Phoenix Contact UT 4-TG-EX

Selling Points

  • 1High current carrying capacity of 20 A
  • 2Compact design for efficient use in mechanical and plant engineering
  • 3Ex nA approval for process technology applications
  • 4Double bridge shaft for individual potential distribution and supply
  • 5Suitable for various conductor cross sections (0.14 mm² - 6 mm²)
Product Details
UT 4-TG-EX
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
General
Current and voltage are determined by the plug used.
Product type
Disconnect terminal block
Area of application
Machine building Plant engineering
Number of connections
2
Number of rows
1
Potentials
1
Article revision
08
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
6 kV
Maximum power dissipation for nominal condition
1.02 W
Number of connections per level
2
Nominal cross section
4 mm²
Screw thread
M3
Tightening torque
0.6 ... 0.8 Nm
Stripping length
9 mm
Internal cylindrical gage
A4
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section rigid
0.14 mm² ... 6 mm²
Cross section AWG
26 ... 10 (converted acc. to IEC)
Conductor cross section flexible
0.14 mm² ... 6 mm²
Conductor cross section, flexible [AWG]
26 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
0.14 mm² ... 4 mm²
2 conductors with same cross section, solid
0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible
0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.14 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.5 mm² ... 2.5 mm²
Nominal current
20 A
Maximum load current
20 A (with 6 mm² conductor cross section) 20 A (with 6 mm² conductor cross section)
Nominal voltage
500 V
Nominal cross section
4 mm²
Identification
 II 3 G  Ex ec llC Gc
Operating temperature range
-50 °C ... 130 °C
Ex-certified accessories
3047183 ATP-UT-TWIN 3036807 P-FU 5X20-EX 3036821 P-FU 5X20 LED 24-EX 3036823 P-FU 5X20 LED 60-EX 3036836 P-FU 5X20 LA 250-EX 3022276 CLIPFIX 35-5 3022218 CLIPFIX 35 1205053 SZS 0,6X3,5
List of bridges
Plug-in bridge / FBS 2-6 / 3030336 Plug-in bridge / FBS 3-6 / 3030242 Plug-in bridge / FBS 4-6 / 3030255 Plug-in bridge / FBS 5-6 / 3030349 Plug-in bridge / FBS 10-6 / 3030271 Plug-in bridge / FBS 20-6 / 3030365
Bridge data
6.3 A / 4 mm²
Rated voltage
250 V
output
(Permanent)
Rated current
6.3 A
Maximum load current
6.3 A
Torque range
0.6 Nm ... 0.8 Nm
Nominal cross section
4 mm²
Rated cross section AWG
12
Connection capacity rigid
0.14 mm² ... 6 mm²
Connection capacity AWG
26 ... 10
Connection capacity flexible
0.14 mm² ... 6 mm²
Connection capacity AWG
26 ... 12
2 conductors with same cross section, solid
0.14 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG rigid
26 ... 16
2 conductors with same cross section, stranded
0.14 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG flexible
26 ... 16
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4 mm²
Single conductor/terminal point, flexible, with ferrule, without plastic sleeve, AWG
26 ... 12
Width
6.2 mm
Height
57.8 mm
Depth on NS 35/7,5
47.5 mm
Depth on NS 35/15
55 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Open side panel
No
Ambient temperature (operation)
-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC 60947-7-1
Mounting type
NS 35/7,5 NS 35/15

Specifications may be subject to change without notice