Phoenix Contact UT 2,5-MTS-EX

Selling Points

  • 1Compact design with high current-carrying capacity of 20A.
  • 2Single-level, screw termination for easy cable wiring.
  • 3Suitable for energy sector and industrial building management.
  • 4Double bridge shaft enables individual potential distribution and supply.
  • 5Rated for 400V and 2.5mm² cable CSA, with a maximum operating temperature of +120°C.
Product Details
UT 2,5-MTS-EX
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Disconnect terminal block
Area of application
Process industry Machine building Plant engineering
Number of connections
2
Number of rows
1
Article revision
03
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
6 kV
Maximum power dissipation for nominal condition
0.77 W
Number of connections per level
2
Nominal cross section
2.5 mm²
Screw thread
M3
Stripping length
10 mm
Internal cylindrical gage
A3
Nominal cross section
2.5 mm²
Identification
 II 3 G  Ex ec llC Gc
Operating temperature range
-50 °C ... 125 °C
Operating cycles of the disconnect knife
100
Ex-certified accessories
3047141 D-UT 2,5/4-TWIN 1205053 SZS 0,6X3,5 3022276 CLIPFIX 35-5 3022218 CLIPFIX 35
List of bridges
Plug-in bridge / FBS 2-5 / 3030161 Plug-in bridge / FBS 3-5 / 3030174 Plug-in bridge / FBS 4-5 / 3030187 Plug-in bridge / FBS 5-5 / 3030190 Plug-in bridge / FBS 10-5 / 3030213 Plug-in bridge / FBS 20-5 / 3030226
Bridge data
17.5 A / 2.5 mm²
Rated voltage
440 V
output
(Permanent)
Rated current
18.5 A (2.5 mm²)
Maximum load current
21.5 A (4 mm²)
Contact resistance
0.27 mΩ
Torque range
0.5 Nm ... 0.6 Nm
Nominal cross section
2.5 mm²
Rated cross section AWG
14
Connection capacity rigid
0.14 mm² ... 4 mm²
Connection capacity AWG
26 ... 12
Connection capacity flexible
0.14 mm² ... 4 mm²
Connection capacity AWG
26 ... 12
2 conductors with same cross section, solid
0.14 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG rigid
26 ... 16
2 conductors with same cross section, stranded
0.14 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG flexible
26 ... 16
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
2.5 mm²
Single conductor/terminal point, flexible, with ferrule, without plastic sleeve, AWG
26 ... 14
Width
5.2 mm
Height
56.8 mm
Depth on NS 35/7,5
47.5 mm
Depth on NS 35/15
55 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Open side panel
Yes
Ambient temperature (operation)
-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Mounting type
NS 35/7,5 NS 35/15

Specifications may be subject to change without notice