Rockwell Automation 140G-G2C3-C35-UJ

Selling Points

  • 11. High Interrupting Ratings: The 140G-G2C3-C35-UJ boasts an interrupting rating of 50kA at 240V and 65kA at 220-230V AC, ensuring reliable protection against short circuits.;
  • 22. Global Standards Compliance: This circuit breaker meets global standards including UL, CSA, CCC, and IEC, ensuring it is suitable for worldwide applications.;
  • 33. Thermal Magnetic Design: The thermal magnetic design provides both thermal and magnetic trip units, offering robust protection against overcurrent and short circuits.;
  • 44. Reverse-Fed Capability: Designed for reverse-fed applications, this circuit breaker can handle up to 690V AC, making it versatile for various industrial setups.;
  • 55. Compact and Reliable: With a compact design and a high mechanical life of 25,000 operations, the 140G-G2C3-C35-UJ is both reliable and space-efficient, fitting well into most panel configurations.
Product Details
140G-G2C3-C35-UJ
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Stock Status
NON_STOCKED
Dimension Length
8.6
Dimension Width
14.3
Lead Time
15
Dimension Height
13.0
Quick Turnaround
false
Preferred Availability
false
Repairable
NOT_REPAIRABLE
Ambient temperature without derating
104
Rated uninterrupted current (Iu)
98% of current rating @ 3000 m (9840 ft) altitude
Operational voltage (Ue)
90% of voltage rating @ 3000 m (9840 ft) altitude
Wire temperature rating
Cu 75 °C
Storage temperature
-40
Depth
70
Width
76.2
Device construction
Built-in device fixed built-in technique
Height
130
Factory option
Under voltage release, 24...30V AC/DC
Shock
Peak acceleration: 150 m/s2 peak, pulse duration 11 ms
Vibration
2...13.2 Hz ±1 mm, 13.2...100 Hz ±0.7 G
Mechanical life operations
25000
Weight
1.2
Degree of protection (IP)
IP40
DIN rail (top hat rail) mounting optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Screw connection
Position of connection for main current circuit
Front side
Motor drive optional
Yes
With switched-off indicator
No
Motor drive integrated
No
Rated service short-circuit breaking capacity (Ics)
IEC 60947-2: 75% lcu @ 690V AC @ 50/60Hz
Rated ultimate short-circuit breaking capacity (Icu)
IEC 60947-2: 65kA @ 220...230V AC, 50/60 Hz
Interrupting rating
50kA @ 240V, 50/60 Hz per NEMA, UL, CSA
Electrical life cycle
8000 @ 415V AC
Construction type
T/M-fixed thermal/fixed magnetic TMF
Insulation voltage (Ui)
Rated 800V per IEC
Watt loss
Thermal magnetic type: 6.0 W
Votlage for reverse-fed circuit breaker, max
690V AC per IEC
Frame size
125
Magnetic trip current (Im)
500
Thermal trip current (Ir = In (fixed))
35 A
Rated impulse withstand voltage (Uimp)
8
Type of control element
Toggle
Rated permanent current Iu
35 A
Complete device with protection unit
Yes
Integrated earth fault protection
No
With integrated under voltage release
Yes
Number of poles
3

Specifications may be subject to change without notice