Product Model

UMK- 8 OM-R/MF/MKDS

In Stock
Last updated: 2025/4/25
Phoenix Contact UMK- 8 OM-R/MF/MKDS

Selling Points

  • 1Status Indicator: Features a yellow LED for channel status display.
  • 2Integrated Fuse: Provides line protection with an integrated fuse.
  • 3Solid-State Relay Compatibility: Can be fitted with solid-state relays or I/O modules.
  • 4Secure Connection: Includes a security latch and screw connection for secure mounting.
  • 5Technical Specifications: Compatible with digital I/O modules, input voltage range 4 V to 32 V, and limiting continuous current 4 A.
Product Details
UMK- 8 OM-R/MF/MKDS
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Multi-channel solid-state relay module
No. of channels
8
Compatible components
Digital I/O modules
With components
no
Input voltage range
4 V ... 32 V
Typical input current at U
30 mA (Optocoupler dependent)
Status display/channel
Yellow LED
Compatible components
Digital I/O modules
Limiting continuous current
4 A (Optocoupler dependent)
Error detection (line break / short-circuit)
no
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Number of connections
2
Number of positions
12
Conductor cross section rigid
0.2 mm² ... 4 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Number of connections
16
Number of positions
3
Conductor cross section rigid
0.2 mm² ... 6 mm²
Conductor cross section flexible
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 10
Status display present
Yes
Width
180 mm
Height
77 mm
Depth
72 mm
Color
green (RAL 6021)
Housing insulation material
PVC, side panel PA non-reinforced,
Ambient temperature (operation)
-20 °C ... 55 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Standards/regulations
DIN VDE 0110b, Gr. C for 250 V DC DIN VDE 0160 (in relevant parts)
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice