Product Model

UT 2,5-MTD P/P BU

In Stock
Last updated: 2025/4/20
Phoenix Contact UT 2,5-MTD P/P BU

Selling Points

  • 1High voltage rating of 400V for robust electrical connections.
  • 2Reliable screw termination method for secure connections.
  • 3Single-level design for straightforward installation and use.
  • 4Blue color coding for easy identification in electrical systems.
  • 5Manufactured in Germany with high-quality standards.
Product Details
UT 2,5-MTD P/P BU
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Feed-through terminal block
Number of connections
2
Number of rows
1
Potentials
1
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
8 kV
Number of connections per level
2
Nominal cross section
2.5 mm²
Rated cross section AWG
12
Screw thread
M3
Tightening torque
0.5 ... 0.6 Nm
Stripping length
9 mm
Internal cylindrical gage
A3
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section rigid
0.14 mm² ... 4 mm²
Cross section AWG
26 ... 12 (converted acc. to IEC)
Conductor cross section flexible
0.14 mm² ... 4 mm²
Conductor cross section, flexible [AWG]
26 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
0.14 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
0.14 mm² ... 2.5 mm²
2 conductors with same cross section, solid
0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible
0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.14 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.5 mm² ... 1.5 mm²
Nominal current
24 A
Maximum load current
32 A (with 4 mm² conductor cross section)
Nominal voltage
630 V
Nominal cross section
2.5 mm²
Width
5.2 mm
End cover width
2.2 mm
Color
blue
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)
27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Result
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Result
Test passed
Short-time withstand current 2.5 mm²
0.3 kA
Short-time withstand current 4 mm²
0.48 kA
Result
Test passed
Test voltage setpoint
1.89 kV
Result
Test passed
Open side panel
Yes
Result
Test passed
DIN rail/fixing support
NS 32/NS 35
Result
Test passed
Rotation speed
10 (+/- 2) rpm
Revolutions
135
Conductor cross section/weight
0.14 mm² / 0.2 kg 2.5 mm² / 0.7 kg 4 mm² / 0.9 kg
Result
Test passed
Time of exposure
30 s
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2018-05
Spectrum
Service life test category 2, bogie-mounted
Frequency
f
ASD level
6.12 (m/s²)²/Hz
Acceleration
3.12g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Pulse shape
Half-sine
Acceleration
30g
Shock duration
18 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Connection in acc. with standard
IEC 60947-7-1
Mounting type
NS 35/7,5 NS 35/15

Specifications may be subject to change without notice