Phoenix Contact UKH  95-FE-F

Selling Points

  • 1Reliable cable connection ensured by three-point centering of the conductor in the prismatic sleeve base.
  • 2Screw locking by means of spring-loaded elements in the clamping part for secure connections.
  • 3Low contact resistance due to ribbing on the contact surface for efficient power transfer.
  • 4Insulating material group I with a maximum power dissipation of 7.54 W and a rated surge voltage of 8 kV.
  • 5Compliant with IEC 60947-7-1 standards and suitable for direct screw mounting with M8 screws.
Product Details
UKH 95-FE-F
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
High current terminal block
Number of connections
2
Number of rows
1
Potentials
1
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
8 kV
Maximum power dissipation for nominal condition
7.54 W
Number of connections per level
2
Nominal cross section
95 mm²
Screw thread
M8
Note
Screws with hexagonal socket
Tightening torque
15 ... 20 Nm
Stripping length
33 mm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section rigid
25 mm² ... 95 mm²
Cross section AWG
4 ... 3/0 (converted acc. to IEC)
Conductor cross section flexible
35 mm² ... 95 mm²
Conductor cross section, flexible [AWG]
2 ... 3/0 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
35 mm² ... 95 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
35 mm² ... 95 mm²
Cross-section with insertion bridge, rigid
95 mm²
Cross-section with insertion bridge, flexible
70 mm²
2 conductors with same cross section, solid
25 mm² ... 35 mm²
2 conductors with same cross section, flexible
25 mm² ... 35 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
16 mm² ... 35 mm²
Nominal current
232 A
Maximum load current
232 A
Nominal voltage
1000 V
Note
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Nominal cross section
95 mm²
Width
25 mm
Height
90 mm
Color
black/yellow
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Result
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Result
Test passed
Short-time withstand current 95 mm²
11.4 kA
Result
Test passed
Test voltage setpoint
2.2 kV
Result
Test passed
Terminal block mounting
15 Nm ... 20 Nm (PE foot with mounting screw, M8)
Open side panel
No
Result
Test passed
DIN rail/fixing support
NS 32/NS 35
Result
Test passed
Rotation speed
10 (+/- 2) rpm
Revolutions
135
Conductor cross section/weight
25 mm² / 4.5 kg 35 mm² / 6.8 kg 95 mm²/14 kg
Result
Test passed
Time of exposure
30 s
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2022-06
Spectrum
Service life test category 2, bogie-mounted
Frequency
f
ASD level
6.12 (m/s²)²/Hz
Acceleration
3.12g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2022-06
Pulse shape
Half-sine
Acceleration
5g
Shock duration
30 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Result
Test passed
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC 60947-7-1
Mounting type
direct screw connection
Terminal block mounting
15 Nm ... 20 Nm (PE foot with mounting screw, M8)

Specifications may be subject to change without notice