Phoenix Contact UK 10,3-HESI 1000V

Selling Points

  • 1Up to 1000 V DC for reliable electrical insulation.
  • 2Midget fuse type with a 10.3 x 38 mm footprint for compact installations.
  • 3Suitable for cross-sections from 1.5 to 25 mm² and AWG 16 to 4.
  • 4Meets UL 94 V0 inflammability class and DIN EN 50274 shock protection standards.
  • 5Black color with PA insulating material and M5 screw thread for straightforward connections.
Product Details
UK 10,3-HESI 1000V
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Fuse terminal block
Number of connections
2
Number of rows
1
Article revision
02
Overvoltage category
II
Degree of pollution
3
Fuse type
Glass / ceramics / ...
Rated surge voltage
6 kV
Maximum power dissipation for nominal condition
4 W
Fuse
gPV 10.3 x 38 mm in accordance with 60269-6
Number of connections per level
2
Nominal cross section
25 mm²
Rated cross section AWG
3
Screw thread
M5
Tightening torque
2 ... 2.5 Nm
Stripping length
11 mm
Internal cylindrical gage
A7
Connection in acc. with standard
IEC 60269-1 / -2
Conductor cross section rigid
1.5 mm² ... 25 mm²
Cross section AWG
14 ... 4 (converted acc. to IEC)
Conductor cross section flexible
0.75 mm² ... 25 mm²
Conductor cross section, flexible [AWG]
18 ... 4 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
1.5 mm² ... 16 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
1.5 mm² ... 16 mm²
Cross-section with insertion bridge, rigid
10 mm²
Cross-section with insertion bridge, flexible
10 mm²
2 conductors with same cross section, solid
1.5 mm² ... 4 mm²
2 conductors with same cross section, flexible
0.75 mm² ... 10 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
1.5 mm² ... 4 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
1.5 mm² ... 10 mm²
Nominal current
30 A (the current and voltage are determined by the fuse)
Maximum load current
30 A (the current and voltage are determined by the fuse)
Nominal voltage
1000 V DC (the current and voltage are determined by the fuse)
Nominal cross section
16 mm²
Width
18 mm
Height
81 mm
Depth on NS 35/7,5
65.5 mm
Depth on NS 35/15
73 mm
Color
black (RAL 9005)
Flammability rating according to UL 94
V2
Insulating material group
IIIa
Relative insulation material temperature index (Elec., UL 746 B)
125 °C
Open side panel
No
Ambient temperature (operation)
-60 °C ... 85 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 55 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC 60269-1 / -2
Mounting type
NS 35/7,5 NS 35/15

Specifications may be subject to change without notice