Product Model
UKH 95-FE-F

Selling Points
- 1Reliable cable connection ensured by three-point centering of the conductor in the prismatic sleeve base.
- 2Screw locking by means of spring-loaded elements in the clamping part for secure connections.
- 3Low contact resistance due to ribbing on the contact surface for efficient power transfer.
- 4Insulating material group I with a maximum power dissipation of 7.54 W and a rated surge voltage of 8 kV.
- 5Compliant with IEC 60947-7-1 standards and suitable for direct screw mounting with M8 screws.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | High current terminal block | Number of connections | 2 |
Number of rows | 1 | Potentials | 1 |
Overvoltage category | III | Degree of pollution | 3 |
Rated surge voltage | 8 kV | Maximum power dissipation for nominal condition | 7.54 W |
Number of connections per level | 2 | Nominal cross section | 95 mm² |
Screw thread | M8 | Note | Screws with hexagonal socket |
Tightening torque | 15 ... 20 Nm | Stripping length | 33 mm |
Connection in acc. with standard | IEC 60947-7-1 | Conductor cross section rigid | 25 mm² ... 95 mm² |
Cross section AWG | 4 ... 3/0 (converted acc. to IEC) | Conductor cross section flexible | 35 mm² ... 95 mm² |
Conductor cross section, flexible [AWG] | 2 ... 3/0 (converted acc. to IEC) | Conductor cross-section flexible (ferrule without plastic sleeve) | 35 mm² ... 95 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 35 mm² ... 95 mm² | Cross-section with insertion bridge, rigid | 95 mm² |
Cross-section with insertion bridge, flexible | 70 mm² | 2 conductors with same cross section, solid | 25 mm² ... 35 mm² |
2 conductors with same cross section, flexible | 25 mm² ... 35 mm² | 2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 16 mm² ... 35 mm² |
Nominal current | 232 A | Maximum load current | 232 A |
Nominal voltage | 1000 V | Note | Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area. |
Nominal cross section | 95 mm² | Width | 25 mm |
Height | 90 mm | Color | black/yellow |
Flammability rating according to UL 94 | V0 | Insulating material group | I |
Insulating material | PA | Result | Test passed |
Requirement temperature-rise test | Increase in temperature ≤ 45 K | Result | Test passed |
Short-time withstand current 95 mm² | 11.4 kA | Result | Test passed |
Test voltage setpoint | 2.2 kV | Result | Test passed |
Terminal block mounting | 15 Nm ... 20 Nm (PE foot with mounting screw, M8) | Open side panel | No |
Result | Test passed | DIN rail/fixing support | NS 32/NS 35 |
Result | Test passed | Rotation speed | 10 (+/- 2) rpm |
Revolutions | 135 | Conductor cross section/weight | 25 mm² / 4.5 kg
35 mm² / 6.8 kg
95 mm²/14 kg |
Result | Test passed | Time of exposure | 30 s |
Result | Test passed | Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
Spectrum | Service life test category 2, bogie-mounted | Frequency | f |
ASD level | 6.12 (m/s²)²/Hz | Acceleration | 3.12g |
Test duration per axis | 5 h | Test directions | X-, Y- and Z-axis |
Result | Test passed | Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
Pulse shape | Half-sine | Acceleration | 5g |
Shock duration | 30 ms | Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) | Result | Test passed |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) | Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C | Permissible humidity (storage/transport) | 30 % ... 70 % |
Connection in acc. with standard | IEC 60947-7-1 | Mounting type | direct screw connection |
Terminal block mounting | 15 Nm ... 20 Nm (PE foot with mounting screw, M8) |
Specifications may be subject to change without notice