Phoenix Contact UTI 2,5-PE/L/NT

Selling Points

  • 1High-quality construction with thermoplastic insulation.
  • 224A max rating for reliable electrical connections.
  • 34 connections for versatile wiring configurations.
  • 45.2mm width for compact installations.
  • 5Gray color with protective earth function (PE).
Product Details
UTI 2,5-PE/L/NT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
General
For secure fastening of the neutral busbar, supports must be set at the beginning and end of each terminal strip as well as every 20 cm on longer terminal strips.
Product type
Ground terminal block
Number of positions
1
Number of connections
5
Number of rows
3
Potentials
2
Article revision
05
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
4 kV 6 kV
Maximum power dissipation for nominal condition
1.02 W
Current carrying capacity of the neutral busbar
140 A
Grounding foot
Yes
Number of connections per level
2
Nominal cross section
4 mm²
Screw thread
M3
Note
Please observe the current carrying capacity of the DIN rails.
Tightening torque
0.5 ... 0.6 Nm
Stripping length
9 mm
Internal cylindrical gage
A3
Conductor cross section rigid
0.2 mm² ... 4 mm²
Cross section AWG
24 ... 12 (converted acc. to IEC)
Conductor cross section flexible
0.2 mm² ... 4 mm²
Conductor cross section, flexible [AWG]
24 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
0.25 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
0.25 mm² ... 2.5 mm²
2 conductors with same cross section, solid
0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible
0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.25 mm² ... 0.75 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.5 mm² ... 0.75 mm²
Nominal current
24 A (with 4 mm² conductor cross section)
Maximum load current
30 A (with 4 mm² conductor cross section and 3-pos. terminal block)
Nominal voltage
400 V (phase conductor/phase conductor) 250 V (phase conductor/PE) 250 V (phase conductor/N)
Nominal cross section
4 mm²
Width
5.2 mm
End cover width
2.2 mm
Height
93.5 mm
Depth on NS 35/7,5
51.5 mm
Depth on NS 35/15
59 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)
27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Test voltage setpoint
7.3 kV
Result
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Result
Test passed
Short-time withstand current 2.5 mm²
0.3 kA
Short-time withstand current 4 mm²
0.48 kA
Result
Test passed
Test voltage setpoint
1.89 kV
Result
Test passed
Open side panel
Yes
Result
Test passed
DIN rail/fixing support
NS 35
Test force setpoint
1 N
Result
Test passed
Rotation speed
10 rpm
Revolutions
135
Conductor cross section/weight
0.2 mm² / 0.2 kg 2.5 mm² / 0.7 kg 4 mm² / 0.9 kg
Result
Test passed
Temperature cycles
192
Result
Test passed
Time of exposure
30 s
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2008-03
Spectrum
Service life test category 2, bogie-mounted
Frequency
f
ASD level
6.12 (m/s²)²/Hz
Acceleration
3.12g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Result
Test passed
Specification
DIN EN 50155 (VDE 0115-200):2008-03
Pulse shape
Half-sine
Acceleration
30g
Shock duration
18 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Result
Test passed
Ambient temperature (operation)
-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Mounting type
NS 35/7,5 NS 35/15