Phoenix Contact UT 4/ 1P-H

Selling Points

  • 1High Current Capacity: Handles up to 41A with a 6mm² conductor cross-section.
  • 2Reliable Voltage Rating: Operates at 1000V, ensuring safe and efficient power transmission.
  • 3Durable Construction: Built with robust materials and designed to withstand harsh industrial conditions.
  • 4Easy Installation: Features screw-type terminals for quick and secure connections.
  • 5Comprehensive Testing: Meets stringent standards including overvoltage category III and temperature-rise tests.
Product Details
UT 4/ 1P-H
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Note
With a free-hanging connection, an insulating foil has to be placed between the plug connection and electrically conductive surfaces.
Product type
Plug-in terminal block
Product family
UT
Number of connections
2
Number of rows
1
Potentials
1
Article revision
03
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
8 kV
Maximum power dissipation for nominal condition
1.02 W
Nominal cross section
4 mm²
Screw thread
M3
Tightening torque
0.6 ... 0.8 Nm
Stripping length
9 mm
Internal cylindrical gage
A4
Connection in acc. with standard
IEC 61984
Conductor cross section rigid
0.14 mm² ... 6 mm²
Cross section AWG
26 ... 14 (converted acc. to IEC)
Conductor cross section flexible
0.14 mm² ... 6 mm²
Conductor cross section, flexible [AWG]
26 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
0.14 mm² ... 4 mm²
2 conductors with same cross section, solid
0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible
0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.14 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.5 mm² ... 2.5 mm²
Nominal current
32 A
Maximum load current
32 A (with 6 mm² conductor cross section)
Nominal voltage
800 V
Nominal cross section
4 mm²
Width
6.2 mm
End cover width
2.2 mm
Height
49.8 mm
Depth on NS 35/7,5
47.5 mm
Depth on NS 35/15
55 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Test voltage setpoint
9.8 kV
Result
Test passed
Short-time withstand current 4 mm²
0.48 kA
Result
Test passed
Test voltage setpoint
2 kV
Result
Test passed
Open side panel
Yes
Result
Test passed
Time of exposure
30 s
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2022-06
Spectrum
Service life test category 1, class B, body mounted
Frequency
f
ASD level
0.964 (m/s²)²/Hz
Acceleration
0.58g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2022-06
Pulse shape
Half-sine
Acceleration
5g
Shock duration
30 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Result
Test passed
Ambient temperature (operation)
-60 °C ... 110 °C (max. operating temperature see derating curve)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC 61984
Mounting type
NS 35/7,5 NS 35/15

Specifications may be subject to change without notice