Phoenix Contact UK 16 N GN

Selling Points

  • 1ATEX Certification: Meets IEC/EN 60079 standards for hazardous areas.
  • 2Screw Termination: Easy and secure connection method.
  • 3High Current Rating: Supports up to 101 A with 25 mm² conductor cross section.
  • 4Durable Construction: Made from high-quality polyamide for long-lasting performance.
  • 5Comprehensive Specifications: Includes detailed technical data for precise application needs.
Product Details
UK 16 N GN
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Feed-through terminal block
Number of connections
2
Number of rows
1
Potentials
1
Article revision
03
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
8 kV
Maximum power dissipation for nominal condition
2.43 W
Number of connections per level
2
Nominal cross section
16 mm²
Screw thread
M4
Tightening torque
1.5 ... 1.8 Nm
Stripping length
11 mm
Internal cylindrical gage
B7
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section rigid
2.5 mm² ... 25 mm²
Cross section AWG
12 ... 4 (converted acc. to IEC)
Conductor cross section flexible
4 mm² ... 16 mm²
Conductor cross section, flexible [AWG]
10 ... 6 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
1.5 mm² ... 16 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
1.5 mm² ... 16 mm²
Cross-section with insertion bridge, rigid
16 mm²
Cross-section with insertion bridge, flexible
16 mm²
2 conductors with same cross section, solid
1.5 mm² ... 6 mm²
2 conductors with same cross section, flexible
1.5 mm² ... 4 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
1.5 mm² ... 6 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.75 mm² ... 10 mm²
Nominal current
76 A
Maximum load current
101 A (with 25 mm² conductor cross section)
Nominal voltage
800 V
Nominal cross section
16 mm²
Identification
 II 2 GD  Ex eb IIC Gb
Operating temperature range
-60 °C ... 110 °C
Ex-certified accessories
3006027 D-UK 16 1205066 SZS 1,0X4,0 VDE 1201442 E/UK
List of bridges
Fixed bridge / FBI 2-12 / 0200075 Fixed bridge / FBI 10-12 / 0203454
Bridge data
66 A / 16 mm²
Ex temperature increase
40 K (75.1 A / 16 mm²)
Rated voltage
690 V
for bridging with bridge
690 V
Rated insulation voltage
630 V
output
(Permanent)
Rated current
68 A
Maximum load current
91 A
Contact resistance
0.17 mΩ
Torque range
1.5 Nm ... 1.8 Nm
Nominal cross section
16 mm²
Rated cross section AWG
6
Connection capacity rigid
2.5 mm² ... 25 mm²
Connection capacity AWG
14 ... 4
Connection capacity flexible
4 mm² ... 16 mm²
Connection capacity AWG
12 ... 6
2 conductors with same cross section, solid
1.5 mm² ... 6 mm²
2 conductors with the same cross-section AWG rigid
16 ... 10
2 conductors with same cross section, stranded
1.5 mm² ... 4 mm²
2 conductors with the same cross-section AWG flexible
16 ... 12
Width
12.2 mm
End cover width
1.5 mm
Height
42.5 mm
Depth on NS 32
59 mm
Depth on NS 35/7,5
54 mm
Depth on NS 35/15
61.5 mm
Color
green (RAL 6021)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Open side panel
Yes
Ambient temperature (operation)
-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC 60947-7-1
Mounting type
NS 35/7,5 NS 35/15 NS 32

Specifications may be subject to change without notice