Phoenix Contact UT 4-PE/MT P/P

Selling Points

  • 1High-Voltage Capability: Handles up to 500V for reliable high-voltage connections.
  • 2Durable Construction: Made with PA insulating material, ensuring long-lasting performance.
  • 3Flexible Conductor Capacity: Supports conductors from 0.14mm² to 6mm², accommodating various wire sizes.
  • 4Compact Design: Measures 6.2mm in width and 70.8mm in length, ideal for space-efficient installations.
  • 5Compliance with Standards: Meets IEC 60947-7-1/IEC 60947-7-2 standards and UL 94 flammability rating V0.
Product Details
UT 4-PE/MT P/P
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Ground terminal block
Number of connections
2
Number of rows
1
Article revision
09
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
6 kV
Maximum power dissipation for nominal condition
1.02 W
Grounding foot
Yes
Number of connections per level
2
Nominal cross section
4 mm²
Screw thread
M3
Note
Please observe the current carrying capacity of the DIN rails.
Tightening torque
0.6 ... 0.8 Nm
Stripping length
9 mm
Internal cylindrical gage
A4
Connection in acc. with standard
IEC 60947-7-1/IEC 60947-7-2
Conductor cross section rigid
0.14 mm² ... 6 mm²
Cross section AWG
26 ... 10 (converted acc. to IEC)
Conductor cross section flexible
0.14 mm² ... 6 mm²
Conductor cross section, flexible [AWG]
26 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
0.14 mm² ... 4 mm²
Nominal current
20 A
Maximum load current
20 A (with 6 mm² conductor cross section)
Nominal voltage
500 V
Nominal cross section
2.5 mm²
Width
6.2 mm
Height
70.8 mm
Depth on NS 35/7,5
49.1 mm
Depth on NS 35/15
56.6 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Test voltage setpoint
9.8 kV
Result
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Result
Test passed
Short-time withstand current 4 mm²
0.48 kA
Short-time withstand current 6 mm²
0.72 kA
Result
Test passed
Test voltage setpoint
1.89 kV
Result
Test passed
Open side panel
No
Result
Test passed
DIN rail/fixing support
NS 35
Test force setpoint
1 N
Result
Test passed
Rotation speed
10 rpm
Revolutions
135
Conductor cross section/weight
0.2 mm² / 0.2 kg 4 mm² / 0.9 kg 6 mm² / 1.4 kg
Result
Test passed
Time of exposure
30 s
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2018-05
Spectrum
Service life test category 2, bogie-mounted
Frequency
f
ASD level
6.12 (m/s²)²/Hz
Acceleration
3.12g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Pulse shape
Half-sine
Acceleration
30g
Shock duration
18 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Ambient temperature (operation)
-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC 60947-7-1/IEC 60947-7-2
Mounting type
NS 35/7,5 NS 35/15

Specifications may be subject to change without notice