Selling Points
- 1High-Voltage Capability: Handles up to 500V for reliable high-voltage connections.
- 2Durable Construction: Made with PA insulating material, ensuring long-lasting performance.
- 3Flexible Conductor Capacity: Supports conductors from 0.14mm² to 6mm², accommodating various wire sizes.
- 4Compact Design: Measures 6.2mm in width and 70.8mm in length, ideal for space-efficient installations.
- 5Compliance with Standards: Meets IEC 60947-7-1/IEC 60947-7-2 standards and UL 94 flammability rating V0.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Ground terminal block | Number of connections | 2 |
Number of rows | 1 | Article revision | 09 |
Overvoltage category | III | Degree of pollution | 3 |
Rated surge voltage | 6 kV | Maximum power dissipation for nominal condition | 1.02 W |
Grounding foot | Yes | Number of connections per level | 2 |
Nominal cross section | 4 mm² | Screw thread | M3 |
Note | Please observe the current carrying capacity of the DIN rails. | Tightening torque | 0.6 ... 0.8 Nm |
Stripping length | 9 mm | Internal cylindrical gage | A4 |
Connection in acc. with standard | IEC 60947-7-1/IEC 60947-7-2 | Conductor cross section rigid | 0.14 mm² ... 6 mm² |
Cross section AWG | 26 ... 10 (converted acc. to IEC) | Conductor cross section flexible | 0.14 mm² ... 6 mm² |
Conductor cross section, flexible [AWG] | 26 ... 10 (converted acc. to IEC) | Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 4 mm² | Nominal current | 20 A |
Maximum load current | 20 A (with 6 mm² conductor cross section) | Nominal voltage | 500 V |
Nominal cross section | 2.5 mm² | Width | 6.2 mm |
Height | 70.8 mm | Depth on NS 35/7,5 | 49.1 mm |
Depth on NS 35/15 | 56.6 mm | Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 | Insulating material group | I |
Insulating material | PA | Static insulating material application in cold | -60 °C |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C | Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 | Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 | Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed | Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Test voltage setpoint | 9.8 kV | Result | Test passed |
Requirement temperature-rise test | Increase in temperature ≤ 45 K | Result | Test passed |
Short-time withstand current 4 mm² | 0.48 kA | Short-time withstand current 6 mm² | 0.72 kA |
Result | Test passed | Test voltage setpoint | 1.89 kV |
Result | Test passed | Open side panel | No |
Result | Test passed | DIN rail/fixing support | NS 35 |
Test force setpoint | 1 N | Result | Test passed |
Rotation speed | 10 rpm | Revolutions | 135 |
Conductor cross section/weight | 0.2 mm² / 0.2 kg
4 mm² / 0.9 kg
6 mm² / 1.4 kg | Result | Test passed |
Time of exposure | 30 s | Result | Test passed |
Specification | DIN EN 50155 (VDE 0115-200):2018-05 | Spectrum | Service life test category 2, bogie-mounted |
Frequency | f | ASD level | 6.12 (m/s²)²/Hz |
Acceleration | 3.12g | Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis | Pulse shape | Half-sine |
Acceleration | 30g | Shock duration | 18 ms |
Number of shocks per direction | 3 | Test directions | X-, Y- and Z-axis (pos. and neg.) |
Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) | Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C ... 70 °C | Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (operation) | 20 % ... 90 % | Permissible humidity (storage/transport) | 30 % ... 70 % |
Connection in acc. with standard | IEC 60947-7-1/IEC 60947-7-2 | Mounting type | NS 35/7,5
NS 35/15 |
Specifications may be subject to change without notice