Rockwell Automation 140G-H6C4-C70

Selling Points

  • 11. High Interrupting Ratings: The 140G-H6C4-C70 boasts high interrupting ratings from 18 to 100 kA, ensuring it can handle even the most demanding electrical faults in industrial settings.;
  • 22. Compact Design: With its compact design, this circuit breaker fits seamlessly into a variety of panel configurations, making it ideal for space-constrained applications.;
  • 33. Customizable Trip Units: The device offers a wide range of operating mechanisms and trip units, allowing for greater customization to fit specific panel configurations and protection needs.;
  • 44. Global Certification: Approved for global application, the 140G-H6C4-C70 meets UL, CSA, CCC, and IEC performance standards, ensuring it can be used in diverse industrial environments worldwide.;
  • 55. Current-Limiting Option: The current-limiting option (available in H, J, and K frames) provides half-cycle interrupt to limit let-through energy, reducing the risk of damage to equipment and ensuring a safer operation.
Product Details
140G-H6C4-C70
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Stock Status
NON_STOCKED
Dimension Length
22.352
Dimension Width
15.748
Lead Time
15
Dimension Height
13.335
Quick Turnaround
false
Preferred Availability
false
Repairable
NOT_REPAIRABLE
Ambient temperature without derating
104 °F
Rated uninterrupted current (Iu)
98% of current rating @ 3000 m (9840 ft) altitude
Operational voltage (Ue)
90% of voltage rating @ 3000 m (9840 ft) altitude
Wire temperature rating
Cu 75 °C
Storage temperature
-40 °F
Depth
82.5 mm
Width
120 mm
Device construction
Built-in device fixed built-in technique
Height
130 mm
Factory option
None
Shock
Peak acceleration: 150 m/s2 peak, pulse duration 11 ms
Vibration
2...13.2 Hz ±1 mm, 13.2...100 Hz ±0.7 G
Mechanical life operations
25000 /h
Weight
2.127
Degree of protection (IP)
IP40
DIN rail (top hat rail) mounting optional
True
Suitable for DIN rail (top hat rail) mounting
False
Type of electrical connection of main circuit
Screw connection
Position of connection for main current circuit
Front side
Motor drive optional
True
With switched-off indicator
False
Motor drive integrated
False
Protection type
T/M-fixed thermal/fixed magnetic TMF
Rated service short-circuit breaking capacity (Ics)
IEC 60947-2: 100% lcu @ 500V DC, 3-poles in series, thermal-magnetic trip unit only
Rated ultimate short-circuit breaking capacity (Icu)
IEC 60947-2: 70kA @ 500V DC, 3-poles in series, thermal-magnetic trip unit only
Interrupting rating
65kA @ 480V AC, 50/60 Hz per NEMA, UL, CSA
Electrical life cycle
8000 @ 415V AC
Thermal trip rating, max
70 A @ ambient temperature 40 °C
Insulation voltage (Ui)
Rated 1000V per IEC
Watt loss
Thermal magnetic type: 17.8 W
Voltage for reverse-fed circuit breaker, max
480V AC per UL/CSA
Thermal trip current (Ir)
70 A
Magnetic trip current (Im)
700 A
Frame size
125 A
Rated impulse withstand voltage (Uimp)
8 kV
Type of control element
Toggle
Rated permanent current Iu
70 A
Complete device with protection unit
True
Integrated earth fault protection
False
With integrated under voltage release
False
Number of poles
4

Specifications may be subject to change without notice