Product Model

UKH 240-3L-F

In Stock
Last updated: 2025/4/19
Phoenix Contact UKH 240-3L-F

Selling Points

  • 1Robust Surge Protection: Rated surge voltage of 8 kV ensures reliable operation in high-voltage environments.
  • 2Efficient Cable Connection: Three-point centering of the conductor in the prismatic sleeve base ensures a secure and low-resistance connection.
  • 3Durable Design: Made from PA insulating material with a flammability rating of UL 94 V0 for enhanced safety and durability.
  • 4Versatile Connectivity: Supports cross sections from 70 mm² to 240 mm², accommodating various conductor sizes including AWG 2/0 to 500 kcmil.
  • 5Easy Installation: Direct screw connection with spring-loaded elements for quick and secure mounting.
Product Details
UKH 240-3L-F
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
High current terminal block
Number of positions
3
Number of connections
6
Number of rows
1
Potentials
3
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
8 kV
Number of connections per level
6
Nominal cross section
240 mm²
Screw thread
M10
Note
Screws with hexagonal socket
Tightening torque
25 ... 30 Nm
Stripping length
40 mm
Internal cylindrical gage
B15
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section rigid
70 mm² ... 240 mm²
Cross section AWG
2/0 ... 500 kcmil (converted acc. to IEC)
Conductor cross section flexible
70 mm² ... 240 mm²
Conductor cross section, flexible [AWG]
2/0 ... 500 kcmil (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
70 mm² ... 185 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
70 mm² ... 185 mm²
Cross-section with insertion bridge, rigid
240 mm²
Cross-section with insertion bridge, flexible
185 mm²
2 conductors with same cross section, solid
35 mm² ... 95 mm²
2 conductors with same cross section, flexible
50 mm² ... 95 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
35 mm² ... 50 mm²
Nominal current
415 A
Maximum load current
415 A (with 240 mm² conductor cross section)
Nominal voltage
1000 V
Note
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Nominal cross section
240 mm²
Width
108 mm
Height
124 mm
Color
gray
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)
28 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Result
Test passed
Short-time withstand current 240 mm²
28.8 kA
Result
Test passed
Test voltage setpoint
2.2 kV
Result
Test passed
Open side panel
No
Result
Test passed
DIN rail/fixing support
NS 32/NS 35
Result
Test passed
Time of exposure
30 s
Result
Test passed
Connection in acc. with standard
IEC 60947-7-1
Mounting type
direct screw connection

Specifications may be subject to change without notice