (400 V AC) 3x 0.6 A (500 V AC) 2x 1.1 A (400 V AC) 2x 1.1 A (500 V AC)
Nominal power consumption
451.7 VA
Protective circuit
Transient surge protection; Varistor
Power factor (cos phi)
0.58
Typical response time
< 1 s
Input fuse
3.15 A (internal (device protection), slow-blow)
Recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE
< 3.5 mA < (550 V AC, 60 Hz)
Efficiency
> 92 % (at 400 V AC and nominal values)
Output characteristic
U/I with dynamic load reserve
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (U
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I
10 A
Dynamic Boost (I
15 A (5 s)
Derating
> 60 °C ... 70 °C (2.5 %/K)
Protection against overvoltage at the output (OVP)
≤ 30 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ±10 %)
Residual ripple
≤ 20 mV
Short-circuit-proof
yes
No-load proof
yes
Output power
240 W 360 W
Maximum no-load power dissipation
< 1.1 W (400 V AC)
Power loss nominal load max.
< 22 W (480 V AC)
Rise time
≤ 120 ms (U
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Continuous load current
100 mA
Default
closed
Digital
30 V AC 30 V DC 100 mA
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
Types of signaling
LED Floating signal contact
Signalization designation
DC OK
Status display
LED
Color
green
DC OK
U
Number of phases
3.00
Insulation voltage input/output
3 kV AC (type test) 1.5 kV AC (routine test)
Product type
Power supply
Product family
TRIO POWER
MTBF (IEC 61709, SN 29500)
> 2100000 h (25 °C) > 1200000 h (40 °C) > 590000 h (60 °C)
Article revision
07
Protection class
I (in closed control cabinet)
Degree of pollution
2
Width
42 mm
Height
130 mm
Depth
160 mm
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Mounting type
DIN rail mounting
Assembly note
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
no
Flammability rating according to UL 94 (housing / terminal blocks)
V0
Housing material
Metal
Type of housing
Aluminum (AlMg3)
Hood version
Polycarbonate
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 4g, 90 min.
Rail applications
EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Electrical safety
IEC 62368-1 (SELV)
Standard – Safety extra-low voltage
IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safety of transformers
EN 61558-2-16 (air clearances and creepage distances only)
UL approvals
UL Listed UL 508 UL/C-UL Recognized UL 60950-1
SIL in accordance with IEC 61508
0
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission
EN 61000-6-3 EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1 EN 61000-6-2
Conducted noise emission
EN 55016 EN 61000-6-3 (Class B)
Noise emission
EN 55011 (EN 55022)
Standards/regulations
EN 61000-4-2
Contact discharge
6 kV (Test Level 4)
Discharge in air
8 kV (Test Level 4)
Comments
Criterion A
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
2 GHz ... 3 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
4 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 1 - symmetrical) 2 kV (Test Level 1 - asymmetrical)
Output
0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
Input/Output
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-6-3
Radio interference voltage in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice