Product Model

TRIO-UPS-2G/1AC/1AC/230V/750VA

In Stock
Last updated: 2025/4/17
Phoenix Contact TRIO-UPS-2G/1AC/1AC/230V/750VA

Selling Points

  • 1Space-saving design: UPS module and energy storage combined in one housing.
  • 2Smooth transition: Pure sine curve ensures seamless transition to battery operation.
  • 3Long buffer times: Integrated VRLA energy storage provides extended backup.
  • 4USB interface: Connect to higher-level controllers like industrial PCs safely.
  • 5Startup without mains: Possible startup from energy storage even without mains input.
Product Details
TRIO-UPS-2G/1AC/1AC/230V/750VA
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Note on the battery
This product contains a battery with a limited shelf life that must be charged every few months. The product packaging indicates when the battery must be started up or recharged. The general shelf life can be found in the energy storage devices area under “Latest startup”.
Input voltage
230 V AC
Input voltage range
184 V AC ... 264 V AC
Voltage type of supply voltage
AC
Frequency range (f
45 Hz ... 55 Hz 55 Hz ... 65 Hz
Current consumption
3 A (max.)
Power factor (cos phi)
0.8
Input fuse
10 A 400 V gRL
Permissible backup fuse
B6 B10 B16
Designation
Remote
Low signal
Connection to SGnd with < 2.7 kΩ
High signal
Open (> 35 kΩ between Remote and SGnd)
Battery-operated start 230 V AC low signal
Connection to SGnd with < 2.7 kΩ
Battery-operated start 230 V AC high signal
Open (> 200 kΩ between Bat.-Start and SGnd)
Classification according to IEC 62040-3
VFD-SS-311
Efficiency
> 95 % (100% load, with charged battery) ~ 81 % (100 % load )
Nominal output voltage
230 V AC
Form of output voltage
Pure sine
Nominal output current (I
3 A
Bridging time
60 s
UPS connection in parallel
no
UPS connection in series
no
Apparent power
750 VA
Nominal power
600 W (Real power)
Crest factor
2.8
Switch-over time
< 10 ms
Connection in parallel
no
Connection in series
no
Nominal output voltage
230 V AC
Nominal output current (I
3 A (750 VA)
Nominal output voltage
230 V AC
Nominal output current (I
3 A (750 VA)
Frequency (after automatic detection in mains operation)
50 Hz 60 Hz
Output voltage
24 V (SELV)
Continuous load current
≤ 20 mA
Output voltage
24 V (SELV)
Continuous load current
≤ 20 mA
Output voltage
24 V (SELV)
Continuous load current
≤ 20 mA
Signal ground SGnd
Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start
Nominal voltage U
24 V DC
Charging current
0.7 A ... 1.1 A
Nominal capacity
4 Ah
Nominal capacity range
4 Ah
Charging time
7 h
Buffer period
20 min (100 W) 4 min (300 W) 1 min (600 W)
Latest startup date (battery only)
6 Months (0 °C ... 20 °C)
Latest startup (battery only) - range
6 Months ... 3 Months (20 °C ... 30 °C) 3 Months ... 1 Months (30 °C ... 40 °C)
Battery technology
Lead rechargeable battery module
Memory medium
Lead rechargeable battery module
Accumulator type
2x Panasonic UP-VW1220P1 / BB Battery HR4.2-12FR
Can be extended with external battery
1x 24 V 4 Ah
Battery fuse
40 A, 32 V
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
Connection method
Push-in connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
Interface
MINI-USB type B
Maximum cable length
3 m
Types of signaling
LED
Signalization designation
Alarm
Status display
LED
Color
red
Signalization designation
Battery mode
Status display
LED
Color
yellow
Signalization designation
Ready
Status display
LED
Color
green
Signalization designation
Battery charge
Status display
LED
Color
yellow
Signalization designation
Service
Status display
LED
Color
red
Number of phases
1.00
Product type
AC UPS
Product family
TRIO AC UPS – UPS with integrated battery
MTBF (IEC 61709, SN 29500)
> 206000 h (40 °C)
Article revision
06
Protection class
I
Overvoltage category
III
Degree of pollution
2
Time
32000 h
Width
210 mm
Height
170 mm
Depth
136 mm
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Mounting type
DIN rail mounting
Type of housing
DX51D+AZ (steel sheet / Galvalume)
Hood version
PC + ABS
Degree of protection
IP20
Ambient temperature (operation)
0 °C ... 40 °C
Ambient temperature (storage/transport)
-15 °C ... 40 °C (with charged energy storage device)
Maximum altitude
≤ 3000 m (> 2000 m, observe derating)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (25 °C, non-condensing)
Shock
20g in all directions (EN 60068-2-27) 30g in each space direction with UWA 130
Vibration (operation)
5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)
Standard uninterruptible power supply systems
EN 62040-1
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Interference emission
Noise emission in accordance with EN 62040-2
Noise immunity
Immunity in accordance with EN 62040-2
Conducted noise emission
EN 62040-02 (Class C2)
Standards/regulations
EN 61000-4-2
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 3 GHz
Test field strength
10 V/m
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical) 2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 3 - asymmetrical) 2 kV (Test Level 3 - asymmetrical)
Comments
Criterion A (B for USB)
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Output
1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V
Standards/regulations
EN 61000-4-8
Frequency
50 Hz
Test field strength
100 A/m
Comments
Criterion A
Emitted radio interference in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.

Specifications may be subject to change without notice